A NOVEL OCCUPANT DETECTION-BASED VENTILATION CONTROL STRATEGY FOR SMART BUILDING APPLICATIONS

Sayfa
24–35
DOI
—
🏛️Bu makalenin bibliyografik verileri ve tam metin bağlantısı DergiPark üzerinden sağlanmıştır.
DergiPark Kaydı ↗
✨

Yapay Zeka Hızlı Bakış & Çıkarımlar

AI Insight
⚡ TL;DR(1 Cümlede Hızlı Çıkarım)

The results showed that proposed controller decreased energy consumption by 16% while satisfying thermal comfort for the 94% of total number of occupants.

📌 3 Maddede Bu Makale

🎯
Amaç & Hipotez:Traditional ventilation systems supply fresh air to the building on a consistent basis, however, do not ensure adequate comfortable areas in indoor environments.
📊
Temel Bulgular & Veri:ASHRAE Standard 62, which shows ventilation strategies for acceptable indoor air quality, uses steady-state occupancy detection algorithms, however, dynamic methods are required behind simulation studies.
💡
Sonuç & Katkı:The results showed that proposed controller decreased energy consumption by 16% while satisfying thermal comfort for the 94% of total number of occupants.
🔬Tür:Araştırma Makalesi
📍Kapsam:2020 Verileri
⚙️Değişkenler:Occupant detection · Smart buildings · Ventilation systems

Abstract

Traditional ventilation systems supply fresh air to the building on a consistent basis, however, do not ensure adequate comfortable areas in indoor environments. On the other hand, smart ventilation systems adjust indoor environment parameters optionally by occupancy schedules to provide desired indoor air quality while minimizing energy consumption. ASHRAE Standard 62, which shows ventilation strategies for acceptable indoor air quality, uses steady-state occupancy detection algorithms, however, dynamic methods are required behind simulation studies. To this aim, this study presents a dynamic novel ventilation control strategy by detecting occupants in an office building in Ankara-Turkey. The novel control strategy includes deployment of several sensors which measure carbon dioxide concentration, indoor air temperature and position of the door. A prototype of the controller is manufactured and tested in a real environment with the help of regulation of air flow in HVAC system. The proposed control strategy is tested between January 1st, 2020 and August 15th, 2020 and compared with traditional controller in terms of thermal comfort and energy consumption. The results showed that proposed controller decreased energy consumption by 16% while satisfying thermal comfort for the 94% of total number of occupants.

🔖

Bu Makaleye Atıf Yap

TURHAN, C., ÇETER, A. E. (2021). A NOVEL OCCUPANT DETECTION-BASED VENTILATION CONTROL STRATEGY FOR SMART BUILDING APPLICATIONS. Mugla Journal of Science and Technology, Cilt: 7 - Sayı: 2, 24–35. https://ajindex.com/articles/396466

📄 Tam Metin PDF Okuyucu

📄

PDF görüntüleyici hazırlanıyor...

Kaynakça (12)

  1. N. Payam, J. Fatemeh, M. T. Mohammad, G. Mohammad, and M. A. Muhd Zaimi, “A global review ofenergy consumption, CO2 emissions and policy in the residential sector (with an overview of the top tenCO2emitting countries),” Renewable and Sustainable Energy Reviews, 43, 843–862, 2015.
  2. Singh, S. and Kennedy, C., “Estimating future energy use and CO2 emissions of the world's cities”, Environmental Pollution, 203, 271-278, 2015.
  3. Escriva-Escriva, G., Segura-Heras, I. and Alcazar-Ortega, M., “Application of an energy management and control system to assess the potential of different control strategies in HVAC systems”, Energy and Buildings, 42(11), 2258-2267, 2010.
  4. Rashid, S. A., Haider, Z., Hossain, S. M. C., Memon, K., Panhwar, F., Mbogba, M. K., Hu, P. and Zhao, G., “Retrofitting low-cost heating ventilation and air-conditioning systems for energy management in buildings”, Applied Energy, 236, 648-661, 2019.
  5. American Society of Heating, Refrigerating and Air-Conditioning Engineers, 2019. Ventilation for Acceptable Indoor Air Quality (Standard 62.1). Atlanta, GA: ASHRAE. Turhan, C., “Development of Energy Efficient Personalized Thermal Comfort Driven Control in HVAC Systems”, (PhD Thesis), Izmir Institute of Technology, İzmir, 127, 2018.
  6. Yang, Z. and Becerik-Gerber, B., “The coupled effects of personalized occupancy profile-based HVAC schedules and room reassignment on building energy use”, Energy and Buildings, 78, 113-122, 2014.
  7. Ansanay-Alex, G., “Estimating Occupancy Using Indoor Carbon Dioxide Concentrations Only in an Office Building: a Method and Qualitative Assessment”, In: 11th REHVA World Congress ''Energy efficient, smart and healthy buildings”: Clima, Prague, June 2013.
  8. Wang, S. W. and Jin, X. Q., “CO2-based occupancy detection for on-line outdoor air flow control”, Indoor and Built Environment, 7(3), 165-181, 1998.
  9. Cali, D., Matthes, P., Huchtmann, K., Streblow, R. and Muller, D., “CO2 based occupancy detection algorithm: Experimental analysis and validation for office and residential buildings”, Building and Environment, 86, 39-49, 2015.
  10. Hobson, B. W., Lowcay, D., Gunay, H. B., Ashouri, A. and Newsham, G. R., “Opportunistic occupancy-count estimation using sensor fusion: A case study”, Building and Environment, 159, 106154, 2019.
  11. Candenedo, L. M. and Feldheim, V., “Accurate occupancy detection of an office room from light, temperature, humidity and CO2 measurements using statistical learning models”, Energy and Buildings, 112, 28-39, 2016.
  12. Masood, M.