Study offlue gas emission and improvement measure in a natural draft dry-cooling tower withflue gas injection under unfavorable working conditions

Pages
963–972
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

The results showed that the air massflow rate and heat rejection of the cooling tower decreasedsignificantly, and the airflow in the cooling tower became disorganized when the louvers were closed underunfavorable working condition.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:In this paper, we observed thatflue gas from a natural draft dry-cooling tower (NDDCT) withflue gas injectioncould not be discharged smoothly under unfavorable working conditions (e.g., when the louvers are closed inwinter), which may have caused severe corrosion on the inner shell of the cooling tower.
📊
Key Findings & Data:The results showed that the air massflow rate and heat rejection of the cooling tower decreasedsignificantly, and the airflow in the cooling tower became disorganized when the louvers were closed underunfavorable working condition.
💡
Conclusion & Impact:After increasingthe height offlue gas outlet, the pollutant concentration on the inner shell of the cooling tower decreasedobviously.
🔬Design:Modeling & Simulation
📍Scope:Comprehensive Sample
⚙️Variables:Domain Parameters

Özet

In this paper, we observed thatflue gas from a natural draft dry-cooling tower (NDDCT) withflue gas injectioncould not be discharged smoothly under unfavorable working conditions (e.g., when the louvers are closed inwinter), which may have caused severe corrosion on the inner shell of the cooling tower. In light of this issue, weproposed an improvement measure. On the basis of the computationalfluid dynamics (CFD) method, we es-tablished a numerical model for NDDCT withflue gas injection to predict theflowfield and pollutant diffusion.We simulatedflue gas emissions for a NDDCT withflue gas injection under normal and unfavorable workingconditions. The results showed that the air massflow rate and heat rejection of the cooling tower decreasedsignificantly, and the airflow in the cooling tower became disorganized when the louvers were closed underunfavorable working condition. Compared with normal working conditions, the pollutant concentration on theinner shell of the cooling tower increased by 1.5 times under unfavorable working conditions. After increasingthe height offlue gas outlet, the pollutant concentration on the inner shell of the cooling tower decreasedobviously.

🔖

Cite This Article

YANG, G., DİNG, L., TİAN, W., XU, Z., WANG, Z., SUN, F., MİN, J., XU, J., WANG, S. Y., GUO, T., Lİ, X., GUO, Z. (2020). Study offlue gas emission and improvement measure in a natural draft dry-cooling tower withflue gas injection under unfavorable working conditions. Atmospheric Pollution Research, Cilt: 11 - Sayı: 5, 963–972. https://ajindex.com/articles/351546

References (13)

  1. Al-Waked, R., Behnia, M., 2004. The performance of natural draft dry cooling towersunder crosswind: CFD study. Int. J. Energy Res. 28 (2), 147–161.
  2. Al-Waked, R., Behnia, M., 2006. CFD simulation of wet cooling towers. Appl. Therm. Eng.26 (4), 382–395.
  3. Al-Waked, R., Behnia, M., 2007. Enhancing performance of wet cooling towers. EnergyConvers. Manag. 48 (10), 2638–2648.
  4. Al-Waked, R., 2010. Crosswinds effect on the performance of natural draft wet coolingtowers. Int. J. Therm. Sci. 49 (1), 218–224.
  5. Busch, D., Harteb, R., Kr€atzig, W., Montag, U., 2002. New natural draft cooling tower of200 m of height. Eng. Struct. 24 (12), 1509–1521.
  6. Chen, L., Yang, L., Du, X., Yang, Y., 2017. Flue gas diffusion for integrated dry-coolingtower and stack system in power plants. Int. J. Therm. Sci. 114, 257–270.
  7. Cui, K., Chai, F., 2005. The environmental effect of natural draft cooling towers withfluegas injection in a burning coal plant partII: the evaluation of environment effect forthe case at huaneng beijing thermoelectric plant. Research of Environmental Sciences18 (1), 31–34 (in Chinese). Córdoba, P., 2015. Status offlue gas desulphurisation (FGD) systems from coal-firedpower plants: overview of the physic-chemical control processes of wet limestoneFGDs. Fuel 144, 274–286.
  8. Eldredge, T., Benton, D., Hodgson, J., 1997. An investigation of the effects offlue gasinjection on natural draft dry-cooling tower performance. J. Eng. Gas Turbines Power119 (2), 478–483.
  9. Galos, K., Smakowski, T., Szlugaj, J., 2003. Flue-gas desulphurisation products fromPolish coal-fired power-plants. Appl. Energy 75 (3), 257–265.
  10. Goodarzi, M., 2013. Proposing a new technique to enhance thermal performance andreduce structural design wind loads for natural drought cooling tower. Energy 62 (6),164–172.
  11. Goodarzi, M., Ramezanpour, R., 2014. Alternative geometry for cylindrical natural draftcooling tower with higher cooling efficiency under crosswind condition. EnergyConvers. Manag. 77 (1), 243–249.
  12. Inagaki, Y., Koiso, H., Takumi, H., Ioka, I., Miyamoto, Y., 1998. Thermal hydraulic studyon a high-temperature gas–gas heat exchanger with helically coiled tube bundles.Nucl. Eng. Des. 185 (2–3), 141–151. Jahangiri,A., Golneshan, A., 2001. Feasibility study of the thermal performance im-provement of natural draft dry cooling towers due toflue gas injection. World Appl.Sci. J. 12 (4), 568–575.
  13. Kröger, D., 2004. Air-cooled Heat Exchangers and Cooling Towers. Penn WellCorporation, Oklahoma, USA.Klimanek, A., Ced