Journals / Sakarya University Journal of Science / 2020 / Cilt: 24 Sayı: 4

Reduction through Brick Wall Barrier and Acoustic Sponge of Environmental Noise Levels from Chiller Cooling System

Pages
637–651
Publication Date
2020-08-01
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

It is shown that, due to the noise produced by the chiller fans and compressors, so as to achieve significantly cognizable levels of noise reduction it is necessary to isolation brick walls with acoustic sponge.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:The aim of this study was to investigate the noise level reduction of the air cooled liquid chiller to the desired levels of environmental noise requisite.
📊
Key Findings & Data:When the chiller was covered with a brick wall, the noise level was reduced by 5.5 Leq dBA 1 m away from the nearest residence.
💡
Conclusion & Impact:It is shown that, due to the noise produced by the chiller fans and compressors, so as to achieve significantly cognizable levels of noise reduction it is necessary to isolation brick walls with acoustic sponge.
🔬Design:Research Article
📍Scope:Comprehensive Sample
⚙️Variables:Noise control · reduction · chiller

Abstract

The aim of this study was to investigate the noise level reduction of the air cooled liquid chiller to the desired levels of environmental noise requisite. Noise control procedures are implemented with various systems to prevent environmental noise disturbances. This paper examines the application of a passive noise control approach to the control of air-cooled liquid chiller noise located in the garden of an official institution. The approach of passive noise control utilizing brick walls with acoustic sponge in the immediate vicinity of the chiller is discussed. When the chiller was covered with a brick wall, the noise level was reduced by 5.5 Leq dBA 1 m away from the nearest residence. However, this reduction could not meet the requirements of legal regulations. Therefore, the inside of brick wall was covered with acoustic sponge. As a result, the ambient noise level where 1m away from the nearest residence to the chiller has been reduced to the background noise levels with a total reduction of about 8.5 Leq dBA. It is shown that, due to the noise produced by the chiller fans and compressors, so as to achieve significantly cognizable levels of noise reduction it is necessary to isolation brick walls with acoustic sponge.

🔖

Cite This Article

TUFANER, F. (2020). Reduction through Brick Wall Barrier and Acoustic Sponge of Environmental Noise Levels from Chiller Cooling System. Sakarya University Journal of Science, Cilt: 24 Sayı: 4, 637–651. https://ajindex.com/articles/941903

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (14)

  1. J. Cheer, S. J. Elliott, "Active noise control of a diesel generator in a luxury yacht", Applied Acoustics, vol. 105, pp. 209-214, 2016
  2. J. Landaluze, I. Portilla, J. Pagalday, A. Martı́nez, R. Reyero, "Application of active noise control to an elevator cabin", Control Engineering Practice, vol. 11, no. 12, pp. 1423-1431, 2003
  3. E. Avşar, H. Erol, İ. Toröz, E. Piro, "Evaluation of environmental noise and vibration levels of dry type transformers and determination of solution alternatives: Istanbul case study", Bitlis Eren University Journal of Science vol. 8, no. 3, pp. 958-967, 2019
  4. G. S. Papini, R. L. Pinto, E. B. Medeiros, F. B. Coelho, "Hybrid approach to noise control of industrial exhaust systems", Applied Acoustics, vol. 125, pp. 102-112, 2017
  5. Y. J. Wong, R. Paurobally, J. Pan, "Hybrid active and passive control of fan noise", Applied Acoustics, vol. 64, no. 9, pp. 885-901, 2003
  6. N. Tandon, B. Nakra, D. Ubhe, N. Killa, "Noise control of engine driven portable generator set", Applied acoustics, vol. 55, no. 4, pp. 307-328, 1998
  7. H. Wang, P. Luo, M. Cai, "Calculation of noise barrier insertion loss based on varied vehicle frequencies", Applied Sciences, vol. 8, no. 1, pp. 100, 2018
  8. J. Moreland, R. Minto, "An example of in-plant noise reduction with an acoustical barrier", Applied Acoustics, vol. 9, no. 3, pp. 205-214, 1976
  9. S. B. Knight, J. B. Evans, C. N. Himmel, "Case study: Air cooled chillers with rotary helical (screw) compressors at hospital with impact on patient rooms, residential neighborhoods, and open park", The 2001 International Congress and Exhibition on Noise Control Engineering, pp. 1-5, 2001
  10. J. A. Paulauskis, "Addressing noise problems in screw chillers", ASHRAE Journal, vol. 41, pp. 22-27, 1999
  11. J. B. Evans, C. N. Himmel, J. D. Leasure, "Environmental noise case studies: Air-cooled refrigeration chiller installations near residential structures", ASHRAE Transactions, vol. 118, no. 2, pp. 50-58, 2012
  12. T. Van Renterghem, J. Forssén, K. Attenborough, P. Jean, J. Defrance, M. Hornikx, et al., "Using natural means to reduce surface transport noise during propagation outdoors", Applied Acoustics, vol. 92, pp. 86-101, 2015
  13. T. G. Hawkins, "Studies and research regarding sound reduction materials with the purpose of reducing sound pollution", [Master Thesis]. San Luis Obispo: California Polytechnic State University; 2014
  14. A. Shalool, N. Zainal, K. B. Gan, C. Umat, "An investigat