At above pressures of 400 kPa and 15 mm electrode gap spacing, there exists a critical field where the breakdown voltage of CO2 has a maximum value.
📌 3 Maddede Bu Makale
🎯
Amaç & Hipotez:AC breakdown strengths of CO2, N2, SF6 and air in non-uniform field were experimentally studied.
📊
Temel Bulgular & Veri:The experimental results have shown that the breakdown voltages of SF6 in the practical range of pressure (100-200 kPa) are always higher than those of other gases.
💡
Sonuç & Katkı:At above pressures of 400 kPa and 15 mm electrode gap spacing, there exists a critical field where the breakdown voltage of CO2 has a maximum value.
🔬Tür:Araştırma Makalesi
📍Kapsam:Genişletilmiş Akademik Örneklem
⚙️Değişkenler:Alan Parametreleri
Abstract
AC breakdown strengths of CO2, N2, SF6 and air in non-uniform field were experimentally studied. The experimental results have shown that the breakdown voltages of SF6 in the practical range of pressure (100-200 kPa) are always higher than those of other gases. Although at short gaps, the breakdown strength of SF6 is superior at the pressure range from 100-500 kPa, at 25 mm electrode gap spacing and 300 kPa the breakdown voltage of air is %7.8 higher than that of SF6. At above pressures of 400 kPa and 15 mm electrode gap spacing, there exists a critical field where the breakdown voltage of CO2 has a maximum value.
🔖
Bu Makaleye Atıf Yap
ÖNAL, E. (2022). Breakdown characteristics of gases in non-uniform fields. Istanbul University Journal of Electrical and Electronics Engineering, Cilt: 4 - Sayı: 2, 1177–1182. https://ajindex.com/articles/543873
Malik, N. H., Qureshi, A H., “A review of electrical breakdown in mixtures of SF6 and other gases", IEEE Trans. Electrical Insulation, Vol. EI-14, No. 1, pp. 1-11, Feb 1979
Olivier, G., Gervais, Y., Mukhedkar, D., "A new approach to compute uniform field breakdown of gases", IEEE Trans. on Power Apparatus and Systems, Vol. PAS-97, pp. 969-976, 1978
Malik, N. H., Qureshi, A. H., "Breakdown gradients for SF6+N2, SF6+CO2 and SF6+air mixtures", IEEE Transactions on Electrical Insulation, Vol. 15, No. 5, pp. 413-418, 1980
Malik, N. H., Qureshi, A. H., Theophilus, G. D., “Static field breakdown of SF6-N2 mixtures in rod-plane gaps", IEEE Trans. Electrical Insulation, Vol. EI-14, No. 2,, pp. 61-70, April 1979
Cookson, A. H., Pedersen, B. O., "High voltage performance of mixtures of SF6 with N2, air and CO2 in compressed gas insulated equipment", Proceedings Fifth Int. Conf. on Gas Discharges, pp. 161-164, 1978
Qiu, Y., Xiao, D. M., "Dielectric strength of the SF6+CO2 gas mixture in different electric fields", Ninth International Symposium on High Voltage Engineering, Graz, Sept., Paper 2255-1-4, 1995
Kuffel, E., Yializis, A., “Impulse breakdown of positive and negative rod plane gaps in SF6-N2 mixtures", IEEE Trans. on Power Apparatus and Systems, Vol. PAS-97, No. 6, Nov-Dec, pp. 2359-2366, 1978
Safar, Y. A., Malik, N. H., Qureshi A. H., "Impulse breakdown behavior of negative rod plane gaps in SF6+N2, SF6+air and SF6+CO2 mixtures", IEEE Trans. on Electrical Insulation, Vol. 17, No. 5, pp. 441-449, October 1982
Medeiros, P.T, Naidu, S.R., "Positive and negative lightning impulse breakdown of rod-plane gaps in nitrogen", Conference of Electrical and Dielectric Phenomena, Annual Report, New York, pp.48-53, 1983
Yializis, A., Malik, N. H., Qureshi A. H., Kuffel, E., “Impulse breakdown and corona characteristics for rod-plane gaps in mixtures of SF6 and nitrogen with less than 1% of SF6 content", IEEE Trans. on Power Apparatus and Systems, Vol. PAS-98, No. 5, pp. 1832-1839, Sep-Oct 1979
Chalmers, L. D., Qiu, X. Q., Coventry, P., "The Study of SF6 Mixtures with Buffer Gases”, Gaseous Dielectrics VIII, pp. 189-195, 1998
Rajendran, T. V., Lakshminarasimha, C. S., Naidu M. S., "Effect of electrode geometry on positive impulse breakdown in carbon dioxide", IEEE Trans. on Electrical Insulation, Vol. EI-18, No. 4, pp. 455-457, August 1983
Önal, E., Kalenderli, Ö., Mardikyan, K., ”Breakdown Characteristics