Journals / Sakarya University Journal of Science / 2019 / Cilt: 23 Sayı: 2

Effects of The Shell Thickness On The Directional Deformation And Buckling On The Cylindrical Steel Water Tanks Under The Kobe Earthquake Loading

Pages
269–281
Publication Date
2019-04-01
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

The differences obtained are detailed with

📌 3 Key Takeaways

🎯
Objective & Hypothesis:Cylindrical steel storage tanks are widely used for the storage of various liquids, industrial chemicals and firefighting waters.
📊
Key Findings & Data:Dimensions of cylindrical open-top, flat-closed and torispherical-closed top tanks were determined for 3D-finite element method (FEM) models in an ANSYS workbench software.
💡
Conclusion & Impact:The differences obtained are detailed with
🔬Design:Modeling & Simulation
📍Scope:Comprehensive Sample
⚙️Variables:Cylindrical Storage Tank · API 650 · FEM Analysis

Abstract

Cylindrical steel storage tanks are widely used for the storage of various liquids, industrial chemicals and firefighting waters. They have been used for cooling purposes in nuclear power plants in recent years. Liquid-storage tanks have many different configurations; however, in this study, cylindrical ground-supported liquid steel tanks were preferred because of their simplicity in design and construction as well as their efficiency in resisting hydrostatic and hydrodynamic applied loads, when compared with other configurations. If liquid steel tanks are damaged in an earthquake, they can also cause great financial and environmental damage with their hazardous chemical contents. These tanks may be exposed to some damages such as elephant-foot buckling, diamond-shape buckling, overturning and uplifting during earthquakes. Dimensions of cylindrical open-top, flat-closed and torispherical-closed top tanks were determined for 3D-finite element method (FEM) models in an ANSYS workbench software. This article focuses on the seismic-activity-resistant ground-supported cylindrical (vertical) steel storage liquid tanks. Seismic analyses were conducted under Kobe earthquake loads. The frequency values calculated with API 650 were verified with the FEM model results. Directional deformation, buckling results were presented for both impulsive and convective regions. According to API 650 standard, the tank shell thickness is 6 mm. Simulations were performed with 4 mm and 8 mm shell thickness for tanks. In this study, directional deformation and buckling were observed with simulations made by choosing the shell thickness under (4 mm) the standard and above (8 mm) the standard, unlike the approaches in the literature. As a result, it was observed that the 8 mm shell thickness determined above the standard increased the deformation in the flat-closed tank. In addition, torispherical dome-shaped tanks have been observed to lower directional deformation and buckling in any case. The differences obtained are detailed with

🔖

Cite This Article

ÇELİK, A. İ., KÖSE, M. M., AKGÜL, T., APAY, A. C. (2019). Effects of The Shell Thickness On The Directional Deformation And Buckling On The Cylindrical Steel Water Tanks Under The Kobe Earthquake Loading. Sakarya University Journal of Science, Cilt: 23 Sayı: 2, 269–281. https://ajindex.com/articles/942053

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (1)

  1. Bayraktar A, Sevim B, Altunışık A C, Türker T. Effect of the model updating on the earthquake behavior of steel storage tanks. J Constr Steel Res, 2010, 66: 462–468 [2] F.H. Hamdan, Seismic behaviour of cylindrical steel liquid storage tanks, J. Constr. Steel Res. 53 (3) (2000) 307–333. [3] M.A. Haroun, G.W. Housner, Earthquake response of deformable liquid storage tanks, J. Appl. Mech. Trans ASME 48 (2) (1981) 411–418. [4] B. Hunt, N. Priestley, Seismic water-waves in a storage tank, B Seismol. Soc. Am. 68 (2) (1978) 487–499. [5] Y. Tang, Dynamic-response of tank containing 2 liquids, J. Eng. Mech. ASCE 119 (3) (1993) 531–548. [6] A.S. Veletsos, Y. Tang, H.T. Tang, Dynamic-response of flexibly supported liquid storage tanks, J. Struct. Eng. ASCE 118 (1) (1992) 264–283. [7] Houser, G. W.,“Earthquake Pressures on Fluid Containers”, Eighth Technical Report under Office of Naval Research, Project Designation No. 081 - 095, California Institute of Technology, Pasadena, California, pp. 02-16, Aug.-1954 [8] Housner G W. Dynamic pressures on accelerated fluid containers. Bull Seismol Soc Am, 1957, 47(1): 15–35 [9] Housner G W. The Dynamic Behavior of Water Tanks. Bull Seismol Soc Am, 1963, 53(2): 381–387 [10] Malhotra P K, Wenk T, Wieland M. Simple Procedure for Seismic Analysis of Liquid-Storage Tanks. Struct Eng Int, 2000, 10(3): 197–201 [11] Sunitha K R, Jacob B. Dynamic Buckling Of Steel Water Tank Under Seismic Loading. International Journal of Civil Engineering (IJCE), 2015, 4(6): 81–90 [12] Mohamadshahi M, Afrous A. General considerations in the seismic analysis of steel storage tanks. Journal of Scientific Research and Development, 2015, 2(6): 151–156 [13] Brebbia C A, Popov V, Popov V. Thirty-third international conference on Boundary Elements and Other Mesh Reduction Methods XXXIII. Southamption: Wit Press, 2011,286, web link: https://books.google.com.tr/books?id=bOwoKUfWONIC&printsec=frontcover&hl=tr#v=onepage&q&f=false [14] Naghdali H, Hamid K, Masoud G, Ehsan A, Navid K. Comparison of API650-2008 provisions with FEM analyses for seismic assessment of existing steel oil storage tanks. J Loss Prevent Proc Ind 2013;26(4). [15] J.M. Spritzer, S. Guzey, “Review of API 650 Annex E: Design of large steel welded abovegroundstorage tanks excited by seismic loads”, Thin-Walled Structures 112 (2017) 41–65, 2017. [16] S. Nicolici, R.M. Bilegan, “Fluid structure interaction modeling of liquid sloshing phenomena in flexible tanks”, Nucl. Eng. Des. 258 (2013) 5