Journals / Gazi University Journal of Science / 2019 / Cilt: 32 - Sayı: 2

Non-Linear Eddy Current Loss and Thermal Analysis on Transformer Cover

Pages
558–570
Publication Date
2022-10-19
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

The reliability of the technique, confirmed by experimental and FEM results.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:High current conductors of transformers cause to produce losses and thermal problems in theirtank cover.
📊
Key Findings & Data:Finite Difference (FD) Method (FDM) magnetic analysis is used to find out an exactestimation of the magnetic field and the losses near the bushings in the transient solution,considering the non-linear magnetic permeability of the cover plate, because FDM is moreflexible to deal with the nonlinear constitutive law and easy-to-be implemented especially in thecase of simple geometry.
💡
Conclusion & Impact:The reliability of the technique, confirmed by experimental and FEM results.
🔬Design:Research Article
📍Scope:Comprehensive Sample
⚙️Variables:Domain Parameters

Abstract

High current conductors of transformers cause to produce losses and thermal problems in theirtank cover. Finite Difference (FD) Method (FDM) magnetic analysis is used to find out an exactestimation of the magnetic field and the losses near the bushings in the transient solution,considering the non-linear magnetic permeability of the cover plate, because FDM is moreflexible to deal with the nonlinear constitutive law and easy-to-be implemented especially in thecase of simple geometry. Finite Element Method (FEM) thermal analysis is used to determinethe plate temperature based on magnetic FD analysis, taking account non-linear heat fluxboundary condition. A calibration procedure is used between the analyses to ensure the precisionof assumptions. The reliability of the technique, confirmed by experimental and FEM results.

🔖

Cite This Article

ISKENDER, I., ZAHEDI, M. Z. (2022). Non-Linear Eddy Current Loss and Thermal Analysis on Transformer Cover. Gazi University Journal of Science, Cilt: 32 - Sayı: 2, 558–570. https://ajindex.com/articles/521330

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (14)

  1. Kulkarni, S. V., Olivares, J. C., Perez, R. E., Lakhiani, V. K., and Turowski, J., “Evaluation of eddy current losses in the cover plates of distribution transformers”, IEE Proceedings - Science, Measurement and Technology, 151(5): 313-318, (2004).
  2. Maximov, S., Perez, R. E., Adame, S. M., Olivares, J. C., and Littlewood, E. C., “Calculation of nonlinear electromagnetic fields in the steel wall vicinity of transformer bushings”, IEEE Transactions on Magnetics, 51(6): (2015).
  3. Olivares, J. C., Georgilakis, P. S., and Ocon-Valdez, R., “A review of transformer losses”, Electric Power Components and Systems, 37(9): 1046-1062, (2009).
  4. Kulkarni, S. V. and Khaparde, S., Transformer engineering: design, technology and diagnostics, CRC Press, (2016).
  5. Turowski, J. and Pelikant, A., “Eddy currents losses and hot-spot evaluation in cover plates of power transformers”, IEE Proceedings-Electric Power Applications, 144(6): 435-440, (1997).
  6. Turowski, J., Elektrodynamika techniczna 2 nd ed., WNT, Warszawa, Poland, (1993)
  7. Olivares, J. C., Perez, R. E., Kulkarni, S. V., Leon, F. D., and Vega, M. A. V., “2D finite-element determination of tank wall losses in pad-mounted transformers”, Electric Power Systems Research, 71: 179-185, (2004).
  8. Zahedi, M. Z. and Iskender, I., “3D FEM optimal design of transformer cover plates to decrease stray losses and hot spot temperature”, International Journal on Technical and Physical Problems of Engineering (IJTPE), 8(3): 56-60, (2016).
  9. Olivares, J. C., Perez, R. E., Kulkarni, S. V., Leon, F. D., Vasquez, E. M., and Anaya, O. H., “Improved insert geometry for reducing tank-wall losses in pad-mounted transformers”, IEEE Transactions on Power Delivery, 19(3): 1120-1126, (2004).
  10. Maximov, S., Olivares-Galvan, J. C., Magdaleno-Adame, S., Escarela-Perez, R., and CamperoLittlewood, E., “New analytical formulas for electromagnetic field and eddy current losses in bushing regions of transformers”, IEEE Transactions on Magnetics, 51: (2015).
  11. Del Vecchio, R. M., Del Vecchio, R., Poulin, B., Feghali, P. T., Shah, D. M., and Ahuja, R., Transformer design principles with applications: with applications to core-form power transformers 3 rd ed, CRC press, (2017).
  12. Zahedi, M. Z. and Iskender, I., “FDM electromagnetic analysis in bushing regions of transformer”, International Journal on Technical and Physical Problems of Engineering (IJTPE), 10(34): 27-33,
  13. Mar. (2018).