Dergiler / Anadolu Üniversitesi Bilim ve Teknoloji Dergisi :A-Uygulamalı Bilimler ve Mühendislik / 2017 / Cilt: 18 - Sayı: 1

USE OF BOUNDING ANALYSES TO ESTIMATE THE PERFORMANCE OF A SEISMICALLY ISOLATED STRUCTURE

Sayfa
161–177
Yayın Tarihi
2022-10-11
DOI
—
🏛️Bu makalenin bibliyografik verileri ve tam metin bağlantısı DergiPark üzerinden sağlanmıştır.
DergiPark Kaydı ↗
✨

Yapay Zeka Hızlı Bakış & Çıkarımlar

AI Insight
⚡ TL;DR(1 Cümlede Hızlı Çıkarım)

However, it is revealed that there may be individual cases where bounding analyses fails to provide a safe envelope.

📌 3 Maddede Bu Makale

🎯
Amaç & Hipotez:Current design approach for seismic isolated structures is to perform bounding analyses.
📊
Temel Bulgular & Veri:These analyses provide an envelope for the response of the seismic isolated structure rather than focusing on the actual performance.
💡
Sonuç & Katkı:However, it is revealed that there may be individual cases where bounding analyses fails to provide a safe envelope.
🔬Tür:Modelleme & Sayısal Simülasyon
📍Kapsam:Genişletilmiş Akademik Örneklem
⚙️Değişkenler:Alan Parametreleri

Abstract

Current design approach for seismic isolated structures is to perform bounding analyses. These analyses provide an envelope for the response of the seismic isolated structure rather than focusing on the actual performance. In this study, the success of bounding analyses to estimate performance of a seismic isolated structure, in which the isolation is provided by means of lead rubber bearings (LRBs), is evaluated in a comparative manner. For this purpose, nonlinear response history analyses were performed under the effect of bidirectional ground motion excitations. In bounding analyses, non-deteriorating hysteretic representations were used to model the hysteretic behavior of LRBs. On the other hand, to estimate the actual performance of both the superstructure and isolator units, deteriorating hysteretic idealizations were employed. The deterioration in strength of LRBs was defined as a function of temperature rise in the lead core. The analyzed structure is an existing seismically isolated hospital building and analytically modeled in accordance with its reported design properties for both isolation units and superstructure. Results obtained from analyses where LRBs are idealized by both deteriorating and non-deteriorating hysteretic representations are used in the comparisons. The response quantities used in the comparisons are maximum isolator displacement, maximum isolator force, maximum absolute floor acceleration, and maximum relative story displacements. In an average sense, bounding analyses is found to provide conservative estimates for the selected response quantities and fulfills its intended purpose. However, it is revealed that there may be individual cases where bounding analyses fails to provide a safe envelope.

🔖

Bu Makaleye Atıf Yap

AVŞAR, Ö., ÖZDEMİR, G. (2022). USE OF BOUNDING ANALYSES TO ESTIMATE THE PERFORMANCE OF A SEISMICALLY ISOLATED STRUCTURE. Anadolu Üniversitesi Bilim ve Teknoloji Dergisi :A-Uygulamalı Bilimler ve Mühendislik, Cilt: 18 - Sayı: 1, 161–177. https://ajindex.com/articles/438264

📄 Tam Metin PDF Okuyucu

📄

PDF görüntüleyici hazırlanıyor...

Kaynakça (17)

  1. Robinson WH. Lead-rubber hysteretic bearings suitable for protecting structures during earthquakes. Earthquake Eng Struc 1982; 10: 593-604
  2. American Association of State Highway and Transportation Officials (AASHTO). Guide specifications for seismic isolation design. Washington, 1999
  3. American Society of Civil Engineers (ASCE). Minimum design loads for buildings. ASCE/SEI-7- 10 Reston, 2010
  4. Kalpakidis IV, Constantinou MC. Effects of heating on the behavior of lead-rubber bearing. I:Theory. J Struct Eng 2009; 135: 1440-1449
  5. Kalpakidis IV, Constantinou MC. Effects of heating on the behavior of lead-rubber bearing. II:Verification of theory. J Struct Eng 2009; 135: 1450-1461
  6. Ozdemir G, Avsar O, Bayhan B. Change in response of bridges isolated with LRBs due to lead core heating. Soil Dyn Earthq Eng 2011; 31: 921-929
  7. Ozdemir G, Dicleli M. Effect of lead core heating on the seismic performance of bridges isolated with LRB in near fault zones. Earthquake Eng Struc 2012; 41: 1989-2007
  8. Ozdemir G. Formulations for equivalent linearization of LRBs in order to incorporate effect of lead core heating. Earthq Spectra 2015; 31: 317-337
  9. Ozdemir G. Lead core heating in LRBs subjected to bidirectional ground motion excitations in various soil types. Earthquake Eng Struc 2014; 43: 267-285
  10. Ozdemir G, Bayhan B. Response of an isolated structure with deteriorating hysteretic isolator model. Res Eng Struct Mat 2015; 1: 1-10
  11. Providakis CP. Effect of supplemental damping on LRB and FPS seismic isolators under nearfault ground motions. Soil Dyn Earthq Eng 2009; 29: 80-90
  12. Yang TY, Konstantinidis D, Kelly JM. The influence of isolator hysteresis on equipment performance in seismic isolated buildings. Earthq Spectra 2010; 26: 275-293
  13. Erdik M. Seismic isolation for buildings. 6th National Conference on Earthquake Engineering; 16-20 October 2007; Istanbul, Turkey
  14. Ministry of Public Works and Settlement, General Directorate of Disaster Affairs. Earthquake Zoning Map of Turkey, 96/8109, 1996
  15. Open System for Earthquake Engineering Simulation (OpenSees). Version: 2.1.0. University of California, Pacific Earthquake Engineering Research Center, Berkeley, California, 2001
  16. Erdik M, Constantinou MC. Design and analysis of seismic isolation system for Erzurum Hospital, Turkey. Technical Report, Ankara, Turkey, 2005
  17. Park YJ, Wen YK, Ang AH. Random vibration of hysteretic systems under bi-directional ground mo