Stability analysis of medium sized power plants subjected to grid events

Sayfa
491–498
Yayın Tarihi
2022-10-11
DOI
—
🏛️Bu makalenin bibliyografik verileri ve tam metin bağlantısı DergiPark üzerinden sağlanmıştır.
DergiPark Kaydı ↗
✨

Yapay Zeka Hızlı Bakış & Çıkarımlar

AI Insight
⚡ TL;DR(1 Cümlede Hızlı Çıkarım)

The results also show that even 100% penetrated synchronous generator based power plants in distribution system do not affect stability badly in steady state operation.

📌 3 Maddede Bu Makale

🎯
Amaç & Hipotez:Connection of small generating units in the medium voltage distribution system is increasing substantially.
📊
Temel Bulgular & Veri:Such units, called distributed generation, can have a significant impact on, load flow, shortcircuit, voltage, frequency, power quality, stability, islanding and synchronized running, protection and reliability.
💡
Sonuç & Katkı:The results also show that even 100% penetrated synchronous generator based power plants in distribution system do not affect stability badly in steady state operation.
🔬Tür:Araştırma Makalesi
📍Kapsam:Genişletilmiş Akademik Örneklem
⚙️Değişkenler:Stability analysis · power plants · distribution grid

Özet

Connection of small generating units in the medium voltage distribution system is increasing substantially. Such units, called distributed generation, can have a significant impact on, load flow, shortcircuit, voltage, frequency, power quality, stability, islanding and synchronized running, protection and reliability. In this study, the stability impact of a private sector power plant in Thrace region having synchronous generators driven by gas engine and gas turbine has been investigated in terms of fault ride through capability. Critical clearing time has been determined, once the criteria of fault ride through capability were explored. Grid operators do limit penetration levels of such plants and can also disconnect available units when grid fails. Stability is affected by voltage dip much worsely than penetration levels. It has been seen that the disconnection of power plants is not necessary, when the voltage dip restricted to 0,5 pu. Also that the stability is positively affected when the power factor is decreased to 0,8 from 1,0. The results also show that even 100% penetrated synchronous generator based power plants in distribution system do not affect stability badly in steady state operation.

🔖

Bu Makaleye Atıf Yap

KILIÇ, L., ARSOY, A. B. (2022). Stability analysis of medium sized power plants subjected to grid events. Dicle Üniversitesi Mühendislik Fakültesi Mühendislik Dergisi, Cilt: 11 - Sayı: 2, 491–498. https://ajindex.com/articles/487602

📄 Tam Metin PDF Okuyucu

📄

PDF görüntüleyici hazırlanıyor...

Kaynakça (16)

  1. Schavemaker P.H., Van der Sluis L. (2008). Electrical Power System Essentials, Wiley&Sons, Chichester, United Kingdom
  2. Reza M. (2006), Stability analysis of transmission systems with high penetration of distributed generation. Ph.D. Thesis, Technische universiteit Delft
  3. Ackermann T., Knyazkin V. (2002). Interaction between distributed generation and the distribution grid: Operation aspects, IEEE Transmission and distribution conference and exhibition Asia Pacific, Yokohama
  4. Ishchenko A., Myrzik J.M.A., Kling W.L. (2007). Dynamic equivalencing of distribution grids with dispersed generation using hankel norm approximation, IET Proceedings on Generation, Transmission and Distribution, 1(5), 818-825
  5. Nuroglu F. M., Arsoy A. B. (2008). Voltage Profile and Short Circuit Analysis in Distribution Systems with DG, Electric Power and Energy Conference, Canada
  6. Thong V. V., Vermeyen P., Driesen J., Belmans R. (2005). Grid Connection Aspects of Distributed Generation, International Energy Journal, 6(1), 148-161
  7. Walling R.A. (Reigh), Saint R., Dugan R. C., Burke J., Kojovic L. (2008). A. Summary of Distributed Resources Impact on Power Delivery Systems, IEEE Transactions on Power Delivery, 23(3), 1636-1644
  8. Xyngi I., Ishchenko A., Popov M., Sluis L. V. D. (2009). Transient Stability Analysis of a Distribution Grid With Distributed Generation, IEEE Transactions on Power Systems, 24(2), 1102-1104
  9. Sun X., Chen D., Gao M., Liu D., Zhu T. (2011). Generator Parameters’ Impact on Power System Stability and Their Engineering Testing Methods, Electrical Power Systems and Computers, 99, 259-276
  10. IEEE 1547, (2003). IEEE Standard for interconnecting distributed resources with electrical power systems, The Institute of Electrical and Electronics Engineers, New York
  11. Mozina C. J. (2006). Distributed generator interconnect pretection practices, IEEE Power Engineering Society Power System Conference and Exposition, Dallas
  12. Driesen J., Belmans R. (2006). Distributed generation: Challenges and possible solutions, IEEE Power Engineering Society General Meeting, Montreal
  13. DigSilent Power Factory Manual, (2007). Version 13.2, Germany
  14. IEEE Committee report, (1982). Proposed terms and definitions for power system stability, in IEEE transactions PAS, 1894-1898
  15. Venikov V., (1980). Transient Processes in Electrical Power Systems, Mir, Moscow
  16. Peterson H. A., (1951). Transients in Power Systems, John Wiley & Sons, New Y