Dergiler / Journal of Thermal Engineering / 2018 / Cilt: 4 - Sayı: 6

EXPERIMENTAL EXAMINATION OF HEAT TRANSFER PERFORMANCE OF THE HEATED RADIANT WALL SYSTEM

Sayfa
2394–2407
Yayın Tarihi
2022-10-18
DOI
—
🏛️Bu makalenin bibliyografik verileri ve tam metin bağlantısı DergiPark üzerinden sağlanmıştır.
DergiPark Kaydı ↗
✨

Yapay Zeka Hızlı Bakış & Çıkarımlar

AI Insight
⚡ TL;DR(1 Cümlede Hızlı Çıkarım)

According to the results, the approximate mean values of 2.40, 5.49 and 8.29 W/m2K were evaluated, respectively for the convective, radiant and total heat transfer coefficients of radiant wall heating systems.

📌 3 Maddede Bu Makale

🎯
Amaç & Hipotez:In recent years, radiant heating systems have been catching more observation under favor of the many advantages such as; energy saving and thermal comfort.
📊
Temel Bulgular & Veri:In this regard, to evaluate the heat transfer coefficients of the radiant wall panels, 10 different test cases were run using different supply water temperatures.
💡
Sonuç & Katkı:According to the results, the approximate mean values of 2.40, 5.49 and 8.29 W/m2K were evaluated, respectively for the convective, radiant and total heat transfer coefficients of radiant wall heating systems.
🔬Tür:Araştırma Makalesi
📍Kapsam:Genişletilmiş Akademik Örneklem
⚙️Değişkenler:Radiant Heating · Heat Transfer Coefficient · Radiant Wall Heating

Abstract

In recent years, radiant heating systems have been catching more observation under favor of the many advantages such as; energy saving and thermal comfort. However, owing the fact that limited information on the system dynamics and the heat transfer characteristics of radiant systems, conventional systems are still preferred to radiant systems. Thereupon, radiant ceiling and floor systems are favored to wall systems. Also previous researchers have focused on radiant ceiling and floor systems instead of radiant wall systems. For this reason, a controlled climatic test set-up was built and detailed examinations were conducted. In this regard, to evaluate the heat transfer coefficients of the radiant wall panels, 10 different test cases were run using different supply water temperatures. On the basis of the obtained measurements, in the steady state, heat transfer coefficients, depending on the characteristic temperature differences and the heat transfer rates have been calculated. According to the results, the approximate mean values of 2.40, 5.49 and 8.29 W/m2K were evaluated, respectively for the convective, radiant and total heat transfer coefficients of radiant wall heating systems.

🔖

Bu Makaleye Atıf Yap

KOCA, A. (2022). EXPERIMENTAL EXAMINATION OF HEAT TRANSFER PERFORMANCE OF THE HEATED RADIANT WALL SYSTEM. Journal of Thermal Engineering, Cilt: 4 - Sayı: 6, 2394–2407. https://ajindex.com/articles/566826

📄 Tam Metin PDF Okuyucu

📄

PDF görüntüleyici hazırlanıyor...

Kaynakça (15)

  1. Okamoto, S., Kitora, H., Yamaguchi, H., Oka, T., (2010). A simplified calculation method for estimating heat flux from ceiling radiant panels. Energy and Buildings, 42, 29-33
  2. Imanari, T., Omori, T., Bogaki, K. (1999). Thermal comfort and energy consumption of the radiant ceiling panel system, comparison with the conventional all-air system. Energy and Buildings, 30, 167-175
  3. Stetiu, C. (1999). Energy and peak power savings potential of radiant cooling systems in U.S. commercial buildings. Energy and Buildings, 30, 127-138
  4. Milorad, B., Dragan, C. (2012). Energy, cost, and CO2 emission comparison between radiant wall panel systems and radiator systems. Energy and Buildings, 54, 496-502
  5. DeWerth, D.W., Loria, R.L. (1989). In-space Heater Energy Use for Supplemental and Whole House Heating. ASHRAE Transaction, 95 (1), 239-250
  6. Franc, S. (1999). Economic Viability of Cooling Ceiling Systems. Energy and Building, 30, 195-201
  7. Catalina, T., Virgone, J., Kuznik, F. (2009). Evaluation of thermal comfort using combined CFD and experimentation study in a test room equipped with a cooling ceiling. Building and Environment, 44, 1740-1750
  8. Dudkiewicz, E., Jezowiecki, J. (2009). Measured Radiant Thermal Fields in Industrial Spaces Served by High Intensity Infrared Heater. Energy and Buildings, 41, 27-35
  9. Myhren, J. A., Holmberg, S. (2009). Flow Patterns and Thermal Comfort in a Room with Panel, Floor and Wall Heating. Energy and Buildings, 40, 524-536
  10. Koca, A., Gemici, Z., Bedir, K. (2014). Thermal comfort analysis of novel low exergy radiant heating cooling system and energy saving potential comparing to conventional systems. Progress in Exergy, Energy and Environment, Springer International Publishing, Switzerland, 38, 435-445
  11. Koca, A., Gemici, Z., Topaçoğlu, Y., Çetin, G., Acet, R.C., Kanbur, B.B. (2013). Işınım ısıtma ve soğutma sistemlerinin ısıl konfor analizleri
  12. Ulusal tesisat mühendisliği kongresi, İzmir, 2025-2042
  13. Manuel, A., Tejero-González, A. (2012). Experimental Study on the Cooling Capacity of a Radiant Cooled Ceiling System. Energy and Buildings, 54, 207-214
  14. Causone, F., Corgnati, S.P., Filippi, M., Olesen, W.B. (2009). Experimental evaluation of heat transfer coefficients between radiant ceiling and room. Energy Buildings, 41, 622-628
  15. Miriel, J., Serres, L., Trombe, A. (2002). Radiant ceiling panel heating-cooling systems: experimental and simulated study of the performances, thermal