Journals / Erciyes Üniversitesi Fen Bilimleri Enstitüsü Fen Bilimleri Dergisi / 2010 / Cilt: 26 - Sayı: 2

Integration of geothermal heat pumps with existing hydronic heating systems

JEOTERMAL KAYNAKLI ISI POMPASININ MEVCUT HİDRONİK ISITMA SİSTEMLERİNE ENTEGRASYONU

Pages
112–124
DOI
—

Abstract

In this work, in the context of usability of warm (30oC) water drawn from the wells drilled for CO2 production near Aksaray University campus, integration of geothermal heat pump with the existing hydronic heating system is considered. A water-water type heat pump system with 2,5 kW compressor power was installed for this purpose. The heat pump system produces hot water at 70oC for heating system using the geothermal resource at 30oC. The gas R134a was used as cooler fluid, and COP of the heat pump was measured between 2.15 and 2.75 depending on the source temperature. Economical viability of the system is shown by comparing with alternative systems.

Özet

Bu çalışmada Aksaray Üniversitesi yerleşkesi yakınlarında CO2 üretimi için açılan kuyulardan çıkarılan sıcak (30oC) suyun ısıtma amaçlı kullanılabilirliği bağlamında, jeotermal kaynaklı ısı pompasının binalardaki mevcut radyatörlü ısıtma sistemine nasıl entegre edileceği üzerinde durulmuştur. Bu amaçla kompresör gücü 2,5 kW olan sudan-suya ısı pompası düzeneği kurulmuştur. Sistemde 30oC sıcaklıkta jeotermal kaynak kullanılarak radyatörlü ısıtma sistemi için 70oC sıcaklıkta su üretilmiştir. Soğutucu akışkan olarak R134a gazı kullanılmış, kaynak sıcaklığına bağlı olarak ısı pompasının etkinliği 2.15 ile 2.75 arasında değişmiştir. Sistemin diğer yakıtlarla karşılaştırılması yapılarak ekonomikliği gösterilmiştir.

Keywords: Jeotermal, Isı Pompası, Mahallsıtma