AN ESTIMATE OF ENERGY CONSUMPTION FOR HOUSING BUILDINGS IN HOT CLIMATIC ZONES THROUGH ARTIFICAL INTELLIGENCE METHODS: CASE OF ANTALYA

Sayfa
273–284
Yayın Tarihi
2018-07-23
DOI
—
🏛️Bu makalenin bibliyografik verileri ve tam metin bağlantısı DergiPark üzerinden sağlanmıştır.
DergiPark Kaydı ↗
✨

Yapay Zeka Hızlı Bakış & Çıkarımlar

AI Insight
⚡ TL;DR(1 Cümlede Hızlı Çıkarım)

Of the models for which heating and cooling load calculation had not been made before, the estimates for the thermal loads were made using an energy simulation program, and it has been reached that thermal insulation thickness and window-to-wall area ratio have effect on both loads.

📌 3 Maddede Bu Makale

🎯
Amaç & Hipotez:Buildings use about one-third of total energy consumed in order to meet their heating and cooling needs.
📊
Temel Bulgular & Veri:For the energy efficient solutions, it is necessary to enhance the heating and cooling performance of the building envelope.
💡
Sonuç & Katkı:Of the models for which heating and cooling load calculation had not been made before, the estimates for the thermal loads were made using an energy simulation program, and it has been reached that thermal insulation thickness and window-to-wall area ratio have effect on both loads.
🔬Tür:Modelleme & Sayısal Simülasyon
📍Kapsam:Genişletilmiş Akademik Örneklem
⚙️Değişkenler:Thermal Performance · Heating Load · Cooling Load

Özet

Buildings use about one-third of total energy consumed in order to meet their heating and cooling needs. The building envelope that enables to protect it from physical factors in the outer environment is quite effective upon the amount of energy consumed. For the energy efficient solutions, it is necessary to enhance the heating and cooling performance of the building envelope. With this aim, in the study, the energy loads were calculated, which were consumed for heating and cooling by a building established as a reference through a simulation program in the province of Antalya, which respects a hot climatic zone, and the shifts in yearly heating and cooling loads of the alternative models were examined, which were developed by changing the thermal insulation thickness and the window-to-wall area ratio. In the study, the modern, effective artificial intelligence methods were used to enhance the energy performance of multi-dimensional buildings. Of the models for which heating and cooling load calculation had not been made before, the estimates for the thermal loads were made using an energy simulation program, and it has been reached that thermal insulation thickness and window-to-wall area ratio have effect on both loads.

🔖

Bu Makaleye Atıf Yap

HAYDARASLAN, K. S., HAYDARASLAN, E., KAHRAMAN, H. T., YAŞAR, Y. (2018). AN ESTIMATE OF ENERGY CONSUMPTION FOR HOUSING BUILDINGS IN HOT CLIMATIC ZONES THROUGH ARTIFICAL INTELLIGENCE METHODS: CASE OF ANTALYA. Technological Applied Sciences, Cilt: 13 Sayı: 3, 273–284. https://ajindex.com/articles/1007680

📄 Tam Metin PDF Okuyucu

📄

PDF görüntüleyici hazırlanıyor...

Kaynakça (14)

  1. Kaynaklı, O., (2008). A Study on Residential Heating Energy Requirement and Optimum Insulation Thickness. Renewable Energy, Volume:33, pp:1164-1172
  2. Chowdhury, A.A., Rasul, M.G., and Khan, M.M.K., (2008). Thermal-Comfort Analysis and Simulation for Various Low-Energy Cooling-Techonologies Applied to an Office Building in a Subtropical Climate. Applied Enegy, Volume:85, pp:449-462
  3. Al-Sanea, S. and Zedan M., (2011). Improving Thermal Performance of Building Walls by Optimizing Insulation Layer Distribution and Thickness for Same Thermal Mass. Applied Energy, Volume:88, pp:3113-3124
  4. Cheung, C.K., Fuller, R.J., and Luther, M.B., (2005). Energy-Efficient Envelope Design for High-Rise Apartments. Energy and Buildings, Volume:37, pp:37-48
  5. Baykal, C., (2014). Binalarda Yönlere Göre Yalıtım Kalınlığının Ekonomikliğinin Araştırılması. Master of Thesis, Natural&Applied Science, Yıldız Technical University, İstanbul
  6. Daouas, N., (2011). A Study on Optimum Insulation Thickness in Walls and Energy Savings in Tunisian Buildings Based on Analytical Calculation of Cooling and Heating Transmission Loads. Applied Energy, Volume:88, pp:156-164
  7. Tsanas, A. and Xifara, A., (2012). Accurate quantitative Estimation of Energy Performance of Residential Buildings Using Statistical Machine Learning Tools. Energy and Buildings, Volume:49, pp:560-567
  8. Maçka, S., Yaşar, Y., and Pehlevan, A., (2011). Investigating of the Effects on Building Energy Consumption and Life Cycle Cost of Building Envelope Alternatives. 12th International Conference on Durability of Building Materials and Component, Porto, Portugal
  9. General Directorate of Meteorology, Antalya Average Temperature Data, (2017. htpp://www.mgm.gov.tr
  10. Meteonorm, (2017).
  11. DesignBuilder Software, (2017).
  12. Üstün O., (2009). Determination of Activation Functions in A Feedforward Neural Network by using Genetic Algorithm. Pamukkale Üniversitesi Mühendislik Bilimleri Dergisi, Volume:15, pp:225-234
  13. Kahraman, H.T., (2016). A Novel and Powerful Hybrid Classifier Method: Development and Testing of Heuristic k-nn Algorithm with Fuzzy Distance Metric. Data & Knowledge Engineering, Volume:103, pp:44-59
  14. Kahraman, H.T., Bayindir, R., and Sagiroglu, S., (2012). Applying A Genetic Algorithm-Based K-Nearest Neighbor Estimator For Estimating The Excitation Current and Parameter Weighting of Synchronous Motors. Energy Conversion and Manage