It was seen for the investigated cycles that the highest exergetic efficiency could be obtained in the case of R445A.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:In this study, the energy parameters (i.e., cooling capacity and COP) were theoretically investigated for three different vapour compression refrigeration system (basic cycle, basic cycle with liquid-to-suction heat exchanger and two-stage cascade cycle) for which R1234yf, R1234ze(E), R513A, R445A and R450A alternative refrigerants with low GWP value were used instead of R134a.
📊
Key Findings & Data:The studied refrigerants demonstrated similar thermodynamic behaviour.
💡
Conclusion & Impact:It was seen for the investigated cycles that the highest exergetic efficiency could be obtained in the case of R445A.
🔬Design:Research Article
📍Scope:Comprehensive Sample
⚙️Variables:Domain Parameters

Abstract

In this study, the energy parameters (i.e., cooling capacity and COP) were theoretically investigated for three different vapour compression refrigeration system (basic cycle, basic cycle with liquid-to-suction heat exchanger and two-stage cascade cycle) for which R1234yf, R1234ze(E), R513A, R445A and R450A alternative refrigerants with low GWP value were used instead of R134a. The studied refrigerants demonstrated similar thermodynamic behaviour. The exergetic efficiency of the systems was also compared. The comparison of the energy parameters was carried out for two different evaporation temperatures (-30 and 0C) and two condensing temperatures (40 and 55C). According to the calculation results, R450A which almost has the same COP values as R134a comes into prominence with 58% lower GWP value compared to R134a. Among the studied refrigeration cycles, system with LSHEX can be suggested for providing a better effect in terms of COP for the considered refrigerants and temperature cases as well as assumed system parameters. It was seen for the investigated cycles that the highest exergetic efficiency could be obtained in the case of R445A.

🔖

Cite This Article

ORUÇ, V., DEVECİOĞLU, A. G. (2022). A COMPARATIVE ENERGETIC ANALYSIS FOR SOME LOW-GWP REFRIGERANTS AS R134a REPLACEMENTS IN VARIOUS VAPOR COMPRESSION REFRIGERATION SYSTEMS. Isı Bilimi ve Tekniği Dergisi, Cilt: 38 - Sayı: 2, 51–61. https://ajindex.com/articles/542474

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (5)

  1. Bolaji, O., Huan, Z., 2014, Performance Investigation of Some Hydro-Fluorocarbon Refrigerants with Low Global Warming as Substitutes to R134a in Refrigeration Systems. J. Eng. Thermophys, 23(2), 148–157. Chemours, 2016. HFC-134a Properties, Uses, Storage, and Handling, https://www.chemours.com/Refrigerants/en_US/assets/d ownloads/freon-134a-properties-uses-storage- handling.pdf Chemours, 2018. Opteon™ XP10, https://www.chemours.com/Refrigerants/en_US/product s/Opteon/Stationary_Refrigeration/assets/downloads/Op teon_XP10_prodinfo.pdf Devecioğlu, A.G., Oruç, V., 2017, An analysis on the comparison of low-GWP refrigerants to alternatively use in mobile air-conditioning systems, Therm. Sci. Eng. Prog, 1, 1–5.
  2. Dinçer İ., Kanoğlu M., 2010, Refrigeration Systems and Applications, John Wiley and Sons Ltd. European Parliament and of the Council Official, 2006, Directive 2006/40/EC, Journal of the European Union, https://eur-lex.europa.eu/legal-content/EN/TXT/PDF/?uri=CELEX:32006L0040&rid= 1 European Parliament and the Council, 2014, Regulation (EU) No 517/2014, Official Journal of the European Union, http://eur-lex.europa.eu/legal-content/EN/TXT/PDF/?uri=CELEX:32014R0517&from =EN Fukuda, S., Kondou, C., Takata, N., Koyama, S., 2014, Low GWP refrigerants R1234ze(E) and R1234ze(Z) for high temperature heat pumps. Int. J. Refrigeration, 40, 161-173. Honeywell, 2014, Solstice® ze Refrigerant (HFO-1234ze),. Accessed date: 21 December 2015. Honeywell, 2015a, Solstice® N13 (R-450A), http://www.honeywell-refrigerants.com/europe/wp-content/uploads/2015/03/Solstice-N13-TDS-141027-LR-vF.pdf Honeywell, 2015b, Solstice® yf Properties and Materials Compatibility, http://www.honeywell-refrigerants.com/europe/wp- content/uploads/2015/06/Solstice-yf-Properties-and- Materials-Capatibility-060115.pdf Kondou, C., Koyama, S., 2015, Thermodynamic assessment of high-temperature heat pumps using Low-GWP HFO refrigerants for heat recovery, Int. J. Refrigeration, 53, 126-141.
  3. Lee, H., Hwang, Y., Song, I., Jang, K., 2015, Transient thermal model of passenger car's cabin and implementation to saturation cycle with alternative working fluids, Energy, 90, 1859-1868.
  4. Lee, Y., Jung, D., 2012, A brief performance comparison of R1234yf and R134a in a bench tester for automobile applications. Appl. Therm. Eng., 35, 240-242.
  5. Lemmon, E.W., Huber, M.L., McLinden, M.O., 2013, NIST Standard Reference Database 23 Reference Fluid Thermodynamic and Transport Properties-REFPROP, Version 9.1, National Insti