Journals / Çukurova Üniversitesi Mühendislik-Mimarlik Fakültesi Dergisi / 2017 / Cilt: 32 - Sayı: 2

Investigation of Solar Wall Performance for Industrial Facilities

Endüstriyel Tesisler için Güneş Duvarı Performansının İncelenmesi

Pages
215–229
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

Solar wall delivered 113.037 kWh thermal energy in 2013, 246.924 kWh thermal energy in 2014 and energy savings of up to 62% have been achieved, which are similar to simulated results

📌 3 Key Takeaways

🎯
Objective & Hypothesis:In this study, the performance of field tests of first unglazed transpired solar wall installation in Turkey is analyzed.
📊
Key Findings & Data:The performance of the 770 m2 solar wall in an automotive plant in Çayırova - Kocaeli in 2012, has been monitored for winter periods of two years via a building management system.
💡
Conclusion & Impact:Solar wall delivered 113.037 kWh thermal energy in 2013, 246.924 kWh thermal energy in 2014 and energy savings of up to 62% have been achieved, which are similar to simulated results
🔬Design:Research Article
📍Scope:2012 Verileri
⚙️Variables:Domain Parameters

Abstract

In this study, the performance of field tests of first unglazed transpired solar wall installation in Turkey is analyzed. The performance of the 770 m2 solar wall in an automotive plant in Çayırova - Kocaeli in 2012, has been monitored for winter periods of two years via a building management system. In addition, the theoretical analysis of the system was made by a simulation software for solar wall and the results obtained were compared with the field data. Solar wall delivered 113.037 kWh thermal energy in 2013, 246.924 kWh thermal energy in 2014 and energy savings of up to 62% have been achieved, which are similar to simulated results

Özet

Bu çalışmada, Türkiye'de uygulaması yapılan ilk hava sızdırmalı güneş duvarın saha performansının analizi yapılmıştır. 2012 yılında Çayırova-Kocaeli'nde bir otomotiv tesisinde ısıtma ve havalandırma amaçlı olarak uygulaması yapılan 770 m2'lik güneş duvarının performansı, iki yıllık bir süre zarfında kış dönemlerde üçer aylık periyodlar halinde bina yönetim sistemi vasıtasıyla incelenmiştir. Ayrıca, sistemin teorik analizi, bir güneş duvarı simülasyon yazılımı kullanılarak yapılmış ve elde edilen sonuçlar saha verileri ile karşılaştırılmıştır. Simülasyon sonuçlarına benzer olarak, 2013 yılında 113,037 kWh enerji, 2014 yılındaki 246,924 kWh ısı enerjisi üretmiş ve dönemsel olarak %62 varan bir enerji tasarruf elde edilmiştir

🔖

Cite This Article

AKHAN, H., ERYENER, D. (2017). Investigation of Solar Wall Performance for Industrial Facilities. Çukurova Üniversitesi Mühendislik-Mimarlik Fakültesi Dergisi, Cilt: 32 - Sayı: 2, 215–229. https://ajindex.com/articles/198237

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (13)

  1. Mauthner, F., Weiss, W., Spörk-Dür, M., 2016. SHC International Energy Agency, Solar Heat Worldwide-Markets and Contribution to the Energy Supply 2014, IEA Solar Heating & Cooling Programme
  2. Balcomb, J. D., 1992, Passive Solar Buildings, MIT Press
  3. Hordeski, M. F., 2002, New Technologies for Energy Efficiency, The Fairmont Press, Marcel Dekker, New York and Basel, ISBN 0-88173- 369-5
  4. Hollick, J.C., 2003. Unglazed Solar Wall Air Heaters, Conserval Engineering Inc., 200 Wildcat Rd. Downsview, Ontario M3J 2N5, Canada, 5. Kutscher, C.F., 1993. An Investigation of Heat Transfer for Air Flow Through Low Porosity Perforated Plates, University of Colorado, Boulder, s.289
  5. Kutscher, C.F., Christensen, C., Barker, G. 1993. Unglazed Transpired Solar Collectors: Heat Loss Theory. ASME Journal of Solar Engineering, Cilt. 115, s. 182–188
  6. Cao, S., Hollands, K.G.T., Brundrett, E., 1993. Heat Exchange effectiveness of unglazed transpired-plate solar collector in 2D flow.In: Proceedings of ISES Solar World Congress 1993, Budapest, Hungary, Vol. 5, pp. 351–366
  7. Pesaran, A.A., Wipke, K., 1994. Use of unglazed transpired solar collectors for desiccant cooling. Solar Energy Journal 52 (5); 419-427
  8. Kutscher, C.F., 1994. Heat Exchanger Effectiveness and Pressure Drop for Airflow Through Perforated Plates, With and Without Cross Wind. ASME Journal of Heat Transfer 116, 391–399
  9. Van Decker, G.W.E., Hollands, K.G.T., Brunger, A.P., 1996. Heat Exchange Effectiveness of Unglazed Transpired-plate Solar Collector in 3D Flow. In: Goietzburger, A., Luther, J. (Eds.), Proceedings of Euro Sun 96, Freiburg, Germany. DGS–Sonnenenergie Verlags GmbH, Munchen, Germany, pp.130–846
  10. Van Decker, G.W.E., Hollands, K.G.T., 1999. An Empirical Heat Transfer Equation for the Transpired Solar Collectors, Including no-wind Conditions. In: Proceedings of the ISES 99 Solar World Congress, Australia
  11. Van Decker, G.W.E., Hollands, K.G.T., Brunger, A.P., 2001. Heat Exchange Relations for Unglazed Transpired Solar Collectors With Circular Holes on a Square or Triangular Pitch. Solar Energy 71 (1), 33–45. 13.Campbell-Howe, R., 1996. Thermal Simulation and Economic Assessment of Unglazed Transpired Collestor Systems, The 1996 American Solar Energy Society Annual Conference, Asheville, North Carolina, April 13-18
  12. Dymond, C., Kutscher, C., 1997. Development of a Flow Distribution and Design Model for Transpired Solar Collectors. Solar Energy, 60 (5); 291-300
  13. Dymond,