Evaluation of the Safety Performance of a 500-kV AC Substation Grounding Using IEEE Standard 80-2013

Journal
Electrica
Pages
225–234
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

To achieve this purpose, ahigh-resistivity surface material is recommended by IEEE Standard 80-2013, which defines the methodology to calculate safety parameters, including touchpotential and step potential, considering the presence of a high-resistivity material such as gravel in the grid station, including raceways.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:The fundamental purpose of grounding electrical power systems and substations is to ensure safety of equipment and workers.
📊
Key Findings & Data:To achieve this purpose, ahigh-resistivity surface material is recommended by IEEE Standard 80-2013, which defines the methodology to calculate safety parameters, including touchpotential and step potential, considering the presence of a high-resistivity material such as gravel in the grid station, including raceways.
💡
Conclusion & Impact:This is followed by the proposal andvalidation, through simulations, of a cost-effective, non-intrusive, and environmentally friendly solution by recycling old tires as surface material.
🔬Design:Research Article
📍Scope:2013 Verileri
⚙️Variables:Domain Parameters

Özet

The fundamental purpose of grounding electrical power systems and substations is to ensure safety of equipment and workers. To achieve this purpose, ahigh-resistivity surface material is recommended by IEEE Standard 80-2013, which defines the methodology to calculate safety parameters, including touchpotential and step potential, considering the presence of a high-resistivity material such as gravel in the grid station, including raceways. However, concrete isgenerally used for raceway construction, whereas gravel material is used for constructing switch yards. As the resistivity of concrete is far less than gravel, thispractice may lead to injury and even death, because workers and visitors walk on these pathways. This study conducted the safety analysis of concrete usedas surface material. After the collection of data from an operational 500-kV grid station at Nokhar, Pakistan, simulations and analyses were performed usingthe Electrical Transient Analyzer Program software using IEEE Standard 80-2013. The results indicate that the use of concrete poses a considerable threat toequipment and personnel safety, because the measured values of touch and step potential exceed standard values. This is followed by the proposal andvalidation, through simulations, of a cost-effective, non-intrusive, and environmentally friendly solution by recycling old tires as surface material.

🔖

Cite This Article

FAROOQ, H., ALİ, W., IQBAL, H., RASOOL, A., SAJJAD, I. A., NOON, A. A. (2021). Evaluation of the Safety Performance of a 500-kV AC Substation Grounding Using IEEE Standard 80-2013. Electrica, Cilt: 21 - Sayı: 2, 225–234. https://ajindex.com/articles/348145

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (2)

  1. “IEEE guide of safety in ac substation grounding”, IEEE Standard 80-2013, May, 2015. 2. H. Khodr, G. Salloum, J. Saraiva, M. Matos, “Design of grounding systems in substations using a mixed-integer linear programming formulation”, Electric Power Systems Research, vol. 79, no. 1, pp. 126-133, january, 2009. [Crossref] 3. S.B. Mladen, “Line arresters application in lightning protection of high voltage substations with non-standard configuration”, Electric Power Components and Systems, vol. 45, no. 11, pp.1173- 1181, July, 2017. 4. M.U. Aslam, M.U. Cheema, M.B. Cheema, M. Samran, “Design analysis and optimization of ground grid mesh of extra high voltage substation using an intelligent software”, 1st International Conference of Information Technology, Computer and Electrical Engineering, November, 2014,
  2. Semarang, Indonesia. [Crossref] 5. N. Mohamad, R. Jamal, N. Mahmood, H. Ali, “Substation and transmission lines earthing system design under substation fault”, Electric Power Components and Systems, vol. 43, no. 18, pp. 2010- 2018, September, 2015. [Crossref] 6. G. Pesse, C.D. Di, “Interaction by earth between grounding grids of systems responsible for emitting and receiving current”, V Congreso de Generación y Transmisión de Energía Eléctrica, 1989. 7. L.M. Popovic LM, “Efficient reduction of fault current through the grounding grid of substation supplied by cable line”, IEEE Transactions on Power Delivery, vol. 15, no. 2, pp.:556-561, April, 2000. [Crossref] 8. E. Bendito, A. Carmona, A.M. Encinas, M.J. Jimenez, “The external charges method in grounding grid design”, IEEE Transactions on Power Delivery, vol. 17, no. 1, pp. 118-123, January, 2004. [Crossref] 9. N.H.C. Santiago, A.E.A. Araujo, H.W. Dommel, “Evaluation of maximum ground grid currents with the EMTP”, Electric Power Components and Systems, vol. 30, no. 3, pp. 251-261. November, 2010. [Crossref] 10. A. Ackerman, P. Sen, C. Oertli, “Designing safe and reliable grounding in AC substations with poor soil resistivity: an interpretation of IEEE Std. 80”, IEEE Transactions on Industry Applications, vo. 49, no. 4, pp. 1883-1889, July, 2013. [Crossref] 11. “IEEE guide for measuring earth resistivity, ground impedance, and earth surface potentials of a grounding system”, IEEE Standard 81-2012, December, 2012. 12. “IEEE guide for measurement of impedance and safety characteristics of large, extended or interconnected grounding systems”, IEEE Standard 81.2-1991, June, 1992. 13. “IEEE standard for qualify