SPACE COOLING WITH GROUNDWATER PUMPED BY A SOLAR DRIVEN PUMP

Sayfa
1106–1117
Yayın Tarihi
2023-12-01
DOI
—
🏛️Bu makalenin bibliyografik verileri ve tam metin bağlantısı DergiPark üzerinden sağlanmıştır.
DergiPark Kaydı ↗
✨

Yapay Zeka Hızlı Bakış & Çıkarımlar

AI Insight
⚡ TL;DR(1 Cümlede Hızlı Çıkarım)

Although in both experiments the cooling load was not fully met and the temperature inside the structure rose slightly during the experiment, it was kept cool.

📌 3 Maddede Bu Makale

🎯
Amaç & Hipotez:In this study, it was experimentally investigated that the groundwater of a well is brought to the surface using solar energy, which is one of the renewable energy sources, and the cooling of a place with this water with low energy density.
📊
Temel Bulgular & Veri:The study evaluated cooling performance on two different days (Exp. 1 and Exp. 2) and at two different cooling water flow rates.
💡
Sonuç & Katkı:Although in both experiments the cooling load was not fully met and the temperature inside the structure rose slightly during the experiment, it was kept cool.
🔬Tür:Araştırma Makalesi
📍Kapsam:Genişletilmiş Akademik Örneklem
⚙️Değişkenler:Solar water pumping · Space cooling · Cooling performance

Abstract

In this study, it was experimentally investigated that the groundwater of a well is brought to the surface using solar energy, which is one of the renewable energy sources, and the cooling of a place with this water with low energy density. The study evaluated cooling performance on two different days (Exp. 1 and Exp. 2) and at two different cooling water flow rates. The efficiency of the PV system was found to be 8.33±0.44% in Exp. 1 and 8.3±0.44% in Exp. 2. The cooling loads of the cooled buildings differ in Exp. 1 and Exp. 2 due to ambient conditions. The cooling load in Exp. 1 was determined to be 572±22.8 W and in Exp. 2 about 828±33.1 W. The heat loads extracted from the building by the groundwater used as a cooling fluid are 410±16.4 W and 786±31.4 W for Exp. 1 and Exp. 2. The cooling performance evaluation criteria (CPEP) value was found to be 0.72 for Exp. 1 and 0.95 for Exp. 2. Although there was a significant difference between the cooling loads for Exp. 1 and Exp. 2, the cooling load coverage increased with the increase in cooling water flow rate according to the CPEP values. Although in both experiments the cooling load was not fully met and the temperature inside the structure rose slightly during the experiment, it was kept cool.

🔖

Bu Makaleye Atıf Yap

DUMRUL, H., SELİMLİ, S., YILMAZ, S., KORKMAZ, B. (2023). SPACE COOLING WITH GROUNDWATER PUMPED BY A SOLAR DRIVEN PUMP. Konya Journal of Engineering Sciences, Cilt: 11 Sayı: 4, 1106–1117. https://ajindex.com/articles/1019772

📄 Tam Metin PDF Okuyucu

📄

PDF görüntüleyici hazırlanıyor...

Kaynakça (7)

  1. E. Özbaş, “Experimental study of thermal performance and pressure differences of different working fluids in two-phase closed thermosyphons using solar energy,” Journal of Polytechnic, vol. 22, no. 1, pp. 121–128, 2018. P. Sahw and P. Gaur, “Photovoltaic Powered Centrifugal Water Pump,” International Journal of Electronic and Electrical Engineering, vol. 7, no. 3, pp. 247–254, 2014.
  2. M. S. Y. Ebaid, H. Qandil, and M. Hammad, “A unified approach for designing a photovoltaic solar system for the underground water pumping well-34 at Disi aquifer,” Energy Conversion and Management, vol. 75, pp. 780–795, 2013.
  3. P. K. S. Rathore, S. S. Das, and D. S. Chauhan, “Perspectives of solar photovoltaic water pumping for irrigation in India,” Energy Strategy Reviews, vol. 22, pp. 385–395, 2018. R. Kumar and B. Singh, "Buck-boost converter fed BLDC motor drive for solar PV array based water pumping," 2014 IEEE International Conference on Power Electronics, Drives and Energy Systems (PEDES), 2014, pp. 1-6. K. Speidel, “Simple water pump, powered by solar energy,” International Symposium–Workshop on Solar Energy June 1978, 1980, pp. 1748–1761.
  4. C. Ramulu, P. Sanjeevikumar, R. Karampuri, S. Jain, A. H. Ertas, and V. Fedak, “A solar PV water pumping solution using a three-level cascaded inverter connected induction motor drive,” Engineering Science and Technology, an International Journal, vol. 19, no. 4, pp. 1731–1741, 2016. K. M. Bataineh, “Optimization analysis of solar thermal water pump,” Renewable and Sustainable Energy Reviews, vol. 55, pp. 603–613, 2016. R. Foster and A. Cota, “Solar water pumping advances and comparative economics,” Energy Procedia, vol. 57, pp. 1431–1436, 2014.
  5. A. Saini, Anish; Kohli, Shivam; Pillai, “Solar powered stirling engine driven water pump,” International Journal of Research in Engineering and Technology, vol. 02, no. 11, pp. 615–620, 2013.
  6. N. B. Yousuf, K. M. Salim, R. Haider, M. R. Alam, and F. B. Zia, “Development of a three phase induction motor controller for solar powered water pump,” in Proceedings of 2nd International Conference on the Developments in Renewable Energy Technology, ICDRET 2012, 2012, pp. 312–316.
  7. Renu, B. Bora, B. Prasad, O. S. Sastry, A. Kumar, and M. Bangar, “Optimum sizing and performance modeling of solar photovoltaic (SPV) water pumps for different climatic conditions,” Solar Energy, vol. 155, pp. 1326–1338, 2017. R. Senol, “An analysis of solar energy and irrigation systems in Turkey,” Energy Policy, vol. 47, pp. 4