Journals / International Advanced Researches and Engineering Journal / 2021 / Cilt: 5 - Sayı: 2

Experimental investigation of the effects of different refrigerants used in the refrigeration system on compressor vibrations and noise

Pages
152–162
Publication Date
2022-10-19
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

Generally, it was observed that the noise and vibration values are very close to each other for all refrigerants examined.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:Vibration and noise are undesirable effects in daily life and energy-consuming systems.
📊
Key Findings & Data:The study compared the noise and vibration performances of refrigerants with lower ozone depletion potential (ODP) values compared to R22, which has a high ODP value.
💡
Conclusion & Impact:Generally, it was observed that the noise and vibration values are very close to each other for all refrigerants examined.
🔬Design:Research Article
📍Scope:Comprehensive Sample
⚙️Variables:Alternative refrigerants · Noise · Vibration

Abstract

Vibration and noise are undesirable effects in daily life and energy-consuming systems. In this study, the effects of different refrigerants on noise and vibration in a sealed reciprocating compressor are discussed. The study compared the noise and vibration performances of refrigerants with lower ozone depletion potential (ODP) values compared to R22, which has a high ODP value. The study was carried out experimentally in two stages. Firstly, tests were conducted for the coefficient of performance (COP) of different refrigerants. Secondly, vibration and noise data were obtained experimentally for different refrigerants. The results obtained from the experiments showed that both the COP value and the compressor vibration and noise have different values for R22 refrigerant and other alternative refrigerants, but values close to R22 are obtained. It was observed that the compressor noise values and vibration values vary depending on the type of used refrigerant. Average vibration values were determined as 0.604 m/s2 in R22, 0.603 m/s2 in R438A, 0.593 m/s2 in R417A, 0.622 m/s2 in R422D and 0.637 m/s2 in R422A. When the noise values are examined, it was measured as 61.327 dB for R22, 62.913 dB for R438A, 62.187 dB for R417A, 63.715 dB for R422D and 64.913 dB for R422A. R417A, which has a 99% similar noise value to R22, was determined as an alternative refrigerant. COP values were found as 4.07 in R22, 3.98 in R438A, 3.63 in R417A, 3.37 in R422D, and 3.18 in R422A. R438A showing 95% similarity for COP can be used as an alternative to R22. Generally, it was observed that the noise and vibration values are very close to each other for all refrigerants examined.

🔖

Cite This Article

ÇAY, Y., KATIRCIOĞLU, F., CİNGİZ, Z., YILDIZ, G., SARIDEMİR, S. (2022). Experimental investigation of the effects of different refrigerants used in the refrigeration system on compressor vibrations and noise. International Advanced Researches and Engineering Journal, Cilt: 5 - Sayı: 2, 152–162. https://ajindex.com/articles/539308

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (14)

  1. Ceylan, İ., G. Yıldız, A. E. Gürel, A. Ergün, and A. Tosun, The effect of malfunctions in air handling units on energy and exergy efficiency. Heat Transfer Research, 2020. 51(11): 1007-1028
  2. United Nations Development Programme UNDP. "20 years of success: Montreal protocol on substances that deplete the ozone layer.," [cited 2020 29 October]; Available from: http://www un.org. kh/undp/knowledge/publications/20-years-of-success-montreal-protocol-on-substances-that deplete-the-ozone-layer-2
  3. Li, W. L., and V. Eyo, Dynamic Analysis of a Compressor Mounting System. International Compressor Engineering Conference, 1996
  4. Hamilton, J. F., Measurement and control of compressor noise, West Lafayette, Purdue University, USA, 1988
  5. Celik, S., and E. C. Nsofor, Studies on the flow-induced noise at the evaporator of a refrigerating system. Applied Thermal Engineering, 2011. 31(14-15): p. 2485-2493
  6. Lee, C., Y. Cho, B. Baek, S. Lee, D. Hwang, and K. Jo, Analyses of refrigerator noises. In Proceedings of the IEEE International Symposium on Industrial Electronics, 2005: p. 1179-1184
  7. Han, H. S., W. B. Jeong, M. S. Kim, and T. H. Kim, Analysis of the root causes of refrigerant-induced noise in refrigerators. Journal of Mechanical Science and Technology, 2009. 23(12): p. 3245-3256
  8. Han, H. S., W. B. Jeong, M. S. Kim, S. Y. Lee, and M. Y. Seo, Reduction of the refrigerant-induced noise from the evaporator-inlet pipe in a refrigerator. International Journal of Refrigeration, 2010. 33(7): p. 1478-1488
  9. Jang, S., Choung, H., Park, S., and Lee, S. Investigation on noise of rotary compressors using fluid-structure interaction. Journal of Mechanical Science and Technology, 2019. 33(11): p. 5129-5135
  10. Venkatappa, S., M. Koberstein, and Z. Liu, NVH Challenges with Introduction of New Refrigerant HFO-1234yf. SAE Technical Paper, 2017. (2017-01-0172
  11. Xia, Y., Y. Liu, Y. Liu, Y. Ma, C. Xiao, and T. Wu, Experimental study on reducing the noise of horizontal household freezers. Applied Thermal Engineering, 2014. 68(1-2): p. 107-114
  12. Jeon, J. Y., J. You, and H. Y. Chang, Sound radiation and sound quality characteristics of refrigerator noise in real living environments. Applied Acoustics, 2007. 68(10): p. 1118-1134
  13. Berry, B. F., The work of I-INCE Technical Study Group 2 on noise labels for consumer and industrial products. Noise and Health, 2003. 5(18): p. 21
  14. Kim, K. M., Study of efficiency and noise improvement in a reciprocating compres