Journals / Uludağ Üniversitesi Mühendislik Fakültesi Dergisi / 2018 / Cilt: 23 - Sayı: 3

Simulation of Vertical Type Ground Source Heat Pump

DİKEY TİP TOPRAK KAYNAKLI BİR ISI POMPASININ SİMÜLASYONU

Pages
155–168
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

Of the energy consumption were obtained as 54.36% by the heat pump, 26.78 % by electrical heaters, 13.64% by pumps and 5.22% by fan.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:In this study, vertical type ground source heat pump (GSHP) was used to heat a restaurant located in Istanbul province and to meet the usage hot water requirement.
📊
Key Findings & Data:The designed system is simulated with the help of the TRNSYS (time dependent system simulation) program then its performance and energy consumption are examined.
💡
Conclusion & Impact:Of the energy consumption were obtained as 54.36% by the heat pump, 26.78 % by electrical heaters, 13.64% by pumps and 5.22% by fan.
🔬Design:Research Article
📍Scope:Comprehensive Sample
⚙️Variables:TRNSYS · ısı pompası · simülasyon

Abstract

In this study, vertical type ground source heat pump (GSHP) was used to heat a restaurant located in Istanbul province and to meet the usage hot water requirement. The designed system is simulated with the help of the TRNSYS (time dependent system simulation) program then its performance and energy consumption are examined. While room temperature was kept constant at 22 ºC in winter with the help of the GSHP system, 300 l/h of water at 55ºC was drawn to use for 15 minutes during the whole year (at 06:00 a.m., 08:00 a.m., 20:00 p.m. and 22:00 p.m.). The rated heating capacity of the heat pump used is 78228 kJ/ h and the rated power consumption is 18193 kJ/h. As a result of the analysis, the total annual power consumption of the GSHP system is 3922.88 kW, the annual average performance coefficients of the heat pump and the whole system are calculated as 3.33 and 1.81 respectively. Of the energy consumption were obtained as 54.36% by the heat pump, 26.78 % by electrical heaters, 13.64% by pumps and 5.22% by fan.

Özet

Bu çalışmada İstanbul ilinde yer alan bir restoranın ısıtılması ve kullanım sıcak su ihtiyacının karşılanmasında dikey tip bir toprak kaynaklı ısı pompası (TKIP) kullanılmıştır. Tasarlanan sistem TRNSYS (Zamana bağlı sistem simülasyonu) programı yardımıyla simüle edilmiş ve sistemin performansı enerji tüketimi açısından incelenmiştir. Ele alınan mahallin sıcaklığı, TKIP sistemi yardımıyla kış aylarında 22 ºC’de sabit tutulurken, tüm yıl boyunca günde dört kere (6:00, 8:00, 20:00 ve 22:00) saatlerinde 15 dakika süreyle 55 ºC sıcaklıkta 300 l/h su kullanımı gerçekleşmektedir. Kullanılan TKIP ünitesi nominal ısıtma kapasitesi 78228 kJ/h, nominal güç tüketimi 18193 kJ/h’dır. Analiz sonucunda TKIP sisteminin yıllık toplam güç tüketimi 3922,88 kW, ısı pompası ve tüm sistemin yıllık ortalama performans katsayıları sırasıyla 3,33 ve 1,81 olarak hesaplamıştır. Tüketilen enerjinin %54,36’ü ısı pompası, %26,78 ısıtıcılar, %13,64’ü pompalar, %5,22’i ise fan tarafından tüketilmektedir.

🔖

Cite This Article

COŞKUN, S., GÜLER, F., FAZLİÇ, M. A., ERGÜN, E. H. (2018). Simulation of Vertical Type Ground Source Heat Pump. Uludağ Üniversitesi Mühendislik Fakültesi Dergisi, Cilt: 23 - Sayı: 3, 155–168. https://ajindex.com/articles/329964

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (1)

  1. Emmi, G., Zarrella, A., Carli M.D., Galgaro A. (2015) An analysis of solar assisted ground source heat pumps in cold climates, Energy Conversion and Management, 106: 660–675, doi.org/10.1016/j.enconman.2015.10.016 Gao, J., Li, A., Xu, X., Gang, W., Yan, T. (2018) Ground heat exchanger: Applications, technology integration and potentials for zero energy buildings, Renewable Energy, 128: 337-349, doi: 10.1016/j.renene.2018.05.089 Han, Z., Zheng, M., Kong, F., Wang, F., Li, Z., Bai, T. (2008) Numerical simulation of solar assisted ground-source heat pump heating system with latent heat energy storage in severely cold area, Applied Thermal Engineering, 28: 1427–1436. doi:10.1016/j.applthermaleng.2007.09.013 Januševičius, K. and Streckiene, G. (2013) Solar Assisted Ground Source Heat Pump Performance in Nearly Zero Energy Building in Baltic Countries, Environmental and climate technologies, 48-56, doi: 10.2478/rtuect-2013-0007 Ji,Y., Duanmu, L., Li,X., Airaksinen, M.,Wang, Z. (2017) Simplified method to determine the collector area of solar-assisted ground-source heat pump system, Procedia Engineering, 205: 1138–1145, doi: 10.1016/j.proeng.2017.10.420 Jonas, D, Frey, G., Thesis, D. (2017) Simulation and performance analysis of combined parallel solar thermal and ground or air source heat pump systems, Solar Energy, 150: 500-511, doi:: 10.1016/j.solener.2017.04.070 Li, Y. H. and W.C. Kao (2017) Performance analysis and economic assessment of solar thermal and heat pump combi systems for subtropical and tropical region, Solar Energy, 153: 301-316, doi: 10.1016/j.solener.2017.05.067 Li, H., Xu, W., Yu, Z., Wu, J., & Yu, Z. (2017b). Discussion of a combined solar thermal and ground source heat pump system operation strategy for office heating. Energy and Buildings, 162(2018), 42-53. doi: 10.1016/j.enbuild.2017.12.021 Miglani, S., Orehounig, K., Carmeliet, J. (2017) Design and optimization of a hybrid solar ground source heat pump with seasonal regeneration, Energy Procedia, 122: 1015–1020, doi: 10.1016/j.egypro.2017.07.468 Rad, F. M., Fung, A. S., Leong, W. H. (2013) Feasibility of combined solar thermal and ground source heat pump systems in cold climate, Canada, Energy and Buildings, 61: 224–232, doi: 10.1016/j.enbuild.2013.02.036 Thygesen, R., Karlsson, B. (2013) Economic and energy analysis of three solar assisted heat pump systems in near zero energy buildings, Energy and Buildings, 66: 77–87, doi: 10.1016/j.enbuild.2013.07.042 Wang, E., Fung, A. S.,Qia, C.,