Objective & Hypothesis:In this paper, based on the theory of traveling waves, the fault distances on long transmission lines with various series-compensation levels are determined using transient current and voltage frequencies.
📊
Key Findings & Data:A fast Fourier transform is used for frequency-domain conversion and fault location is estimated from the frequencies of fault-generated harmonics in the transient spectrum.
💡
Conclusion & Impact:The effects of the compensation level, fault resistance, and phase angle are investigated.
🔬Design:Modeling & Simulation
📍Scope:Comprehensive Sample
⚙️Variables:Fault location estimation · traveling waves · series compensation

Abstract

In this paper, based on the theory of traveling waves, the fault distances on long transmission lines with various series-compensation levels are determined using transient current and voltage frequencies. Transmission lines with series compensation are modeled using Alternative Transients Program software with frequency-dependent effects on the line included in the simulation. The transient current and voltage signals are obtained from the model. A fast Fourier transform is used for frequency-domain conversion and fault location is estimated from the frequencies of fault-generated harmonics in the transient spectrum. The algorithm is implemented in MATLAB. To investigate the effect of compensation on accuracy, the results are obtained for different series-compensation levels. The undesirable source-inductance effect is removed and estimation accuracy is further improved using a waveform-relaxation method. The method is found to be successful in determining fault location on series-compensated transmission lines. The effects of the compensation level, fault resistance, and phase angle are investigated.

🔖

Cite This Article

AKMAZ, D., MAMİŞ, M. S., ARKAN, M., TAĞLUK, M. E. (2017). Fault location determination for transmission lines with different series-compensation levels using transient frequencies. Turkish Journal of Electrical Engineering and Computer Science, Cilt: 25 - Sayı: 5, 3764–3775. https://ajindex.com/articles/186995