Data-Driven Validation and Correction of the Distortion Factor Estimated from Current Total Harmonic Distortion Using Industrial Field Measurements

Faruk Kürker(ADIYAMAN ÜNİVERSİTESİ)0000-0003-1544-9743
Ramazan Taşaltın(KAHRAMANMARAS SUTCU IMAM UNIVERSITY)0000-0003-2026-2430
Pages
2639–2651
Publication Date
2026-09-15
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

The results show that the THDI-based formula provides an interpretable initial estimate but cannot, on its own, account for field conditions such as phase asymmetry, load level, power factor, and voltage distortion.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:In this study, the validity of the theoretical distortion factor based on total harmonic distortion of current (THDI) under industrial field conditions was evaluated, and low-complexity, data-driven correction models were developed to reduce formula error.
📊
Key Findings & Data:The dataset was compiled from three-phase field measurements at 12 industrial measurement points.
💡
Conclusion & Impact:The results show that the THDI-based formula provides an interpretable initial estimate but cannot, on its own, account for field conditions such as phase asymmetry, load level, power factor, and voltage distortion.
🔬Design:Modeling & Simulation
📍Scope:Comprehensive Sample
⚙️Variables:Distortion factor · Total harmonic distortion of current · Power factor

Abstract

In this study, the validity of the theoretical distortion factor based on total harmonic distortion of current (THDI) under industrial field conditions was evaluated, and low-complexity, data-driven correction models were developed to reduce formula error. The dataset was compiled from three-phase field measurements at 12 industrial measurement points. The measurement-based distortion factor was calculated from the PF/dPF ratio, while the theoretical distortion factor was calculated from the THDI-based equation. Since the phases at the same measurement point were not considered independent, the models were evaluated using a 12-cycle out-of-sample cross-validation method. The theoretical formula produced a mean absolute error of 0.015662, a root mean square error of 0.019681, and a mean bias of −0.009357. Among the compared models, restricted second-order regression produced the lowest error values, providing improvements of 31.83% and 15.70% in MAE and RMSE, respectively. Ridge regression, on the other hand, reduced the MAE to 0.012263 and brought the mean bias close to zero. However, the data-driven models did not reduce the maximum absolute error. At the measurement-point level, the Wilcoxon signed-rank test indicated lower paired errors after Ridge correction (P=0.0342), whereas the 95% bootstrap confidence interval for the mean paired MAE difference included zero. Taken together, these findings provide positive but limited evidence regarding the error-reduction potential of the Ridge correction. The results show that the THDI-based formula provides an interpretable initial estimate but cannot, on its own, account for field conditions such as phase asymmetry, load level, power factor, and voltage distortion. The proposed correction approach should be considered not as a universal formula but as an empirical calibration approach specific to the available field data.

Özet

In this study, the validity of the theoretical distortion factor based on total harmonic distortion of current (THDI) under industrial field conditions was evaluated, and low-complexity, data-driven correction models were developed to reduce formula error. The dataset was compiled from three-phase field measurements at 12 industrial measurement points. The measurement-based distortion factor was calculated from the PF/dPF ratio, while the theoretical distortion factor was calculated from the THDI-based equation. Since the phases at the same measurement point were not considered independent, the models were evaluated using a 12-cycle out-of-sample cross-validation method. The theoretical formula produced a mean absolute error of 0.015662, a root mean square error of 0.019681, and a mean bias of −0.009357. Among the compared models, restricted second-order regression produced the lowest error values, providing improvements of 31.83% and 15.70% in MAE and RMSE, respectively. Ridge regression, on the other hand, reduced the MAE to 0.012263 and brought the mean bias close to zero. However, the data-driven models did not reduce the maximum absolute error. At the measurement-point level, the Wilcoxon signed-rank test indicated lower paired errors after Ridge correction (P=0.0342), whereas the 95% bootstrap confidence interval for the mean paired MAE difference included zero. Taken together, these findings provide positive but limited evidence regarding the error-reduction potential of the Ridge correction. The results show that the THDI-based formula provides an interpretable initial estimate but cannot, on its own, account for field conditions such as phase asymmetry, load level, power factor, and voltage distortion. The proposed correction approach should be considered not as a universal formula but as an empirical calibration approach specific to the available field data.

🔖

Cite This Article

Kürker, F., Taşaltın, R. (2026). Data-Driven Validation and Correction of the Distortion Factor Estimated from Current Total Harmonic Distortion Using Industrial Field Measurements. Black Sea Journal of Engineering and Science, Cilt: 9 Sayı: 5, 2639–2651. https://doi.org/10.34248/bsengineering.1997953

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (24)

  1. Bland, J. M., & Altman, D. G. (1986). Statistical methods for assessing agreement between two methods of clinical measurement. The Lancet, 1(8476), 307–310. https://doi.org/10.1016/S0140-6736(86)90837-8
  2. Coelho, R. A., Araújo, B. V. S., Xavier, G. V. R., Rodrigues, G. A., Ferreira, T. V., & Brito, N. S. D. (2024). Novel indices for power quality assessment of non-linear loads. Electric Power Systems Research, 236, Article 110952. https://doi.org/10.1016/j.epsr.2024.110952
  3. Czarnecki, L. S. (1987). What is wrong with the Budeanu concept of reactive and distortion power and why it should be abandoned. IEEE Transactions on Instrumentation and Measurement, 36(3), 834–837. https://doi.org/10.1109/TIM.1987.6312797
  4. Efron, B. (1979). Bootstrap methods: Another look at the jackknife. The Annals of Statistics, 7(1), 1–26. https://doi.org/10.1214/aos/1176344552
  5. Emanuel, A. E. (2004). Summary of IEEE Standard 1459: Definitions for the measurement of electric power quantities under sinusoidal, nonsinusoidal, balanced, or unbalanced conditions. IEEE Transactions on Industry Applications, 40(3), 869–876. https://doi.org/10.1109/TIA.2004.827452
  6. Ferrero, A., & Superti-Furga, G. (1991). A new approach to the definition of power components in three-phase systems under nonsinusoidal conditions. IEEE Transactions on Instrumentation and Measurement, 40(3), 568–577. https://doi.org/10.1109/19.87021
  7. Hoerl, A. E., & Kennard, R. W. (1970). Ridge regression: Biased estimation for nonorthogonal problems. Technometrics, 12(1), 55–67. https://doi.org/10.1080/00401706.1970.10488634
  8. Hu, Z., Han, Y., Zalhaf, A. S., Zhou, S., Zhao, E., & Yang, P. (2023). Harmonic sources modeling and characterization in modern power systems: A comprehensive overview. Electric Power Systems Research, 218, Article 109234. https://doi.org/10.1016/j.epsr.2023.109234
  9. IEEE. (2022). IEEE standard for harmonic control in electric power systems (IEEE Std 519-2022). Institute of Electrical and Electronics Engineers.
  10. IEEE. (2025). IEEE standard definitions for the measurement of electric power quantities under sinusoidal, nonsinusoidal, balanced, or unbalanced conditions (IEEE Std 1459-2025). Institute of Electrical and Electronics Engineers.
  11. IEC. (2009). Electromagnetic compatibility (EMC)—Part 4-7: Testing and measurement techniques—General guide on harmonics and interharmonics measurements and instrumentation, for power supply systems and equipment connected thereto (IEC 61000-4-7:2002+AMD1:2008 CSV). International Electrotechnical Commission.
  12. IEC. (2025). Electromagnetic compatibility (EMC)—Part 4-30: Testing and measurement techniques—Power quality measurement methods (IEC 61000-4-30:2025). International Electrotechnical Commission.
  13. Kürker, F. (2017). Enerji sistemlerinde harmonik analizi ve harmonik azaltma teknikleri [Harmonic analysis and harmonic mitigation techniques in energy systems] (Publication No. 468305) [Doctoral dissertation, Harran University]. YÖK Tez Merkezi.
  14. Liu, Q., Liu, F., Li, Y., & Wang, S. (2023). Harmonic modeling and harmonic contribution determination: A case study of industrial power supply system. Electric Power Systems Research, 217, Article 109122. https://doi.org/10.1016/j.epsr.2023.109122
  15. Michalec, Ł., Jasiński, M., Sikorski, T., Leonowicz, Z., Jasiński, Ł., & Suresh, V. (2021). Impact of harmonic currents of nonlinear loads on power quality of a low voltage network—Review and case study. Energies, 14(12), Article 3665. https://doi.org/10.3390/en14123665
  16. Nascimento, C. F., de Oliveira, A. A., Jr., Goedtel, A., & Dietrich, A. B. (2013). Harmonic distortion monitoring for nonlinear loads using neural-network-method. Applied Soft Computing, 13(1), 475–482. https://doi.org/10.1016/j.asoc.2012.08.043
  17. Nur, A., Güre, B., Rüstemli, S., & Bezek Güre, Ö. (2025). Wind speed prediction in microgrid energy management using the random forest and artificial neural networks methods. Middle East Journal of Science, 11(2), 276–289. https://doi.org/10.51477/mejs.1738993
  18. Obulesu, Y. P., Venkateswara Reddy, M., & Kusumalatha, Y. (2014). A %THD analysis of industrial power distribution systems with active power filter—Case studies. International Journal of Electrical Power & Energy Systems, 60, 107–120. https://doi.org/10.1016/j.ijepes.2014.02.037
  19. Roberts, D. R., Bahn, V., Ciuti, S., Boyce, M. S., Elith, J., Guillera-Arroita, G., Hauenstein, S., Lahoz-Monfort, J. J., Schröder, B., Thuiller, W., Warton, D. I., Wintle, B. A., Hartig, F., & Dormann, C. F. (2017). Cross-validation strategies for data with temporal, spatial, hierarchical, or phylogenetic structure. Ecography, 40(8), 913–929. https://doi.org/10.1111/ecog.02881
  20. Senra, R., Boaventura, W. C., & Mendes, E. M. A. M. (2017). Assessment of the harmonic currents generated by single-phase nonlinear loads. Electric Power Systems Research, 147, 272–279. https://doi.org/10.1016/j.epsr.2017.02.028
  21. Ugwuagbo, E., Balogun, A., Olajube, A., Omeje, O., Awelewa, A., & Abba-Aliyu, S. (2021). Experimental data on power quality assessment at point of common coupling of a steel mill to an electric power grid. Data in Brief, 39, Article 107681. https://doi.org/10.1016/j.dib.2021.107681
  22. Vabalas, A., Gowen, E., Poliakoff, E., & Casson, A. J. (2019). Machine learning algorithm validation with a limited sample size. PLOS ONE, 14(11), Article e0224365. https://doi.org/10.1371/journal.pone.0224365
  23. Wilcoxon, F. (1945). Individual comparisons by ranking methods. Biometrics Bulletin, 1(6), 80–83. https://doi.org/10.2307/3001968
  24. Willems, J. L. (2004). Reflections on apparent power and power factor in nonsinusoidal and polyphase situations. IEEE Transactions on Power Delivery, 19(2), 835–840. https://doi.org/10.1109/TPWRD.2003.823182