Journals / Istanbul University Journal of Electrical and Electronics Engineering / 2015 / Cilt: 15 - Sayı: 2

ELIMINATING NEGETIVE EFFECT OF INVERTER-BASED DGs ON FUSE-RECLOSER COORDINATION IN DISTRIBUTION SYSTEMS

Pages
1921–1927
Publication Date
2022-10-18
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

Results ofthe simulation on IEEE 13-bus system showed that the proposed control method was able to remove the negative efl'ectofDG onflue-recloser coordination.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:Despite many advantages of distributed generation (DG) sources, they may have negative eflect on theprotection of distribution systems.
📊
Key Findings & Data:In distribution system, fuse-recloser protection scheme is designed such that therecloser could operate faster than the fuse to prevent Me buming; but, the presence ofDGs in fault conditions maylead to increasedfuse current and thus faster performance of the fuse than the recloser and lack ofcoordination.
💡
Conclusion & Impact:Results ofthe simulation on IEEE 13-bus system showed that the proposed control method was able to remove the negative efl'ectofDG onflue-recloser coordination.
🔬Design:Research Article
📍Scope:Comprehensive Sample
⚙️Variables:Domain Parameters

Abstract

Despite many advantages of distributed generation (DG) sources, they may have negative eflect on theprotection of distribution systems. In distribution system, fuse-recloser protection scheme is designed such that therecloser could operate faster than the fuse to prevent Me buming; but, the presence ofDGs in fault conditions maylead to increasedfuse current and thus faster performance of the fuse than the recloser and lack ofcoordination. In thispaper, effect of DGS on fuse-recloser coordination was studied using analytical relations and simulation. usefulcontrol method was presented for reducing the eflect of DG on fuse-recloser coordination. Accordingly, direction ofDG current was changed by controlling DG reactive power at the fault time, which reduced the fuse current. Results ofthe simulation on IEEE 13-bus system showed that the proposed control method was able to remove the negative efl'ectofDG onflue-recloser coordination.

🔖

Cite This Article

SALEHI, M., NAMDARI, F., .SHAKARAMI, M. (2022). ELIMINATING NEGETIVE EFFECT OF INVERTER-BASED DGs ON FUSE-RECLOSER COORDINATION IN DISTRIBUTION SYSTEMS. Istanbul University Journal of Electrical and Electronics Engineering, Cilt: 15 - Sayı: 2, 1921–1927. https://ajindex.com/articles/543643

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (10)

  1. J.M. Guerrero, F. Blaabjerg, T. Zhelev, K. Hemmes, E. Manmasson, S.Iemei, M. P. Comech, R. Granadino, and J. I. Frau, “Distributed generationzToward new energy paradigm,” IEEE Ind. Electron. Mag.,vol. 4, no. 1, pp. 52—64, Mar. 2010
  2. J. He, Y.W. Li, and S.Munir, “A flexible harmonic control approach through voltage controlled DG-grid interfacing converters,” IEEETrans. Ind. Electron, vol. 59, no. 1, pp. 444—455, Jan. 2012
  3. A. Piccolo and P. Siano, “Evaluating the impact of network investment deferral on distributed generation expansion,” IEEE Trans. Power Sist., vol. 24, no. 3, pp. 1559—1567, Aug. 2009
  4. X. Wang, W. Freitas, and W. Xu, “Dynamic nondetection zones of positive feedback anti-islanding methods for inverter-based distributed generators,” IEEE Trans. Power Del, vol. 26, no. 2, pp. 1145—1155, Apr. 2011
  5. R. A. Walling, R. Saint, R. C. Dugan, J. Burke, and L. A. Kojovic, “Summary of distributed resources impact on power delivery system,” IEEE Trans. Power Del, vol. 23, no. 3, pp. 1636—1644, Jul. 2008
  6. M. H. Kim, S. H. Lim, J. F. Moon, and J. C. Ki, “Method of recloserfuse coordination in power distribution system with superconducting fault current limite,” IEEE Trans. Appl. Supercond, vol. 20, no. 3, pp. 1164—1167, Jun. 2010
  7. H. Cheung, A. Hamlyn, L. Wang, C. Yang, and R. Cheung, Investigations of impacts of distributed generation on feeder protection,” in Proc. IEEE Power Energy Soc. Gen. Meet., 2009, pp. 1—7
  8. T. Seegers et al., “Impact of distributed resources on distribution relay protection,” Rep. to Line Protection Subcommitee, Power System Relay Committee, Power Engineering Society, IEEE, 2004
  9. J. Chen, Fan, X. Duan, and J. Cao, “Penetration level optimization for DG considering reliable action of relay protection device constrains,”in Proc. Int. Conf. Sustainable Power Gener. Supply, 2009, pp. 1—5 [10] S. Chaitusaney and A. Yokoyama, “Prevention of reliability degradation Rom recloser-fuse miscoordination due to distributed generatio,”IEEE Trans. Power Del, vol. 23, no. 4, pp. 2545—2554, Oct.2008. 1927 MR. SHAKARAMI et al. /IU-JEEE Vol. 15(2), (2015), 1921-1927 [11] T. K. Abdel-Galil, A. E. B. Abu—Elnien, E. F. Elsaadany, A. Girgis, Y. A.-R. I. Mohamed, M. M. A. Salma, and H. H.M. Zeineldin, “Protection coordination planning with distributed generation,” Canmet Energy Technology Centre, Varennes, QC, Canada, 2007
  10. H. B. Funrnilayo and K. L. Buyler-Purry, “An approach to mitigate the impact of distribute