Evaluation of the Safety Performance of a 500-kV AC Substation Grounding Using IEEE Standard 80-2013

Sayfa
225–234
DOI
—
🏛️Bu makalenin bibliyografik verileri ve tam metin bağlantısı DergiPark üzerinden sağlanmıştır.
DergiPark Kaydı ↗
✨

Yapay Zeka Hızlı Bakış & Çıkarımlar

AI Insight
⚡ TL;DR(1 Cümlede Hızlı Çıkarım)

This is followed by the proposal andvalidation, through simulations, of a cost-effective, non-intrusive, and environmentally friendly solution by recycling old tires as surface material.

📌 3 Maddede Bu Makale

🎯
Amaç & Hipotez:The fundamental purpose of grounding electrical power systems and substations is to ensure safety of equipment and workers.
📊
Temel Bulgular & Veri:To achieve this purpose, ahigh-resistivity surface material is recommended by IEEE Standard 80-2013, which defines the methodology to calculate safety parameters, including touchpotential and step potential, considering the presence of a high-resistivity material such as gravel in the grid station, including raceways.
💡
Sonuç & Katkı:This is followed by the proposal andvalidation, through simulations, of a cost-effective, non-intrusive, and environmentally friendly solution by recycling old tires as surface material.
🔬Tür:Araştırma Makalesi
📍Kapsam:2013 Verileri
⚙️Değişkenler:Alan Parametreleri

Özet

The fundamental purpose of grounding electrical power systems and substations is to ensure safety of equipment and workers. To achieve this purpose, ahigh-resistivity surface material is recommended by IEEE Standard 80-2013, which defines the methodology to calculate safety parameters, including touchpotential and step potential, considering the presence of a high-resistivity material such as gravel in the grid station, including raceways. However, concrete isgenerally used for raceway construction, whereas gravel material is used for constructing switch yards. As the resistivity of concrete is far less than gravel, thispractice may lead to injury and even death, because workers and visitors walk on these pathways. This study conducted the safety analysis of concrete usedas surface material. After the collection of data from an operational 500-kV grid station at Nokhar, Pakistan, simulations and analyses were performed usingthe Electrical Transient Analyzer Program software using IEEE Standard 80-2013. The results indicate that the use of concrete poses a considerable threat toequipment and personnel safety, because the measured values of touch and step potential exceed standard values. This is followed by the proposal andvalidation, through simulations, of a cost-effective, non-intrusive, and environmentally friendly solution by recycling old tires as surface material.

🔖

Bu Makaleye Atıf Yap

FAROOQ, H., ALİ, W., IQBAL, H., RASOOL, A., SAJJAD, I. A., NOON, A. A. (2021). Evaluation of the Safety Performance of a 500-kV AC Substation Grounding Using IEEE Standard 80-2013. Electrica, Cilt: 21 - Sayı: 2, 225–234. https://ajindex.com/articles/348145

📄 Tam Metin PDF Okuyucu

📄

PDF görüntüleyici hazırlanıyor...

Kaynakça (2)

  1. “IEEE guide of safety in ac substation grounding”, IEEE Standard 80-2013, May, 2015. 2. H. Khodr, G. Salloum, J. Saraiva, M. Matos, “Design of grounding systems in substations using a mixed-integer linear programming formulation”, Electric Power Systems Research, vol. 79, no. 1, pp. 126-133, january, 2009. [Crossref] 3. S.B. Mladen, “Line arresters application in lightning protection of high voltage substations with non-standard configuration”, Electric Power Components and Systems, vol. 45, no. 11, pp.1173- 1181, July, 2017. 4. M.U. Aslam, M.U. Cheema, M.B. Cheema, M. Samran, “Design analysis and optimization of ground grid mesh of extra high voltage substation using an intelligent software”, 1st International Conference of Information Technology, Computer and Electrical Engineering, November, 2014,
  2. Semarang, Indonesia. [Crossref] 5. N. Mohamad, R. Jamal, N. Mahmood, H. Ali, “Substation and transmission lines earthing system design under substation fault”, Electric Power Components and Systems, vol. 43, no. 18, pp. 2010- 2018, September, 2015. [Crossref] 6. G. Pesse, C.D. Di, “Interaction by earth between grounding grids of systems responsible for emitting and receiving current”, V Congreso de Generación y Transmisión de Energía Eléctrica, 1989. 7. L.M. Popovic LM, “Efficient reduction of fault current through the grounding grid of substation supplied by cable line”, IEEE Transactions on Power Delivery, vol. 15, no. 2, pp.:556-561, April, 2000. [Crossref] 8. E. Bendito, A. Carmona, A.M. Encinas, M.J. Jimenez, “The external charges method in grounding grid design”, IEEE Transactions on Power Delivery, vol. 17, no. 1, pp. 118-123, January, 2004. [Crossref] 9. N.H.C. Santiago, A.E.A. Araujo, H.W. Dommel, “Evaluation of maximum ground grid currents with the EMTP”, Electric Power Components and Systems, vol. 30, no. 3, pp. 251-261. November, 2010. [Crossref] 10. A. Ackerman, P. Sen, C. Oertli, “Designing safe and reliable grounding in AC substations with poor soil resistivity: an interpretation of IEEE Std. 80”, IEEE Transactions on Industry Applications, vo. 49, no. 4, pp. 1883-1889, July, 2013. [Crossref] 11. “IEEE guide for measuring earth resistivity, ground impedance, and earth surface potentials of a grounding system”, IEEE Standard 81-2012, December, 2012. 12. “IEEE guide for measurement of impedance and safety characteristics of large, extended or interconnected grounding systems”, IEEE Standard 81.2-1991, June, 1992. 13. “IEEE standard for qualify