3-Years Energetic and Economic Analysis of a 30kWp Rooftop PV Power Plant

30kWp Çatı Tipi PV Santralinin 3 Yıllık Enerjik ve Ekonomik Analizi

Pages
175–194
Publication Date
2023-04-04
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

The price of electricity injected and consumed was calculated according to the FIT conditions at the time the system was installed, and the payback period was calculated as approximately 6 years.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:A 30 kWp rooftop solar photovoltaic (PV) power plant was modelled using energy balance equations, 3-year energy production and its economic return is calculated according to the feed-in tariff agreement.
📊
Key Findings & Data:The system generated 45.35 MWh, 47.05 MWh and 46.34 MWh of energy in year 1, 2 and 3, respectively.
💡
Conclusion & Impact:The price of electricity injected and consumed was calculated according to the FIT conditions at the time the system was installed, and the payback period was calculated as approximately 6 years.
🔬Design:Modeling & Simulation
📍Scope:Comprehensive Sample
⚙️Variables:Photovoltaic · rooftop PV · performance assessment

Abstract

A 30 kWp rooftop solar photovoltaic (PV) power plant was modelled using energy balance equations, 3-year energy production and its economic return is calculated according to the feed-in tariff agreement. Hourly measured electricity generation and Excel spreadsheet simulation results were closely compatible. The system generated 45.35 MWh, 47.05 MWh and 46.34 MWh of energy in year 1, 2 and 3, respectively. It has been observed that the performance ratio of the PV system varies between 84.50 % and 90.27 %, while the capacity factor varies between 17.26 % and 17.63%. While 93.90 MWh of electrical energy has been injected into the grid over a 3-year period, 46.40 MWh of energy has been taken from the grid. The price of electricity injected and consumed was calculated according to the FIT conditions at the time the system was installed, and the payback period was calculated as approximately 6 years.

Özet

30 kWp'lik bir çatı üstü fotovoltaik (FV) güneş enerji santrali, enerji dengesi denklemleri kullanılarak modellenmiş ve 3 yıllık enerji üretimi ile ekonomik getirisi kurulduğu gündeki tarife anlaşmasına göre hesaplanmıştır. Excel’de yapılan modelleme ve benzetim sonuçları ile sistemden saatlik bazda ölçülen elektrik üretimi verilerinin oldukça uyumlu olduğu görülmüştür. Sistem 1., 2. ve 3. yılda sırasıyla 45,35 MWh, 47,05 MWh ve 46,34 MWh enerji üretmiştir. FV sistemin performans oranının %84,50 ile %90,27 arasında değişirken, kapasite faktörünün de %17,26 ile %17,63 arasında değiştiği gözlemlenmiştir. 3 yılda üretim fazlası olarak 93,90 MWh elektrik enerjisi şebekeye verilirken, şebekeden 46,40 MWh enerji çekilmiştir. Enjekte edilen ve tüketilen elektriğin bedeli, sistemin kurulduğu andaki bağlantı anlaşması koşullarına göre hesaplanmış ve geri ödeme süresi yaklaşık 6 yıl olarak bulunmuştur.

🔖

Cite This Article

ATEŞ, A. M. (2023). 3-Years Energetic and Economic Analysis of a 30kWp Rooftop PV Power Plant. Mühendis ve Makina, Cilt: 64 - Sayı: 710, 175–194. https://ajindex.com/articles/887965

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (11)

  1. Adaramola, M. S. (2015). Techno-economic analysis of a 2.1 kW rooftop photovoltaic-grid-tied system based on actual performance. Energy Conversion and Management, 101, 85–93. https://doi.org/10.1016/j.enconman.2015.05.038
  2. Adaramola, M. S., & Vågnes, E. E. T. (2015). Preliminary assessment of a small-scale rooftop PV-grid tied in Norwegian climatic conditions. Energy Conversion and Management, 90 (2015), 458–465. https://doi.org/10.1016/j.enconman.2014.11.028
  3. Al-Otaibi, A., Al-Qattan, A., Fairouz, F., & Al-Mulla, A. (2015). Performance evaluation of photovoltaic systems on Kuwaiti schools’ rooftop. Energy Conversion and Management, 95, 110–119. https://doi.org/10.1016/j.enconman.2015.02.039
  4. Ates, A. M., & Singh, H. (2021). Rooftop solar Photovoltaic (PV) plant – One year measured performance and simulations. Journal of King Saud University - Science, 33(3), 101361. https://doi.org/10.1016/j.jksus.2021.101361
  5. Ates, A. M., Yilmaz, O. S., & Gulgen, F. (2020). Using remote sensing to calculate floating photovoltaic technical potential of a dam’s surface. Sustainable Energy Technologies and Assessments, 41(July), 100799. https://doi.org/10.1016/j.seta.2020.100799
  6. Attari, K., Elyaakoubi, A., & Asselman, A. (2016). Performance analysis and investigation of a grid-connected photovoltaic installation in Morocco. Energy Reports, 2 (December 2015), 261–266. https://doi.org/10.1016/j.egyr.2016.10.004
  7. Ayompe, L. M., Duffy, A., McCormack, S. J., & Conlon, M. (2011). Measured performance of a 1.72 kW rooftop grid connected photovoltaic system in Ireland. Energy Conversion and Management, 52(2), 816–825. https://doi.org/10.1016/j.enconman.2010.08.007
  8. BP. (2019). Statistical Rewiev of World Energy. London, UK. Cherfa, F., Hadj Arab, A., Oussaid, R., Abdeladim, K., Bouchakour, S., Arab, A. H., … Bouchakour, S. (2015). Performance Analysis of the Mini-grid Connected Photovoltaic System at Algiers. Energy Procedia, 83, 226–236. https://doi.org/10.1016/j.egypro.2015.12.177
  9. Cole, R. J., & Sturrock, N. S. (1977). The convective heat exchange at the external surface of buildings. Building and Environment, 12 (4), 207–214. https://doi.org/https://doi.org/10.1016/0360-1323(77)90021-X
  10. Cory, K., Couture, T., & Kreycik, C. (2009). Feed-in Tariff Policy: Design, Implementation, and RPS Policy Interactions. United States. https://doi.org/10.2172/951016
  11. Couture, T. D., Cory, K., Kreycik, C., & Williams, E. (2010). Policymaker’s Guide to Feed-in Tariff Policy Design. United States. https:/