Journals / Istanbul University Journal of Electrical and Electronics Engineering / 2013 / Cilt: 13 - Sayı: 1

Analytical synchronization of two-end measurements for transmission line parameters estimation and fault location

Pages
1569–1574
Publication Date
2022-10-18
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

The presented algorithm has been tested with ATP-EMTP software by generating great number of simulations with various sets of line parameters proving its usefulness for overhead lines up to 200km length.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:This paper presents a new setting-free approach to synchronization of two-end current and voltage unsynchronized measurements.
📊
Key Findings & Data:Authors propose new non-iterative algorithm processing three-phase currents and voltages measured under normal steady state load condition of overhead line.
💡
Conclusion & Impact:The presented algorithm has been tested with ATP-EMTP software by generating great number of simulations with various sets of line parameters proving its usefulness for overhead lines up to 200km length.
🔬Design:Research Article
📍Scope:Comprehensive Sample
⚙️Variables:Domain Parameters

Abstract

This paper presents a new setting-free approach to synchronization of two-end current and voltage unsynchronized measurements. Authors propose new non-iterative algorithm processing three-phase currents and voltages measured under normal steady state load condition of overhead line. Using such synchronization the line parameters can be estimated and then precise fault location can be performed. The presented algorithm has been tested with ATP-EMTP software by generating great number of simulations with various sets of line parameters proving its usefulness for overhead lines up to 200km length.

🔖

Cite This Article

NAYIR, A., IZYKOWSKI, J., DAWIDOWSKI, P. (2022). Analytical synchronization of two-end measurements for transmission line parameters estimation and fault location. Istanbul University Journal of Electrical and Electronics Engineering, Cilt: 13 - Sayı: 1, 1569–1574. https://ajindex.com/articles/543669

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (13)

  1. M.M. Saha, J. Izykowski, E. Rosolowski, “Fault location on power networks”, Springer-Verlag London, Series: Power Systems, 2010
  2. M. Kezunovic, J. Mrkic, B. Perunicic, "An accurate fault location algorithm using synchronized sampling", Electric Power Systems Research Journal, Vol. 29, No. 3, pp. 161– 169, 1994
  3. A.L. Dalcastagne, S.N. Filho, H.H. Zurn, R. Seara, "A Two-terminal fault location approach based on unsynchronized phasors", International Conference on Power System Technology, Chongging, 2006
  4. J. Izykowski, R. Molag, E. Rosolowski, M.M. Saha, "Accurate location of faults on power transmission lines with use of two-end unsynchronized measurements", IEEE Trans. on Power Delivery, Vol. 21, No. 2, pp. 627–633, 2006
  5. E.G. Silveira, C. Pereira, "Transmission line fault location using two-terminal data without time synchronization", IEEE Trans. on Power Delivery, Vol. 22, No. 1, pp. 498– 499, 2007
  6. F. Chunju, D. Xiujua, L. Shengfang, Y. Weiyong, "An adaptive fault location technique based on PMU for transmission line", Power Engineering Society General Meeting, Tampa, USA, 2007
  7. Z.M. Radojevic, B. Kovacevic, G. Preston, V. Terzija, "New approach for fault location on transmission lines not requiring line parameters", International Conference on Power Systems Transients, Kyoto, Japan, 2009
  8. Y. Liao, S. Elangovan, "Unsynchronized two-terminal transmission-line fault-location without using line parameters", IEE Proc.-Gener. Transm. Distrib., Vol. 153, No. 6, pp. 639–643, 2006
  9. Y. Liao, "Algorithms for power system fault location and line parameter estimation", 39th Southeastern Symposium on System Theory, Macon, GA, USA, pp. 207–211, 2007
  10. Y. Liao, "Algorithms for fault location and line parameter estimation utilizing voltage and current data during the fault", 40th Southeastern Symposium on System Theory, New Orleans, LA, USA, pp. 183–187, 2008
  11. Y. Liao, N. Kang, "Fault-location algorithms without utilizing line parameters based on the distributed parameter line model", IEEE Trans. on Power Delivery, Vol. 24, No. 2, pp. 579–584, 2009
  12. E. Price, "Practical considerations for implementing wide area monitoring, protection and control", 59th Annual Conference: Protective Relay Engineers, Texas, 2006
  13. R.E. Wilson, G.A. Zevenbergen, D.L. Mah, A.J. Murphy, "Calculation of transmission line parameters from synchronized measurements", Electric Power Components and Systems, Vol. 33, No. 10, pp. 1269–1278, 2005.