Journals / Turkish Journal of Electrical Engineering and Computer Sciences / 2018 / Cilt: 26 - Sayı: 4
Novel modified impedance-based methods for fault location in the presence of a fault current limiter
- Pages
- 1881–1893
- DOI
- —
Abstract
A fault current limiter (FCL) is promising novel electric equipment to effectively reduce excessive short circuitcurrent in power networks. The presence of a FCL at the time of a fault occurrence makes it necessary to consider newsettings for protective relays and fault locators. This paper examines the presence of a FCL in power networks and itseffects on single-ended impedance-based fault location methods. It will be shown that FCL deployment in a transmissionline makes the traditional fault location method inefficient. Two modified methods are presented to solve the problem.The modified methods locate the fault point using remote bus impedance in the presence of the FCL. The accuracy ofthe proposed methods is validated using the IEEE 14-bus system. The simulation results indicate that the proposedmethods have considerable superiority over the conventional technique and perform well for different faults and FCLtypes.