Experimental investigation of thermal comfort performance of a radiant wall and ceiling panel system

Ahmet Doğan(Department of Mechanical Engineering, Yıldız Technical University, İstanbul, Türkiye)0000-0003-1121-5480
Nurullah Kayacı(Department of Mechanical Engineering, Tekirdağ Namık Kemal University, Tekirdağ, Türkiye)0000-0002-8843-8191
Hakan Demir(Department of Mechanical Engineering, Yıldız Technical University, İstanbul, Türkiye)0000-0002-6891-0831
Mustafa Kemal Sevindir(Department of Mechanical Engineering, Yıldız Technical University, İstanbul, Türkiye)0000-0003-1210-1880
Sayfa
—
Yayın Tarihi
2022-07-29
🏛️Bu makalenin bibliyografik verileri ve tam metin bağlantısı DergiPark üzerinden sağlanmıştır.
DergiPark Kaydı ↗
✨

Yapay Zeka Hızlı Bakış & Çıkarımlar

AI Insight
⚡ TL;DR(1 Cümlede Hızlı Çıkarım)

In the experiment carried out under the conditions of Case 2, while the comfort conditions were provided in almost all of the day, the desired comfort conditions could not be achieved in Case 1 after 11 am.

📌 3 Maddede Bu Makale

🎯
Amaç & Hipotez:The number of radiant heating-cooling systems in building applications is increasing it is because of low energy consumption, low operating temperature and high values they provide in terms of working compatibility with renewable energy sources.
📊
Temel Bulgular & Veri:In this study, ground source heat pump integrated radiant panels installed on the wall and suspended ceiling of the office room in Yıldız Technical University Science and Technology Application and Research Centre were experimentally examined in terms of thermal comfort according to the relevant standards.
💡
Sonuç & Katkı:In the experiment carried out under the conditions of Case 2, while the comfort conditions were provided in almost all of the day, the desired comfort conditions could not be achieved in Case 1 after 11 am.
🔬Tür:Research Article
📍Kapsam:Genişletilmiş Akademik Örneklem
⚙️Değişkenler:GSHP · Heat Pump · Radiant Systems

Abstract

The number of radiant heating-cooling systems in building applications is increasing it is because of low energy consumption, low operating temperature and high values they provide in terms of working compatibility with renewable energy sources. In this study, ground source heat pump integrated radiant panels installed on the wall and suspended ceiling of the office room in Yıldız Technical University Science and Technology Application and Research Centre were experimentally examined in terms of thermal comfort according to the relevant standards. Vertical air temperature differences and mean radiant temperatures were investigated. The mean air temperature differences at 0.1 m and 1.7 m were found to be 3,9 oC 2.9 oC 3.5 oC, 3.1 oC and 3.4 oC on average for the five different stands, respectively. PMV and PPD values were found to be 0.78 and 18.9% for February 12 (Case 1), 0.36 and 8.4% for February 13 (Case 2), respectively. In the experiment carried out under the conditions of Case 2, while the comfort conditions were provided in almost all of the day, the desired comfort conditions could not be achieved in Case 1 after 11 am.

🔖

Bu Makaleye Atıf Yap

Doğan, A., Kayacı, N., Demir, H., Sevindir, M. K. (2022). Experimental investigation of thermal comfort performance of a radiant wall and ceiling panel system. Journal of Thermal Engineering, Volume: 8 Issue: 4. https://doi.org/10.18186/thermal.1149161