Journals / Electrica / 2021 / Cilt: 21 - Sayı: 1

Installation of a Sen Transformer in a Loop Distribution System for Line Loss Minimization by Loop Current Elimination

Journal
Electrica
Pages
85–95
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

Validation of the present work has been done by the simulating loop distribution system with an ST and the loop current is eliminated to address the line loss minimization problem with two different control schemes, line voltage compensation scheme (LVCS) and line inductance compensation scheme (LICS).

📌 3 Key Takeaways

🎯
Objective & Hypothesis:A loop distribution system is mostly preferred in the distribution network rather than the radial one for reliable power and satisfaction of the customers with comparably less power loss.
📊
Key Findings & Data:This paper proposes a method to achieve line loss minimization by installing a “Sen” Transformer (ST) in a loop distribution system.
💡
Conclusion & Impact:Validation of the present work has been done by the simulating loop distribution system with an ST and the loop current is eliminated to address the line loss minimization problem with two different control schemes, line voltage compensation scheme (LVCS) and line inductance compensation scheme (LICS).
🔬Design:Research Article
📍Scope:Comprehensive Sample
⚙️Variables:Domain Parameters

Özet

A loop distribution system is mostly preferred in the distribution network rather than the radial one for reliable power and satisfaction of the customers with comparably less power loss. This paper proposes a method to achieve line loss minimization by installing a “Sen” Transformer (ST) in a loop distribution system. An ST works as a series voltage regulator or impedance regulator in the loop distribution system to address power quality issues with better economic impact by inserting the compensating voltage or virtual impedance in the line. In the present work, the use of an ST is proposed in the loop distribution system with two different control schemes for balanced power flow with a reduction in line loss. The total minimization in line loss can be obtained if the summation of the all voltage drop across the line inductor in the loop distribution system tends to be zero. The total reduction in line loss can be realized by installing the ST in the line that eliminates the circulating current by injecting the compensating voltage. Validation of the present work has been done by the simulating loop distribution system with an ST and the loop current is eliminated to address the line loss minimization problem with two different control schemes, line voltage compensation scheme (LVCS) and line inductance compensation scheme (LICS).

🔖

Cite This Article

PATEL, D., CHOWDHURY, A. (2021). Installation of a Sen Transformer in a Loop Distribution System for Line Loss Minimization by Loop Current Elimination. Electrica, Cilt: 21 - Sayı: 1, 85–95. https://ajindex.com/articles/198012

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (1)

  1. A. Sallam, O. Malik, “Distribution System Planning”, in Electric Distribution Systems, IEEE, 2019, pp. 23-39. [CrossRef] 2. M. M. Adibi, “An Expert System Operational Aid for Restoration and Loss Reduction of Distribution Systems”, in Power System Restoration: Methodologies & Implementation Strategies, IEEE, 2000, pp. 584-590. 3. R. Saino, T. Takeshita, N. Izuhara, F. Ueda, “Power flow estimation and line-loss-minimization control using UPFC in loop distribution system”, 2009 IEEE 6th International Power Electronics and Motion Control Conference, Wuhan, 2009, pp. 2426-2431. [CrossRef] 4. M. A. Sayed, T. Takeshita, “All Nodes Voltage Regulation and Line Loss Minimization in Loop Distribution Systems Using UPFC”, in IEEE Transactions on Power Electronics, vol. 26, no. 6, pp. 1694- 1703, June, 2011. [CrossRef] 5. Z. Zhi-hua, X. Bing-yin, C. Qing, “Research on the optimal Power Flow Control method of the closed-loop distribution network with UPFC”, IEEE PES Innovative Smart Grid Technologies, Tianjin, 2012, pp. 1-3. [CrossRef] 6. M. A. Sayed, T. Takeshita, “Line Loss Minimization in Isolated Substations and Multiple Loop Distribution Systems Using the UPFC,” in IEEE Transactions on Power Electronics, vol. 29, no. 11, pp. 5813- 5822, Nov. 2014. [CrossRef] 7. P. Song, Z. Xu, H. Dong, H. Cai, Z. Xie, “Security-constrained line loss minimization in distribution systems with high penetration of renewable energy using UPFC”, in Journal of Modern Power Systems and Clean Energy, vol. 5, no. 6, pp. 876-886, Nov. 2017. [CrossRef] 8. K. K. Sen, M. L. Sen, “Introducing the family of “Sen” transformers: a set of power flow controlling transformers”, IEEE Power Engineering Society Summer Meeting,, Chicago, IL, USA, 2002, pp. 486 vol.1-. [CrossRef] 9. K. K. Sen, M. L. Sen, “Comparison of the ‘Sen’ transformer with the unified power flow controller”, 2003 IEEE Power Engineering Society General Meeting (IEEE Cat. No.03CH37491), Toronto, Ont., 2003, pp. 2577-2577. 10. O. Faruque, V. Dinavahi, “A tap-chaging algorithm for the implementation of “Sen” transformer”, 2008 IEEE Power and Energy Society General Meeting - Conversion and Delivery of Electrical Energy in the 21st Century, Pittsburgh, PA, 2008, pp. 1-1. [CrossRef] 11. K. K. Sen, M. L. Sen, “SMART Power Flow Controller for smarter grid applications”, 2015 IEEE Power & Energy Society General Meeting, Denver, CO, 2015, pp. 1-5. [CrossRef] 12. K. K. Sen, M. L. Sen, “Comparison of operational characteristics between a Sen