Journals / Afyon Kocatepe Üniversitesi Fen ve Mühendislik Bilimleri Dergisi / 2026 / Cilt: 25 Sayı: 5

Numerical Investigation of Furniture Arrangement, Airflow Velocity, and Blowing Angle with a Wall-Mounted Air Conditioner

Duvar Tipi Klima ile Mobilya Yerleşiminin, Üfleme Hızının ve Açısının Sayısal İncelenmesi

Hüsamettin Tan(Kırıkkale Üniversitesi)0000-0003-2576-8166
Tolga Demircan(KIRIKKALE UNIVERSITY)0000-0003-4805-6428
Pages
1216–1229
Publication Date
2025-10-01
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

As a result of the analysis, it was observed that the change in the blowing velocity of the air conditioner does not have much effect on the overall structure of the flow.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:In this study, the cooling of a room using a wall-mounted air conditioner and keeping it under thermal comfort conditions are discussed.
📊
Key Findings & Data:However, it was determined that changes in the air conditioner’s blowing angle and the room’s layout significantly affected the velocity and temperature distribution of the air in the room.
💡
Conclusion & Impact:As a result of the analysis, it was observed that the change in the blowing velocity of the air conditioner does not have much effect on the overall structure of the flow.
🔬Design:Modeling & Simulation
📍Scope:Comprehensive Sample
⚙️Variables:Klima · Had · Isıl Konfor

Abstract

In this study, the cooling of a room using a wall-mounted air conditioner and keeping it under thermal comfort conditions are discussed. Within this scope, a standard office room model cooled by air conditioning was created and numerical analyses were conducted. In the study, four different blowing velocities, three different blowing angles and two different placements of the furniture in the room were investigated. The effects of these parameters on the velocity and temperature distribution of the air in the room, which influences thermal comfort conditions, were examined. As a result of the analysis, it was observed that the change in the blowing velocity of the air conditioner does not have much effect on the overall structure of the flow. However, it was determined that changes in the air conditioner’s blowing angle and the room’s layout significantly affected the velocity and temperature distribution of the air in the room. Within the range of parameters examined, it was observed that the optimum thermal comfort conditions were achieved with furniture Location-I, a blowing velocity of 0.5 m/s, and a blowing angle of 80°.

Özet

Bu çalışmada, duvar tipi bir klima kullanılan bir odanın soğutulması ve ısıl konfor şartlarında tutulması ele alınmıştır. Bu kapsamda klima ile soğutulan standart bir ofis odası modeli oluşturulmuş ve sayısal analizler yapılmıştır. Çalışmada dört farklı üfleme hızı, üç farklı üfleme açısı ve oda içerisindeki mobilyaların iki farklı yerleşimi için incelemeler yapılmıştır. Bu parametrelerin ısıl konfor şartlarına etki eden oda içerisindeki havanın hız ve sıcaklık dağılımına etkileri incelenmiştir. Yapılan analizlerin sonucunda, klimanın üfleme hızının değişiminin akışın genel yapısı üzerinde fazla etkili olmadığı gözlemlenmiştir. Ancak klimanın üfleme açısının ve odanın yerleşim düzeninin değişiminin akış yapısını değiştirdiği, oda içerisindeki havanın hız ve sıcaklık dağılımını önemli ölçüde etkilediği belirlenmiştir. İncelenen parametre aralığında, 1 numaralı mobilya yerleşimi, 0.5 m/s üfleme hızı ve 80o üfleme açısı için optimum ısıl konfor şartlarının gerçekleştiği gözlemlenmiştir.

🔖

Cite This Article

Şanlı, A., Tan, H., Demircan, T. (2025). Numerical Investigation of Furniture Arrangement, Airflow Velocity, and Blowing Angle with a Wall-Mounted Air Conditioner. Afyon Kocatepe Üniversitesi Fen ve Mühendislik Bilimleri Dergisi, Cilt: 25 Sayı: 5, 1216–1229. https://doi.org/10.35414/akufemubid.1608826

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (31)

  1. Anak A., Barau B., Zambri AN., 2024. Flow Observation on Air Flow Distribution in Room by HVAC System using Ansys Fluent CFD Simulation. Journal of Complex Flow, 6(1),29-37.
  2. Avara, A. and Daneshgar, E., 2008. Optimum placement of condensing units of split-type air-conditioners by numerical simulation. Energy and Buildings, 40(7), 1268-1272. https://doi.org/10.1016/j.enbuild.2007.11.011
  3. Ayad, S. S., 1999. Computational study of natural ventilation. Journal of Wind Engineering and Industrial Aerodynamics, 82, 49-68. https://doi.org/10.1016/S0167-6105(98)00210-4
  4. Başkaya, Ş. and Eken, E., 2006. Numerical investigation of air flow inside an office room under various ventilation conditions. Pamukkale University Engineering College Journal of Engineering Science, 12(1), 87-95.
  5. Bamodu O., Xia L., Tang L., 2017. A Numerical Simulation of Air Distribution in an Office Room Ventilated by 4-Way Cassette Air-conditioner. Energy Procedia, 105:2506-2511. https://doi.org/10.1016/j.egypro.2017.03.7221
  6. Bojic M., Yik F., Lo TY., 2002. Locating air-conditioners and furniture inside residential flats to obtain good thermal comfort. Energy and Buildings, 34(7), 745-751. https://doi.org/10.1016/S0378-7788(01)00143-8
  7. Bonefacic, I., Frankovic, B., Vilicic, I., and Glazar, V., 2007. Numerical modelling of temperature and air flow distribution in enclosed room. Proceedings of the Heat-SET 2007: Heat Transfer in Components and Systems for Sustainable Energy Technologies, Vol II, 1055-1062.
  8. Chung, I. P. and Dunn-Rankin, D., 1998. Using numerical simulation to predict ventilation efficiency in a model room. Energy and Buildings, 28(1), 43–50. https://doi.org/10.1016/S0378-7788(97)00061-3
  9. Costa, J. J., Oliveira, L. A., and Blay, D., 1999. Test of several versions for the k-ε type turbulence modelling of internal mixed convection flows. International Journal of Heat and Mass Transfer, 42, 4391-4409. https://doi.org/10.1016/S0017-9310(99)00075-7
  10. Çalışkan, S., Altunok, T., Başkaya, Ş., and Güngüneş, H. M., 2011. Numerical analysis of a commercial display cabinet with air curtain. Journal Faculty Engineering and Architecture Gazi University, 26(2), 415-425.
  11. Haines, R. W., 1977. Control system for heating, ventilating and air conditioning. 2nd ed. New York: Van Nostrand Reinhold.
  12. Harrington, E., 1933. Air conditioning for comfort and health, past-present-future. Journal of the Franklin Institute, 215(6), 655-696. https://doi.org/10.1016/S0016-0032(33)90679-1
  13. Harsito C., and Permata ANS., 2021. Investigation of air distribution in mosque rooms with different angles of supply and inlet velocity. Int J Heat Technol., 39(4), 1383-1388. https://doi.org/10.18280/ijht.390439
  14. Izgi, F., and Kavacık, M., 2024. Analyzing global competitiveness of Turkish air conditioning industry. Turkish Journal of Engineering, 8(2), 209-234. https://doi.org/10.31127/tuje.1372141
  15. Jerold, L. A., 1992. Architectural plan for adding on or remodeling. TAB Books.
  16. Karaşahin, F., 2011. Numerical investigation of air conditioning of a furnished office room. Master’s Thesis, Gazi University, Ankara.
  17. Koca, F., and Zabun, M., 2021. The effect of outlet location on heat transfer performance in micro pin-fin cooling used for a CPU. European Physical Journal Plus, 136, 1115. https://doi.org/10.1140/epjp/s13360-021-02113-4.
  18. Koca, F., and Zabun, M., 2022. Nozul Mesafesinin Çarpan Jet Isı Transferi ve Akışkan Akışı Üzerindeki Etkileri. Osmaniye Korkut Ata Üniversitesi Fen Bilimleri Enstitüsü Dergisi,5(2),1008–1021.
  19. Lee, S., Lee, J., and Kato, S., 2017. Influence of vane angle on the effectiveness of air of wall-mounted split-type air conditioners in residential buildings. Science and Technology for the Built Environment, 23(5), 761-775. https://doi.org/10.1080/23744731.2016.1260410
  20. Liu, N., Lai, X. L., Yan, K., and Zhang, H., 2016. Investigation of flow and heat transfer characteristics on different heat exchangers of air conditioner. Applied Thermal Engineering, 103, 428–43. https://doi.org/10.1016/j.applthermaleng.2016.04.084
  21. Lu YC., Wei Chen C., Gong XJ., Rong Lee K., Tseng CJ., 2021 CFD Simulations for Thermal Comfort and Energy Saving. Proc - 22nd IEEE/ACIS Int Conf Softw Eng Artif Intell Netw Parallel/Distributed Comput SNPD, 167-170. https://doi.org/10.1109/SNPD51163.2021.9704978
  22. Nielsen, P. V., 1990. Specification of a two-dimensional test case. Institute for Bygningsteknik, Aalborg Universitet.
  23. Pitarma, R. A., Ramos, J. E., and Carvalho, M. G., 2003. Computational and experimental reduced scale modelling of air-conditioned rooms. Building Simulation 2003: Eighth International IBPSA Conference, 1041-1045, Eindhoven, Netherlands.
  24. Pulat, E., 2011. Numerical investigation of air distribution in a room ventilated by an air conditioning unit. Ulusal İklimlendirme Kongresi, 389-400, Antalya, Turkey.
  25. Ramos, G., Lamberts, R., Abrahão, K. C. F. J., Bandeira, F. B., Teixeira, C. F. B., De Lima, M. B., Broday, E. E., Castro, A. P. A. S., Leal, L. De Q., De Vecchi, R., De Zorzi, L. De M., Dornelles, K. A., Duarte, S., Faisca, R. G., Fontenelle, M., Freitas, T., Atem, C. G., Grigoletti, G., Maciel, L., De Moraes, C. M., Mueller, C. M., Sartori, T., Silva, B., Silva, C., Da Silva, M. V., Silveira, A. L., Souza, R. V. G., and Xavier, A. A., 2021. Adaptive behaviour and air conditioning use in Brazilian residential buildings. Building Research & Information, 49(5), 496-511. https://doi.org/10.1080/09613218.2020.1804314
  26. Sabie DD., Fatu V., Ghiaus AG., 2019. Local analysis of airflow distribution in open concept passive houses. E3S Web Conference, 111, 1-7. https://doi.org/10.1051/e3sconf/201911101019
  27. Tripathi, B. and Moulic, S. G., 2007. Investigation of the airflow patterns inside a room through the low Re k-ε Model. Heat and Technology, 25(1), 25-31.
  28. Wang J., Liu X., Tian C., Wu L., Xi G., 2022. Indoor Environment Control Effect Based on Multi-Impeller Air Conditioner. J Therm Sci., 31(6), 2137-2154. https://doi.org/10.1007/s11630-022-1537-5
  29. Yongson, O., Badruddin, I. A., Zainal, Z. A., and Narayana, P. A. A., 2007. Airflow analysis in an air conditioning room. Building and Environment, 42, 1531-1537. https://doi.org/10.1016/j.buildenv.2006.01.002
  30. Youssef AA., Mina EM., ElBaz AR., AbdelMessih RN., 2018 Studying comfort in a room with cold air system using computational fluid dynamics. Ain Shams Eng J., 9(4), 1753-1762. https://doi.org/10.1016/j.asej.2016.07.005
  31. Yüce, B. E., 2019. Comparison of turbulent flow models in office medium and numerical simulation of various heating systems by using thermal comfort indices and Gagge Model. PhD Thesis, Bursa Uludağ University, Bursa.