Dergiler / International Journal of Energy and Smart Grid / 2021 / Cilt: 6 - Sayı: 1-2

ELIMINATION OF HARMONIC COMPONENTS IN SOLAR SYSTEM WITH L AND LC PASSIVE FILTERS

Sayfa
14–27
Yayın Tarihi
2021-12-31
DOI
—
🏛️Bu makalenin bibliyografik verileri ve tam metin bağlantısı DergiPark üzerinden sağlanmıştır.
DergiPark Kaydı ↗
✨

Yapay Zeka Hızlı Bakış & Çıkarımlar

AI Insight
⚡ TL;DR(1 Cümlede Hızlı Çıkarım)

As a result, LC filter improves both the system efficiency and reduce the THDI value.

📌 3 Maddede Bu Makale

🎯
Amaç & Hipotez:As a result of the increase in the use of power electronics-based converters (DC/DC to DC/AC) and non-linear loads, harmonic components occur in the solar networks.
📊
Temel Bulgular & Veri:Six pulse uncontrolled rectifier used as load in off-grid solar system produces 5th, 7th, 11th, 13th etc. harmonic components.
💡
Sonuç & Katkı:As a result, LC filter improves both the system efficiency and reduce the THDI value.
🔬Tür:Modelleme & Sayısal Simülasyon
📍Kapsam:Genişletilmiş Akademik Örneklem
⚙️Değişkenler:: L filter · LC filter · Solar Inverter

Abstract

As a result of the increase in the use of power electronics-based converters (DC/DC to DC/AC) and non-linear loads, harmonic components occur in the solar networks. It is quite common to use passive LC and L filters to eliminate harmonics in the solar PV systems. The solar system analyzed and modeled consists of solar panels, DC boost converter, PWM controlled solar inverter and six pulsed uncontrolled rectifier. Six pulse uncontrolled rectifier used as load in off-grid solar system produces 5th, 7th, 11th, 13th etc. harmonic components. LC and L filters are used to reduce the solar inverter output current total harmonic distortion (THDI). In the solar system, the THDI value has been reduced to the limit values given by the standards.. LC and L filters are commonly used to eliminate harmonics in solar system. Their widespread use is due to their easy structure and control. Modeling and simulation of the stand-alone PV power system was carried out with Matlab/Simulink program. While the value of THDI was reduced from 91.55% to 2.62% with the LC filter, the value of THDI was reduced to 5.73% with the L filter. It has been observed that the performance of the LC in eliminating the harmonic components is better than the L filter. As a result, LC filter improves both the system efficiency and reduce the THDI value.

🔖

Bu Makaleye Atıf Yap

ADAK, S., CANGİ, H. (2021). ELIMINATION OF HARMONIC COMPONENTS IN SOLAR SYSTEM WITH L AND LC PASSIVE FILTERS. International Journal of Energy and Smart Grid, Cilt: 6 - Sayı: 1-2, 14–27. https://ajindex.com/articles/766542

📄 Tam Metin PDF Okuyucu

📄

PDF görüntüleyici hazırlanıyor...

Kaynakça (11)

  1. Liu, Q., Peng, L., Kang, Y. S., Tang, D., Wu, L. and Qi, Y., A novel design and optimization method of an LCL filter for a shunt active power filter,” IEEE Trans. Ind. Electron., 61(2014), 8, pp. 4000–4010.
  2. Haydaroğlu, C., & Gümüş, B. (2017). Investigation of the effect of short term environmental contamination on energy production in photovoltaic panels: Dicle University solar power plant example. Applied Solar Energy, 53(20017), 1, pp. 31-34
  3. Rüstemli, S., Okuducu, E., Efe, S. B., Elektrik Tesislerinde Harmoniklerin Pasif Filtre Kullanılarak Azaltılması ve Simülasyonu, EVK2015, Enerji Verimliliği Kalitesi Sempozyumu, 6(2015), pp.120-124, 4-6
  4. Haziran, Sakarya. Cangi, H., Adak, S., Analysis of solar inverter THD according to PWM’s carrier frequency, IEEE Xplore Digital Library, DOI 10.1109/ICRERA. (2015), 7418694, INSPEC Accession no:15807201. Ozdemir, A. Ferikoglu, A., Low cost mixed-signal microcontroller based power measurement technique, IEE Proceedings-Science Measurement And Technology, 151(2004), pp.253-258, ISSN: 1350-2344 - DOI: 10.1049/ip-smt:20040242 - JUL - - Article - - 2004 - WOS:000222969400004. Malla, S. G., Bhende, C.N., Elsevier: International Journal of Electrical Power & Energy Systems, 56 (2014), pp. 361-373.
  5. San-Sebastian, J., Etxeberria-Otadui, I. A., Rujas, Barrena, J. A. and Rodriguez, P. (2012). Optimized LCL filter design methodology applied to MV grid-connected multimegawatt VSC, in Energy Conversion Congress and Exposition (ECCE), IEEE, (2012), pp. 2506-2512.
  6. TavakoliBina, M., and Pashajavid, E., An efficient procedure to design passive LCL filters for active power filters, Electric Power Systems Research, 79(2009), 4, pp. 606–614.
  7. Muhlethaler, J., Schweizer, M. Blattmann, R. J., Kolar, W. and Ecklebe, A. (2013). Optimal design of LCL harmonic filters for three-phase PFC rectifiers, Power Electronics, IEEE Transactions on, 28(2013), 7, pp. 3114-3125.
  8. Sekkeli, M., Tarkan N., Development of a novel method for optimal use of a newly designed reactive power control relay. International Journal of Electrical Power and Energy Systems, 44 (2013), pp.736-742.
  9. Arifoğlu, U., Matlab9.1-Simulink ve Mühendislik Uygulamaları, Alfa Yayıncılık, 964p. İstanbul-Turkey, 2016.
  10. Liserre, M., Blaabjerg, and Hansen, S. Design and Control of an LCL-Filter-Based Three-Phase Active Rectifier, IEEE Transactions on Industry Applications, 41(2005), 5, pp. 1281-1291.
  11. Adak, S., Cangi, H., Analysis and Simulation Total Harmonic Distortion of Output Voltage T