Dergiler / Turkish Journal of Biology / 2012 / Cilt: 36 - Sayı: 3

Biofilm formation comparison of the SANIPACKING® cooling tower fill material against standard polypropylene fill material in a recirculating model water system

Sayfa
313–318
Yayın Tarihi
2012-03-01
DOI
—
🏛️Bu makalenin bibliyografik verileri ve tam metin bağlantısı DergiPark üzerinden sağlanmıştır.
DergiPark Kaydı ↗
✨

Yapay Zeka Hızlı Bakış & Çıkarımlar

AI Insight
⚡ TL;DR(1 Cümlede Hızlı Çıkarım)

Total bacterial counts on surfaces, determined by epifluorescence microscopy (using DAPI), revealed that significantly low counts of microorganisms colonized on the SANIPACKING® surface.

📌 3 Maddede Bu Makale

🎯
Amaç & Hipotez:Cooling towers are heat rejection systems that are used in some industrial applications, and they have the potential to develop infectious concentrations of Legionella pneumophila.
📊
Temel Bulgular & Veri:SANIPACKING® cooling tower fill material and standard polypropylene fill material were compared in terms of biofilm formation potential and anti-Legionella activity within a 4-month period using a laboratory-scale recirculating water system.
💡
Sonuç & Katkı:Total bacterial counts on surfaces, determined by epifluorescence microscopy (using DAPI), revealed that significantly low counts of microorganisms colonized on the SANIPACKING® surface.
🔬Tür:Modelleme & Sayısal Simülasyon
📍Kapsam:Genişletilmiş Akademik Örneklem
⚙️Değişkenler:Key words: Biofilm · SANIPACKING® · Legionella

Özet

Cooling towers are heat rejection systems that are used in some industrial applications, and they have the potential to develop infectious concentrations of Legionella pneumophila. SANIPACKING® cooling tower fill material and standard polypropylene fill material were compared in terms of biofilm formation potential and anti-Legionella activity within a 4-month period using a laboratory-scale recirculating water system. The recirculating water system was experimentally infected with a L. pneumophila standard strain (ATCC 33152) suspension and operated continuously until all experiments had been completed. Results showed that the L. pneumophila rapidly multiplied in a short time during the study within the model system bulk water. No L. pneumophila was isolated from the SANIPACKING® surface during the 4-month period, whereas intensive colonization occurred on the standard polypropylene material surface in the first month. Heterotrophic bacterial counts on the surfaces showed that a significantly low accumulation was recorded on the SANIPACKING® surface in comparison to the standard polypropylene material. Total bacterial counts on surfaces, determined by epifluorescence microscopy (using DAPI), revealed that significantly low counts of microorganisms colonized on the SANIPACKING® surface.

Abstract

Cooling towers are heat rejection systems that are used in some industrial applications, and they have the potential to develop infectious concentrations of Legionella pneumophila. SANIPACKING® cooling tower fill material and standard polypropylene fill material were compared in terms of biofilm formation potential and anti-Legionella activity within a 4-month period using a laboratory-scale recirculating water system. The recirculating water system was experimentally infected with a L. pneumophila standard strain (ATCC 33152) suspension and operated continuously until all experiments had been completed. Results showed that the L. pneumophila rapidly multiplied in a short time during the study within the model system bulk water. No L. pneumophila was isolated from the SANIPACKING® surface during the 4-month period, whereas intensive colonization occurred on the standard polypropylene material surface in the first month. Heterotrophic bacterial counts on the surfaces showed that a significantly low accumulation was recorded on the SANIPACKING® surface in comparison to the standard polypropylene material. Total bacterial counts on surfaces, determined by epifluorescence microscopy (using DAPI), revealed that significantly low counts of microorganisms colonized on the SANIPACKING® surface.

🔖

Bu Makaleye Atıf Yap

TÜRETGEN, İ., YÜRÜDÜ, N. Ö. Ş., NORDEN, İ. (2012). Biofilm formation comparison of the SANIPACKING® cooling tower fill material against standard polypropylene fill material in a recirculating model water system. Turkish Journal of Biology, Cilt: 36 - Sayı: 3, 313–318. https://ajindex.com/articles/182509

📄 Tam Metin PDF Okuyucu

📄

PDF görüntüleyici hazırlanıyor...

Kaynakça (17)

  1. Yu VL. Could aspiration be the major mode of transmission for Legionella? Am J Med 95: 13-15, 1993
  2. Yamamoto H, Sugiura M, Kusunoki E et al. Factors stimulating propagation of legionellae in cooling tower water. Appl Environ Microbiol 58: 1394-1397, 1992
  3. Bentham RH. Routine sampling and the control of Legionella spp. in cooling tower water systems. Curr Microbiol 41: 271- 275, 2000
  4. Türetgen I, Sungur EI, Cotuk A. Enumeration of Legionella pneumophila in cooling tower water systems. Environ Monit Assess 100: 53-58, 2005
  5. Costerton JW. Introduction to biofi lm. Int J Antimic Agents 11: 217-221, 1999
  6. Tsuneda S, Jung J, Hayashi H et al. Infl uence of extracellular polymers on electrokinetic properties of heterotrophic bacterial cells examined by soft particle electrophoresis theory. Coll Surf 29: 181-188, 2003
  7. Harris A. Problems associated with biofi lms in cooling tower systems. In: Keevil CV, Godfree A, Holt D, Dow C. eds. Biofi lms in the Aquatic Environment. Springer-Verlag; 2000: pp. 139-144
  8. Flemming HC. Role and levels of real-time monitoring for successful anti-fouling strategies - an overview. Wat Sci Technol 47: 1-8, 2003
  9. Cloete TE, Jacobs L, Brözel VS. Th e chemical control of biofouling in industrial water systems. Biodegredation 9: 23- 37, 1998
  10. Lück PC. Ecology and control of Legionella and Pseudomonas bacteria in drinking water systems. Tenth International Symposium on District Heating and Cooling, 2006
  11. Melo LF, Bott TR. Biofouling in water systems. Exp Th er Flu Sci 14: 375-381, 1997
  12. Rusin P, Bright K, Gerba C. Rapid reduction of Legionella pneumophila on stainless steel with zeolite coatings containing silver and zinc ions. Lett Appl Microbiol 36: 69-72, 2003
  13. Gagnon GA, Slawson RM. An effi cient biofi lm removal method for bacterial cells exposed to drinking water. J Microbiol Meth 34: 203-214, 1999
  14. Bopp CA, Sumner JW, Morris GK et al. Isolation of Legionella spp. from environmental water samples by low-pH treatment and use of a selective medium. J Clin Bacteriol 13: 714-719, 1981
  15. Dennis PJL. Isolation of legionellae from environmental specimens. In: Harrison TG, Taylor AG. eds. A Laboratory Manual for Legionella. Wiley; 1988: pp. 31-44
  16. Sedgwick AK, Tilton RC. Identifi cation of Legionella pneumophila by latex agglutination. J Clin Bacteriol 2: 365- 369, 1982
  17. Rodriguez GG, Phipps D, Ishiguro K et al. Use of a fl uorescent redox probe for direct visualization of actively res