Investigation on Current Control Defrosting Method of Multi-split Variable Refrigerant Flow System

Pages
235–243
Publication Date
2020-11-27
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

The phenomenon of thermosensor falling off and the uneven frost formation had little impact on the current control defrosting.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:There are many indoor units in the multi-split variable refrigerant flow (VRF) system.
📊
Key Findings & Data:In this paper, during the experiment, the indoor temperature was 20℃, the outdoor dry bulb temperature was 7℃, 0℃, -5℃ and -7℃, and the wet bulb temperature was 6℃, 0℃, -6℃ and -8℃ respectively.
💡
Conclusion & Impact:The phenomenon of thermosensor falling off and the uneven frost formation had little impact on the current control defrosting.
🔬Design:Research Article
📍Scope:Comprehensive Sample
⚙️Variables:VRF · defrosting · current control

Abstract

There are many indoor units in the multi-split variable refrigerant flow (VRF) system. The continuous operation of heating in winter is longer than that of ordinary household air conditioning, so that the precise defrosting control is energy-saving and improves the comfort for users. In this paper, during the experiment, the indoor temperature was 20℃, the outdoor dry bulb temperature was 7℃, 0℃, -5℃ and -7℃, and the wet bulb temperature was 6℃, 0℃, -6℃ and -8℃ respectively. The defrosting temperature, liquid pipe temperature, defrosting time and the current value change rate of the condenser fan were compared when the heating capacity was reduced by 15%. The experiments showed that the current change rate was little affected by the outdoor temperature. It was only related to the frost mass, which could reflect the real frosting situation. Then through the maximum cycle heating capacity, air supply temperature and capacity decay rate, the most reasonable defrosting time could be seen when the fan current change rate was 15% - 20%. Compared with the traditional defrosting, the current control defrosting had a higher heating capacity. Under the four working conditions, the heating cycle capacity was increased by 2.3%, 4%, 2.8% and 5.8% in turn. At the same time, the control was precise. The phenomenon of thermosensor falling off and the uneven frost formation had little impact on the current control defrosting.

🔖

Cite This Article

LİU, M., LİU, H., WANG, M., CHEN, H. (2020). Investigation on Current Control Defrosting Method of Multi-split Variable Refrigerant Flow System. International Journal of Thermodynamics, Cilt: 23 - Sayı: 4, 235–243. https://ajindex.com/articles/673436

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (14)

  1. P. Byrne, J. Miriel, Y. Lenat, “Experimental study of an air-source heat pump for simultaneous heating and cooling – Part 2: Dynamic behaviour and two-phase thermosiphon defrosting technique,” Appl. Energy, 88, 3072-3078, 2011
  2. M. Wang, R. Q. Zang, E. Hu, A. W. Ezzat, “Investigation of air cooler fan start-up delay in liquid refrigerant defrosting system,” Appl. Therm. Eng., 143, 302-307, 2018
  3. M. L. Qu, L. Xia, S. M. Deng, Y. Q. Jiang, “A study of the reverse cycle defrosting performance on a multi-circuit outdoor coil unit in an air source heat pump – Part I: Experiments,” Appl. Energy, 91, 122-129, 2012
  4. K. Laeun, H. Yunho, R. Reinhard, K. Byungsoon, “Field performance measurements of a VRF system with sub-cooler in educational offices for the cooling season,” Energy and Buildings, 49, 300-305, 2012
  5. T. N. Aynur, “Variable refrigerant flow systems: A review,” Energy and Buildings, 42, 1106-1112, 2010
  6. B. Shen, C. K. Rice, “Multiple-zone variable refrigerant flow system modeling and equipment performance mapping,” Ashrae Transactions, 118, 420-427, 2012
  7. P. Parida, F. H. Mei, J. Jiang, W. J. Meng, S. V. Ekkad, “Experimental investigation of cooling performance of metal-based microchannels,” Heat Transfer Eng., 31, 485-494, 2010
  8. S. A. Tassou, D. Datta, D. Marriott, “Frost formation and defrost control parameters for open multideck refrigerated food display cabinets,” Proceedings of the Institution of Mechanical Engineers Part A Journal of Power & Energy, 215, 213-222, 2001
  9. J. Xiao, W. Wang, Y. H. Zhao, F. R. Zhang, “An analysis of the feasibility and characteristics of photoelectric technique applied in defrost-control,” Int. J. Refrig., 32, 1350-1357, 2009
  10. Z. Y. Wang, H. X. Yang, S. Chen, “Study on the operating performance of cross hot-gas bypass defrosting system for air-to-water screw heat pumps,” Appl. Therm. Eng., 59, 398-404, 2013
  11. K. M. Hwan, L. K. Soo, “Determination method of defrosting start-time based on temperature measurements,” Appl. Energy, 146, 263-269, 2015
  12. W. Wang, J. Xiao, Y. Feng, Q. Guo, L. Wang, “Characteristics of an air source heat pump with novel photoelectric sensors during periodic frost–defrost cycles,” Appl. Therm. Eng., 50, 177-186, 2013
  13. M. J. Song, X. J. Wang, L. Y. Liao, S. M. Deng, “Termination Control Temperature Study for an Air Source Heat Pump Unit During Its Reverse Cycle Defrosting,” Energy Procedia, 105, 335-342, 2017
  14. Y. Q. Jiang, J. K. Dong, M. L.