Dergiler / European Journal of Biology / 2020 / Cilt: 79 - Sayı: 1

Comparison of the Anti-Legionella Fill Material against Standard Polypropylene Fill Material in Model Cooling Tower Water System

Sayfa
62–66
DOI
—

Abstract

Objective: Cooling towers are heat exchangers which are utilized in specific industrial devices. They possess the potentialto support Legionella bacteria. The objective was to evaluate the efficacy of biocide impregnated polymer against regularpolypropylene polymer in terms of anti-Legionella features during a 120-day period.Materials and Methods: To reduce the bacterial colonization in towers, anti-Legionella splash fill and regular polypropylenesplash fill material were tested to compare anti-Legionella activity and biofilm formation potential within a 120-day periodusing a lab-scale recirculating cooling tower model system. The system was experimentally infected with Legionellasuspension and operated continuously for 120 days.Results: Legionella colonization occurred on both test material surfaces beginning at the first month. Legionella counts onsurfaces were increased over time on standard polypropylene surfaces. The product with anti-Legionella activity showedsignificantly lower Legionella colonization in comparison to standard polypropylene fill.Conclusion: The product with anti-Legionella activity has a significant biocidal effect against surface-associated Legionellaunder the above-mentioned conditions which mimics cooling tower water systems. Product seems to facilitate effectivecontrol program criteria against Legionella colonization in cooling towers.