Experimental Investigation on the Cooling Performance of a Counterflow Dew Point Evaporative Cooler

Pages
103–117
Publication Date
2022-10-18
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

The findings showed that the highest wet bulb efficiency, dew point efficiency and EER of evaporative cooler were found to be 0.91, 0.62, and 0.77, respectively.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:In this study, an innovative indirect evaporative cooler is presented and experimentally analysed.
📊
Key Findings & Data:A prototype was assembled for the experimental investigation of the system and tested in the laboratory environment under the conditions of constant air flow rate of 350 m3/h, circulating water temperatures of 15°C and 20°C, inlet air temperatures of 25°C and 30°C and lastly inlet air humidity of 9g/kg and 13g/kg, respectively.
💡
Conclusion & Impact:The findings showed that the highest wet bulb efficiency, dew point efficiency and EER of evaporative cooler were found to be 0.91, 0.62, and 0.77, respectively.
🔬Design:Research Article
📍Scope:Comprehensive Sample
⚙️Variables:Evaporative cooler · M-cycle · experimental study

Abstract

In this study, an innovative indirect evaporative cooler is presented and experimentally analysed. A prototype was assembled for the experimental investigation of the system and tested in the laboratory environment under the conditions of constant air flow rate of 350 m3/h, circulating water temperatures of 15°C and 20°C, inlet air temperatures of 25°C and 30°C and lastly inlet air humidity of 9g/kg and 13g/kg, respectively. Based on the data obtained during the experiments, calculations were performed for the cooling capacity, cooling efficiency, energy efficiency and exergy efficiency of the system for each case. The findings showed that the highest wet bulb efficiency, dew point efficiency and EER of evaporative cooler were found to be 0.91, 0.62, and 0.77, respectively.

🔖

Cite This Article

BÜKER, M. S., ÖZDEN, E. (2022). Experimental Investigation on the Cooling Performance of a Counterflow Dew Point Evaporative Cooler. Gazi Üniversitesi Fen Bilimleri Dergisi Part C: Tasarım ve Teknoloji, Cilt: 10 - Sayı: 1, 103–117. https://ajindex.com/articles/521855

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (11)

  1. Duan, Z., Zhan, C., Zhang, X., Mustafa, M., Zhao, X., Alimohammadisagvand, B., & Hasan, A. (2012). Indirect evaporative cooling: Past, present and future potentials. Renewable and Sustainable Energy Reviews, 16(9), 6823-6850
  2. Buker, Mahmut Sami; Riffat, Saffa B. Recent developments in solar assisted liquid desiccant evaporative cooling technology—A review. Energy and Buildings, 2015, 96: 95-108
  3. Yang, Y., Cui, G., & Lan, C. Q. (2019). Developments in evaporative cooling and enhanced evaporative cooling-A review. Renewable and Sustainable Energy Reviews, 113, 109230
  4. Yang, H., Shi, W., Chen, Y., & Min, Y. (2021). Research development of indirect evaporative cooling technology: An updated review. Renewable and Sustainable Energy Reviews, 145, 111082
  5. Buker, Mahmut Sami; Mempouo, Blaise; Riffat, Saffa B. Experimental investigation of a building integrated photovoltaic/thermal roof collector combined with a liquid desiccant enhanced indirect evaporative cooling system. Energy Conversion and Management, 2015, 101: 239-254
  6. Bom, G. J., Foster, R., Dijkstra, E., Tummers, M., Evaporative air-conditioning: applications for environmentally friendly cooling, The World Bank, 1999 [7] Osma E., Evaporatif Soğutma Sistemlerinin Mekanik Buhar Sıkıştırmalı Soğutma Sistemleri İle Termodinamik Ve Ekonomik Bakımdan Karşılaştırılması, Yüksek Lisans Tezi, Namık Kemal Üniversitesi Fen Bilimleri Enstitüsü, Tekirdağ, 2011
  7. El-Refaie, M. F., Kaseb, S., Speculation in the feasibility of evaporative cooling, Building and Environment, 2009, 44(4): 826-838
  8. Xuan, Y. M., Xiao, F., Niu, X. F., Huang, X., Wang, S. W, Research and application of evaporative cooling in China: A review (I)–Research, Renewable and Sustainable Energy Reviews, 2012, 16(5): 3535-3546
  9. Maisotsenko, V., Gillan, L. E., Heaton, T. L., Gillan, A. D, 2003, Washington, DC: U.S. Patent and Trademark Office U.S., Patent No. 6,581,402. [11]. Dizaji, H. S., Hu, E. J., Chen, L., Pourhedayat, S, Development and validation of an analytical model for perforated (multi-stage) regenerative M-cycle air cooler, Applied Energy, 2018, 228: 2176-2194
  10. Pandelidis, Demis; Pacak, Anna; Anisimov, Sergey. Energy Saving Potential by Using Maisotsenko-Cycle in Different Applications. International Journal of Earth & Environmental Sciences, 2018, 2018