Journals / Politeknik Dergisi / 2018 / Cilt: 21 - Sayı: 4

Optimization of Process Parameters of Ground Source Heat Pumps for Space Heating Applications with Taguchi Method

Pages
991–998
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

The most significant parameter on the COPsys for space heating applications of GSHP system were found as Ti,sa and To,sa with 48.4 %..

📌 3 Key Takeaways

🎯
Objective & Hypothesis:In this paper, optimization of the influence of the process parameters of ground source heat pump (GSHP) with the double U tube heat exchanger for space heating applications was performed.
📊
Key Findings & Data:The coefficient of performance (COPsys) in GSHP system was investigated during experimental measurements with various process parameters; space air inlet/outlet temperatures (Ti,sa and To,sa) and soil inlet/outlet temperatures (Ti,wa and To,wa).
💡
Conclusion & Impact:The most significant parameter on the COPsys for space heating applications of GSHP system were found as Ti,sa and To,sa with 48.4 %..
🔬Design:Modeling & Simulation
📍Scope:Comprehensive Sample
⚙️Variables:Taguchi method · ANOVA · ground source heat pump

Abstract

In this paper, optimization of the influence of the process parameters of ground source heat pump (GSHP) with the double U tube heat exchanger for space heating applications was performed. The coefficient of performance (COPsys) in GSHP system was investigated during experimental measurements with various process parameters; space air inlet/outlet temperatures (Ti,sa and To,sa) and soil inlet/outlet temperatures (Ti,wa and To,wa). Taguchi method performed for obtained the optimum process conditions on the COPsys in GSHP system. Taguchi experimental design considered as L16 orthogonal array. The most influence of process parameter on the COPsys in GSHP system was evaluated by using analysis of variance (ANOVA) and signal/noise (S/N) ratio. The optimum process parameter was determined as A4B1C1D1 for COPsys in GSHP with ANOVA analysis. The optimum levels were computed as Ti,sa at Level 1 (32 °C), the To,sa at Level 2 (17°C), the Ti,wa at Level 2 (6°C) and and the To,wa at Level 1 (9°C). The most significant parameter on the COPsys for space heating applications of GSHP system were found as Ti,sa and To,sa with 48.4 %..

Özet

In this paper, optimization of the influence of the process parameters of ground source heat pump (GSHP) with the double U tube heat exchanger for space heating applications was performed. The coefficient of performance (COPsys) in GSHP system was investigated during experimental measurements with various process parameters; space air inlet/outlet temperatures (Ti,sa and To,sa) and soil inlet/outlet temperatures (Ti,wa and To,wa). Taguchi method performed for obtained the optimum process conditions on the COPsys in GSHP system. Taguchi experimental design considered as L16 orthogonal array. The most influence of process parameter on the COPsys in GSHP system was evaluated by using analysis of variance (ANOVA) and signal/noise (S/N) ratio. The optimum process parameter was determined as A4B1C1D1 for COPsys in GSHP with ANOVA analysis. The optimum levels were computed as Ti,sa at Level 1 (32 °C), the To,sa at Level 2 (17°C), the Ti,wa at Level 2 (6°C) and and the To,wa at Level 1 (9°C). The most significant parameter on the COPsys for space heating applications of GSHP system were found as Ti,sa and To,sa with 48.4 %..

🔖

Cite This Article

ÖZDEMİR, M. B. (2018). Optimization of Process Parameters of Ground Source Heat Pumps for Space Heating Applications with Taguchi Method. Politeknik Dergisi, Cilt: 21 - Sayı: 4, 991–998. https://ajindex.com/articles/306491

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (13)

  1. Ochsner K., Geothermal heat pumps: a guide for planning and installing., 1st ed. London, Earthscan Publications Ltd., (2007)
  2. Sarbu I., Sebarchievici C., Ground Source Heat Pumps, Fundementals, Experiments and applications, 1st Edition, eBook ISBN: 9780128042410, Academic Press, October (2015)
  3. Omer AM. Ground-source heat pumps systems and applications, Renewable Sustainable Energy Review, 12: 344-371, (2008)
  4. Sivasakthivel T, Murugesan K, Sahoo PK., Potential reduction in CO2 emission and saving in electricity by ground source heat pump system for space heating applications-A study on northern part of India, Procedia Engineering, 38: 970-979, (2012)
  5. Kim E, Lee J, Jeong Y, Hwang Y, Lee S, Park N., Performance evaluation under the actual operating condition of a vertical ground source heat pump system in a school building, Energy Build, 50: 1-6, (2012)
  6. Esen H., Turgut E., Optimization of operating parameters of a ground coupled heat pump system by Taguchi method, Energy and Building, 107: 329–334, (2015)
  7. Ramniwas K., Murugesan K., Sahoo P.K., Optimization of operating parameters of ground source heat pump using Taguchi method, in: 23rd IIRConference, Prague, Czech Republic, August 21–26, (2011)
  8. Pandey N., Murugesan K., Thomas H.R., Optimization of ground heat exchangers for space heating and cooling applications using Taguchi method and utility concept, Applied Energy 190: 421–438, (2017)
  9. Sivasakthivel T, Murugesan K, Thomas HR., Optimization of operating parameters of ground source heat pump system for space heating and cooling by Taguchi method and utility concept, Applied Energy, 116: 76-85, (2014)
  10. V. Verma, K. Murugesan, Optimization of solar assisted ground source heat pump system for space heating application by Taguchi method and utilityconcept, Energy and Building, 82: 296–309, (2014)
  11. Özdemir M. Br, Özkaya Musa Galip, Energy and Exergy Analyses of the Vertical Type Ground-Sourced Heat Pump for Ankara Conditions, Gazi University Journal of Polytechnic, 18(4): 269-280, (2015)
  12. Pingfang Hu, Qiushi Hu, Yaolin Lin, Wei Yang, Lu Xing,Energy and exergy analysis of a ground source heat pump system for a public building in Wuhan, China under different control strategies, Energy and Buildings, 152: 301-312, (2017)
  13. Lei Xia, Zhenjun Ma, Craig McLauchlan, Shugang Wang, Experimental investigation and control optimization of a ground source heat pump system, Applied Thermal Engineering, 127: 70-80,