Dergiler / Hittite Journal of Science and Engineering / 2017 / Cilt: 4 - Sayı: 1

Theoretical Performance Analysis of an R1234yf Refrigeration Cycle Based on the Effectiveness of Internal Heat Exchanger

Sayfa
23–30
Yayın Tarihi
2022-10-18
DOI
—
🏛️Bu makalenin bibliyografik verileri ve tam metin bağlantısı DergiPark üzerinden sağlanmıştır.
DergiPark Kaydı ↗
✨

Yapay Zeka Hızlı Bakış & Çıkarımlar

AI Insight
⚡ TL;DR(1 Cümlede Hızlı Çıkarım)

As a result, it was determined that the critical effectiveness to supply the same COP with R1234yf was determined 50% in comparison the baseline cycle

📌 3 Maddede Bu Makale

🎯
Amaç & Hipotez:I n this paper, the effects of internal heat exchanger IHX effectiveness on the performance parameters of the refrigeration cycle with R1234yf were theoretically investigated.
📊
Temel Bulgular & Veri:The analysis were performed between -20°C and 0°C evaporation and 40°C and 50°C condensation temperatures based on the effectiveness value of IHX.
💡
Sonuç & Katkı:As a result, it was determined that the critical effectiveness to supply the same COP with R1234yf was determined 50% in comparison the baseline cycle
🔬Tür:Modelleme & Sayısal Simülasyon
📍Kapsam:Genişletilmiş Akademik Örneklem
⚙️Değişkenler:Alan Parametreleri

Abstract

I n this paper, the effects of internal heat exchanger IHX effectiveness on the performance parameters of the refrigeration cycle with R1234yf were theoretically investigated. For this purpose, a mathematical model was developed based on the energy balance of the cycle. The analysis were performed between -20°C and 0°C evaporation and 40°C and 50°C condensation temperatures based on the effectiveness value of IHX. The cooling capacity, coefficient of performance COP , subcooling, superheat and compressor discharge temperature of the refrigeration cycle was examined. Finally, the performance results of the cycle with R1234yf were compared with the baseline cycle that utilizes with R134a. As a result, it was determined that the critical effectiveness to supply the same COP with R1234yf was determined 50% in comparison the baseline cycle

🔖

Bu Makaleye Atıf Yap

DİREK, M., KELEŞOĞLU, A., AKIN, A. (2022). Theoretical Performance Analysis of an R1234yf Refrigeration Cycle Based on the Effectiveness of Internal Heat Exchanger. Hittite Journal of Science and Engineering, Cilt: 4 - Sayı: 1, 23–30. https://ajindex.com/articles/538073

📄 Tam Metin PDF Okuyucu

📄

PDF görüntüleyici hazırlanıyor...

Kaynakça (13)

  1. Directive 2006/40/EC of the European Parliament and of the Council of 17 May 2006 Relating to Emissions from Air Conditioning Systems in Motor Vehicles and Amending Council Directive 70/156/EC, 2006
  2. Regulation 517/2014/EU of the European Parliament and the Council of 16 April 2014 on Fluorinated Greenhouse Gases and Repealing Regulation (EC) No 842/2006. Official Journal of the European Union, 2014
  3. Solomon S, Qin D, Manning M, Chen Z, Marquis M, Averyt KB, Tignor M, Mille HL. Contribution of Working Groups I, II and III to the Fourth Assessment Report of the Intergovernmental Panel on Climate Change. Cambridge University Press, New York, 2007
  4. Zhaofeng M, Hua Z, Jinyou Q, Mingjing L. Theoretical Analysis of R1234ze(E), R152a, and R1234ze(E)/R152a Mixtures as Replacements of R134a in Vapor Compression System. Advances in Mechanical Engineering 8 (2016) 1-10
  5. Mota-Babiloni A, Navarro-Esbri J, Barragan-Cervera A, Moles F, Peris B. Analysis Based on EU Regulation No 517/2014 of new HFC/HFO Mixtures as Alternatives of High GWP Refrigerants in Refrigeration and HVAC Systems. International Journal of Refrigeration 52 (2015) 21-31
  6. Jarall S. Study of Refrigeration System with HFO-1234yf as a Working Fluid. International Journal of Refrigeration 35 (2012) 1668-1677
  7. Papadimitriou VC, Talukdar RK, Portmann RW, Ravishankara AR, Burkholder JB. CF3CF=CH2 and (Z)-CF3CF=CHF: Temperature Dependent OH Rate Coefficients and Global Warming Potentials. Physical Chemistry Chemical Physics 10 (2008) 808-820
  8. Akasaka R, Tanaka K, Higashi Y. Thermodynamic Property Modeling for 2,3,3,3-tetrafluoropropene (HFO-1234yf). International Journal of Refrigeration 33 (2010) 52-60
  9. Naushad AA, Bipin Y, Jitendra K. Theoretical Exergy Analysis of HFO-1234yf and HFO-1234ze as an Alternative Replacement of HFC-134a in Simple Vapour Compression Refrigeration System. International Journal of Scientific & Engineering Research 4 (2013) 137-144
  10. Hoşöz M, Suhermanto M, Aral MC. Comparative Experimental Performance of an Automotive Air Conditioning System Using Refrigerants R1234yf and R134a, in: Solmaz E, Kaya N, Öztürk F (Eds.)
  11. Automotive Technologies Congress. Paper presented at Automotive Engineering Department, Uludağ University, Bursa, 23-24 May, 2016
  12. Zilio C, Brown JS, Schiochet G, Cavallini A. The Refrigerant R1234yf in Air Conditioning Systems. Energy 36 (2011) 6110-6120
  13. Daviran S, Kasaeian A, Golzari S, Mahian O, Nasirivatan S, Wongwises S. A C