Dergiler / Turkish Journal of Electrical Engineering and Computer Science / 2019 / Cilt: 27 - Sayı: 3

Energy and economic assessment of major free cooling retrofits for data centers in Turkey

Sayfa
2097–2212
Yayın Tarihi
2019-06-01
DOI
—
🏛️Bu makalenin bibliyografik verileri ve tam metin bağlantısı DergiPark üzerinden sağlanmıştır.
DergiPark Kaydı ↗
✨

Yapay Zeka Hızlı Bakış & Çıkarımlar

AI Insight
⚡ TL;DR(1 Cümlede Hızlı Çıkarım)

However, despite greater energy-saving potential, IEC has more extended payback periods of 1.5 to 3.7 years due to the high capital investment compared with those of ASE and WSE with less than 1.4 years.

📌 3 Maddede Bu Makale

🎯
Amaç & Hipotez:Mechanical cooling is responsible for a significant fraction of the energy consumption of data centers (DCs).
📊
Temel Bulgular & Veri:This study utilizes thermodynamic models of major free cooling systems such as the direct air-side economizer (ASE), indirect air-side economizer (IASE), indirect evaporative cooler (IEC), and indirect water-side economizer (WSE) integrated with the existing cooling infrastructure of a typical 1 MW IT load DC.
💡
Sonuç & Katkı:However, despite greater energy-saving potential, IEC has more extended payback periods of 1.5 to 3.7 years due to the high capital investment compared with those of ASE and WSE with less than 1.4 years.
🔬Tür:Modelleme & Sayısal Simülasyon
📍Kapsam:Genişletilmiş Akademik Örneklem
⚙️Değişkenler:Data centers · Turkey · free cooling

Abstract

Mechanical cooling is responsible for a significant fraction of the energy consumption of data centers (DCs). Free cooling systems take advantage of ambient conditions to reduce the need for compressor-based cooling. This study utilizes thermodynamic models of major free cooling systems such as the direct air-side economizer (ASE), indirect air-side economizer (IASE), indirect evaporative cooler (IEC), and indirect water-side economizer (WSE) integrated with the existing cooling infrastructure of a typical 1 MW IT load DC. Proposed models utilize hourly weather data of various cities in Turkey to compute annual energy consumption and cost-saving potentials of each free cooling method with respect to the baseline DC with both open aisle (OA) and enclosed aisle (EA). Results confirm the energy-saving potential by IEC leading to less than 10 % of annual chiller hours across Turkey and less than 1 % in half of the ten cities studied, especially in EA DCs. However, despite greater energy-saving potential, IEC has more extended payback periods of 1.5 to 3.7 years due to the high capital investment compared with those of ASE and WSE with less than 1.4 years.

🔖

Bu Makaleye Atıf Yap

GÖZCÜ, O., ERDEN, H. S. (2019). Energy and economic assessment of major free cooling retrofits for data centers in Turkey. Turkish Journal of Electrical Engineering and Computer Science, Cilt: 27 - Sayı: 3, 2097–2212. https://ajindex.com/articles/186841

📄 Tam Metin PDF Okuyucu

📄

PDF görüntüleyici hazırlanıyor...