Journals / Politeknik Dergisi / 2026 / Cilt: 24 Sayı: 2

Investigation of the Effect of Air Change Rate on Contaminant Removal Performance

Hava Değişim Katsayısının Kirletici Uzaklaştırma Performansına Etkisinin İncelenmesi

Yunus Emre Çetin(KARADENİZ TEKNİK ÜNİVERSİTESİ)0000-0003-0165-2900
Mete Avcı(RECEP TAYYİP ERDOĞAN ÜNİVERSİTESİ)0000-0003-4994-1488
Orhan Aydın(KARADENİZ TEKNİK ÜNİVERSİTESİ)0000-0002-2492-8212
Pages
453–459
Publication Date
2021-06-01
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

In addition, it is determined that the increase in air change rate decreases the concentration of pollutants in this region by 75%.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:In this study, the effect of air change rate on particle dispersion is investigated experimentally and numerically for different contaminant source positions.
📊
Key Findings & Data:An experimental study is carried out on a reduced scale model for isothermal flow conditions and 0.5 µm particles are used as contaminants.
💡
Conclusion & Impact:In addition, it is determined that the increase in air change rate decreases the concentration of pollutants in this region by 75%.
🔬Design:Modeling & Simulation
📍Scope:Comprehensive Sample
⚙️Variables:Hava değişim katsayısı (HDK) · Partikül dağılımı · Kirletici uzaklaştırma

Abstract

In this study, the effect of air change rate on particle dispersion is investigated experimentally and numerically for different contaminant source positions. An experimental study is carried out on a reduced scale model for isothermal flow conditions and 0.5 µm particles are used as contaminants. Particle motions, based on Lagrange approach, are modeled with a computational fluid dynamics (CFD) software ANSYS Fluent. It is found that pollutants outside the main flow region lead to 12 times higher concentration values. In addition, it is determined that the increase in air change rate decreases the concentration of pollutants in this region by 75%.

Özet

Bu çalışmada, hava değişim katsayının partikül dağılımına etkisi farklı kirletici kaynak konumları için deneysel ve sayısal olarak incelenmiştir. Deneysel çalışma küçük ölçekli bir model oda üzerinde izotermal akış şartları için yürütülmüş ve kirletici olarak 0,5 µm ebatında partiküller kullanılmıştır. Partikül hareketleri, Lagrange yaklaşımı esas alınarak bir hesaplamalı akışkanlar dinamiği (HAD) yazılımı olan ANSYS Fluent programında modellenmiştir. Ana akış bölgesi dışında yer alan kirleticilerin daha yüksek konsantrasyon değerlerine yol açtığı tespit edilmiştir. Bununla beraber, hava değişim katsayısındaki artışın bu bölgedeki kirletici konsantrasyonunu azaltmada daha etkili olduğu ortaya konmuştur.

🔖

Cite This Article

Çetin, Y. E., Avcı, M., Aydın, O. (2021). Investigation of the Effect of Air Change Rate on Contaminant Removal Performance. Politeknik Dergisi, Cilt: 24 Sayı: 2, 453–459. https://doi.org/10.2339/politeknik.660484

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (15)

  1. Jones A. P., "Indoor air quality and health", Atmospheric Environment, 33: 4535–4564, (1999)
  2. Pope C. A., Dockery D. W., "Health effects of fine particulate air pollution: Lines that connect", Journal of the Air and Waste Management Association, 56: 709–742, (2006)
  3. Thurston G. D., Burnett R. T., Turner M. C., Shi Y., Krewski D., Lall R., Ito K., Jerrett M., Gapstur S. M., Ryan Diver W., Pope C. A., "Ischemic heart disease mortality and long-term exposure to source-related components of U.S. fine particle air pollution", Environmental Health Perspectives, 124: 785–794, (2016)
  4. Kircher K., Shi X., Patil S., Zhang K. M., "Cleanroom energy efficiency strategies: Modeling and simulation", Energy and Buildings, 42: 282–289, (2010)
  5. Wang X., Zhang Y., Zhao L. Y., Riskowski G. L., "Effect of ventilation rate on dust spatial distribution in a mechanically ventilated airspace", Transactions of the ASAE, 43: 1877–1884, (2000)
  6. Jin M., Memarzadeh F., Lee K., Chen Q., "Experimental study of ventilation performance in laboratories with chemical spills", Building and Environment, 57: 327–335, (2012)
  7. Memarzadeh F., Xu W., "Role of air changes per hour (ACH) in possible transmission of airborne infections", Building Simulation, 5: 15–28, (2012)
  8. Faulkner W.B., Memarzadeh F., Riskowski G., Hamilton K., Chang C. Z., Chang J. R., "Particulate concentrations within a reduced-scale room operated at various air exchange rates", Building and Environment, 65: 71–80, (2013)
  9. Faulkner W. B., Memarzadeh F., Riskowski G., Kalbasi A., Chang A. C. Z., "Effects of air exchange rate, particle size and injection place on particle concentrations within a reduced-scale room", Building and Environment, 92: 246–255, (2015)
  10. Posner J. D., Buchanan C. R., Dunn-Rankin D., "Measurement and prediction of indoor air flow in a model room", Energy and Buildings, 35: 515–526, (2003)
  11. Zhang Z., Zhang W., Zhai Z. J., Chen Q., "Evaluation of various turbulence models in predicting airflow and turbulence in enclosed environments by CFD: Part 2—comparison with experimental data from literature", HVAC&R Research, 13: 871–886, (2007)
  12. ANSYS Inc, Ansys Fluent Theory Guide, Canonsburg, PA, 2013
  13. Hinds W. C., Aerosol Technology: Properties, Behaviour, and Measurements of Airborne Particles, 2nd ed., John Wiley & Sons Inc., 1999
  14. Awbi H., Ventilation of buildings, 2nd ed., Spon press, London, 2003
  15. Nielsen P. V., Lecture Notes on Scale-Model Experiments, 1999. http://vbn.aau.dk/en/publications/lecture-notes-on-scalemodel-experiments(d5ffe240-a869-11da-8341-000ea68e967b).html