Investigation of Coolant Temperature Effect on Thermal Comfort in Wall Mounted Radiant Cooling Systems

Duvardan Radyant Soğutma Sistemlerinde Soğutucu Akışkan Sıcaklığının Isıl Konfora Etkisinin İncelenmesi

Pages
461–468
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

It has been found that all cases fulfilled the thermal comfort conditions specified in ASHRAE 55 standard and the best conditions were obtained at 20°C water temperature.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:Radiant systems provide better thermal comfort conditions than traditional heating and cooling systems, as well as low energy consumption.
📊
Key Findings & Data:The performance of radiant panel systems in terms of energy and exergy have attracted the attention of the academicians around the world.
💡
Conclusion & Impact:It has been found that all cases fulfilled the thermal comfort conditions specified in ASHRAE 55 standard and the best conditions were obtained at 20°C water temperature.
🔬Design:Research Article
📍Scope:Comprehensive Sample
⚙️Variables:Isıl konfor · PMV-PPD · radyant soğutma

Abstract

Radiant systems provide better thermal comfort conditions than traditional heating and cooling systems, as well as low energy consumption. The performance of radiant panel systems in terms of energy and exergy have attracted the attention of the academicians around the world. In this study, the effect of the wall mounted radiant cooling system on thermal comfort was investigated numerically. For this purpose, the coolant temperature inside the radiant panels was defined as 18°C, 20°C and 22°C respectively and the results were compared according to the PMV-PPD parameters. It has been found that all cases fulfilled the thermal comfort conditions specified in ASHRAE 55 standard and the best conditions were obtained at 20°C water temperature.

Özet

Radyant sistemler geleneksel ısıtma ve soğutma sistemlerine göre daha iyi ısıl konfor şartları sağlamalarının yanında düşük enerji tüketimleriyle de ön plana çıkmaktadırlar. Radyant panel sistemlerinin enerji ve ekserji açısından gösterdikleri performanslar dünya çapında akademisyenlerin ilgisini çekmiştir. Bu çalışmada, duvardan radyant soğutma sisteminin ısıl konfora etkisi sayısal olarak incelenmiştir. Bu amaçla yapılan çalışmalarda radyant panellerin içerisinde bulunan soğutucu akışkan sıcaklığı sırasıyla 18°C, 20°C ve 22°C tanımlanarak sonuçlar PMV-PPD parametrelerine göre karşılaştırılmıştır. Tüm durumların ASHRAE 55 standardında belirtilen ısıl konfor şartlarını sağladığı, en iyi ısıl konfor değerine yakın durumun 20°C soğutucu akışkan sıcaklığında gerçekleştiği görülmüştür.

🔖

Cite This Article

ÖZTÜRK, M., ORUÇ, O. (2019). Investigation of Coolant Temperature Effect on Thermal Comfort in Wall Mounted Radiant Cooling Systems. Politeknik Dergisi, Cilt: 22 - Sayı: 2, 461–468. https://ajindex.com/articles/307368

References (16)

  1. Fanger, P. O., "Thermal comfort. Analysis and applications in environmental engineering", (1970)
  2. Oxizidis, S., Papadopoulos, M. A., “Performance of radiant cooling surfaces with respect to energy consumption and thermal comfort”, Energy and Buildings, 57: 199-209, (2013)
  3. Catalina, T., Virgone, J. ve Kuznik, F., "Evaluation of thermal comfort using combined CFD and experimentation study in a test room equipped with a cooling ceiling", Building and Environment, 44: 1740–1750, (2009)
  4. Lim, J.H., Jo, J.H., Yong, Y.K., Souk, M., Kim, K.W., “Application of the control methods for radiant floor cooling system in residential buildings”, Building and Environment, 41: 60-73, (2006)
  5. Hodder, S. G., Loveday, D. L., Parsons, K. C. ve Taki, A. H., "Thermal comfort in chilled ceiling and displacement ventilation environments: vertical radiant temperature asymmetry effects", Energy and Buildings, 27: 167–173, (1998)
  6. Imanari, T., Omori, T. ve Bogaki, K., "Thermal comfort and energy consumption of the radiant ceiling panel system: Comparison with the conventional all-air system", Energy and Buildings, 30: 167–175 (1999)
  7. Zhao, K., Liu, X. H. ve Jiang, Y., "Application of radiant floor cooling in large space buildings - A review", Renewable and Sustainable Energy Reviews, 55: 1083–1096, (2016)
  8. Fernandez Hernandez, F., Cejudo Lopez, J. M., Fernandez Gutierrez, A. ve Dominguez Munoz, F., "A new terminal unit combining a radiant floor with an underfloor air system: Experimentation and numerical model", Energy and Buildings, 133: 70–78, (2016)
  9. TS 825, “Binalarda Isı Yalıtım Kuralları”, (2008)
  10. White, F. M., “Fluid Mechanics”, McGraw-Hill, 3. Baskı, New York, (2003)
  11. Incropera, F.P. ve Dewitt, P.D.,” Fundamentals of Heat and Mass Transfer”, John Wiley and Sons, 3. Baskı, New York (2013)
  12. ANSYS, “Ansys Fluent Theory Guide, Yayın No: 15”, (2013)
  13. Bardina, J.E., Huang, P.G. ve Coakley, T.J., “Turbulence Modeling Validation, Testing, and Development”, NASA technical memorandum, California, (1997)
  14. Yuan, X., “Wall Functions for Numerical Simulation of Natural Convection along Vertical Surfaces”, Yüksek Lisans Tezi, ETH Zürich, Zürih, (1995)
  15. ANSYS, “Ansys Fluent User’s Guide, Yayın No: 16”, (2015). [16]
  16. Alarko Carrier Sanayi ve Ticaret A.Ş., “Şehirlerin Yaz ve Kış Dış Hava Tasarım Sıcaklıkları”, https://www.alarko-carrier.com.tr/tr/TeknikDestek/DisHavaTasarimS