Seasonal Performance Evaluation of an Earth-to-Air Heat Exchanger for Greenhouse Cooling under Humid Tropical Conditions

Nemli Tropikal Koşullar Altında Sera Soğutması İçin Bir Toprak-Hava Isı Eşanjörünün Mevsimsel Performans Değerlendirmesi

Pages
30–40
Publication Date
2026-07-31
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

Results showed consistent cooling throughout operation, with maximum temperature reductions of 3.1°C (dry season, 2 m) and 1.9°C (rainy season, 1 m).

📌 3 Key Takeaways

🎯
Objective & Hypothesis:This study evaluates the seasonal performance of an earth-to-air heat exchanger (EAHE) system for greenhouse cooling under humid tropical conditions in Ibadan, Nigeria.
📊
Key Findings & Data:Experiments were conducted at two burial depths (1 m and 2 m) during the dry and rainy seasons.
💡
Conclusion & Impact:Results showed consistent cooling throughout operation, with maximum temperature reductions of 3.1°C (dry season, 2 m) and 1.9°C (rainy season, 1 m).
🔬Design:Araştırma Makalesi
📍Scope:Comprehensive Sample
⚙️Variables:Toprak-Hava Isı Değiştiricisi · Sera soğutması · Kontrollü çevre tarımı

Abstract

This study evaluates the seasonal performance of an earth-to-air heat exchanger (EAHE) system for greenhouse cooling under humid tropical conditions in Ibadan, Nigeria. Experiments were conducted at two burial depths (1 m and 2 m) during the dry and rainy seasons. The EAHE comprised a 14.24 m polyvinyl chloride (PVC) pipe (inner diameter 101.6 mm) with a mass flow rate of 0.012 kg/s driven by a 0.25 m³/s inline centrifugal blower rated at 0.006 kW. Inlet and outlet temperatures were recorded every five minutes between 9:00 am and 5:00 pm using K-type thermocouples (range: −50°C to +180°C; accuracy: ±1.5°C). Data were analysed to determine the coefficient of performance and degree of cooling achieved. Results showed consistent cooling throughout operation, with maximum temperature reductions of 3.1°C (dry season, 2 m) and 1.9°C (rainy season, 1 m). Paired sample t-tests confirmed statistically significant differences between inlet and outlet air temperatures at both depths in both seasons (p < 0.05). COP values were higher in the dry season (4.5 at 1 m; 5.3 at 2 m) than in the rainy season (2.4 at 1 m; 3.9 at 2 m), representing a 46–53% seasonal reduction. The 2 m installation consistently outperformed the 1 m installation (COP gain: +18% dry season; +62% rainy season); however, the additional excavation required for 2 m depth entails a higher initial cost, suggesting a trade-off between installation expenditure and long-term cooling efficiency that practitioners must weigh against local economic constraints. EAHE systems are effective for passive greenhouse cooling in humid tropical climates, with deeper installation offering superior seasonal resilience.

Özet

Bu çalışma, Nijerya, Ibadan'daki nemli tropikal koşullar altında bir seranın soğutulması için toprak-hava ısı değiştirici (EAHE) sisteminin mevsimsel performansını değerlendirmektedir. Deneyler, kuru ve yağışlı mevsimlerde iki gömme derinliğinde (1 m ve 2 m) gerçekleştirilmiştir. EAHE, 0,012 kg/s kütle akış hızına sahip, 14,24 m uzunluğunda polivinil klorür (PVC) borudan (iç çap 101,6 mm) oluşmakta olup, hava akışı, 0,006 kW gücünde 0,25 m³/s'lik bir hat içi santrifüj fan tarafından sağlanmıştır. Giriş ve çıkış sıcaklıkları, sabah 9:00 ile akşam 5:00 arasında her beş dakikada bir, K tipi termokupllar (aralık: -50°C ila +180°C; doğruluk: ±1,5°C) kullanılarak kaydedilmiştir. Veriler, performans katsayısını (COP) ve elde edilen soğutma derecesini belirlemek için analiz edilmiştir. Sonuçlar, tüm çalışma boyunca tutarlı soğutma olduğunu ve maksimum sıcaklık düşüşlerinin 3,1°C (kuru mevsim, 2 m) ve 1,9°C (yağışlı mevsim, 1 m) olduğunu göstermiştir. Eşleştirilmiş örneklem t-testleri, her iki derinlikte ve her iki mevsimde giriş ve çıkış hava sıcaklıkları arasında istatistiksel olarak anlamlı farklar olduğunu doğrulamıştır (p < 0,05). COP değerleri, kuru mevsimde (1 m'de 4,5; 2 m'de 5,3) yağışlı mevsime göre (1 m'de 2,4; 2 m'de 3,9) daha yüksek bulunmuş olup, bu %46-53 oranında mevsimsel bir azalmayı temsil etmektedir. 2 m'lik tesisat, 1 m'lik tesisata kıyasla tutarlı bir şekilde daha iyi performans göstermiştir (COP kazancı: kuru mevsimde +%18; yağışlı mevsimde +%62); bununla birlikte, 2 m derinlik için gerekli olan ek kazı, daha yüksek bir ilk yatırım maliyeti gerektirmekte olup, bu durum, uygulayıcıların yerel ekonomik kısıtlamaları göz önünde bulundurarak tesisat harcamaları ile uzun vadeli soğutma verimliliği arasında bir denge kurmaları gerektiğini işaret etmektedir. EAHE sistemleri, nemli tropikal iklimlerde pasif sera soğutması için etkilidir ve daha derin tesisat üstün mevsimsel direnç sunmaktadır.

🔖

Cite This Article

Asiru, A., Akpenpuun, T. D., Omobowale, M., Mijinyawa, Y. (2026). Seasonal Performance Evaluation of an Earth-to-Air Heat Exchanger for Greenhouse Cooling under Humid Tropical Conditions. European Journal of Engineering and Applied Sciences, Cilt: 9 Sayı: 1, 30–40. https://doi.org/10.55581/ejeas.1897836

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (24)

  1. Boulard, T., & Wang, S. (2000). Greenhouse crop transpiration simulation from external climate conditions. Agricultural and Forest Meteorology, 100(1), 25–34. https://doi.org/10.1016/S0168-1923(99)00135-0
  2. Kumar, R., Kaushik, S. C., & Garg, S. N. (2009). Heating and cooling potential of an earth-to-air heat exchanger using artificial neural network. Renewable Energy, 34(1), 212–217. https://doi.org/10.1016/j.renene.2008.04.031
  3. Fatnassi, H., Boulard, T., Demrati, H., Bouirden, L., & Sappe, G. (2003). Ventilation performance of a large greenhouse equipped with insect-proof nets. Biosystems Engineering, 85(1), 97–107. https://doi.org/10.1016/S1537-5110(03)00035-0
  4. Olanrewaju, O. O., & Akinbile, C. O. (2020). Climate change and food security in Sub-Saharan Africa: Implications for greenhouse crop production. Scientific African, 7, Article e00243. https://doi.org/10.1016/j.sciaf.2019.e00243
  5. Akpenpuun, T. D., Ogunlowo, Q. O., Rabiu, A., Adesanya, M. A., Na, W. H., Omobowale, M. O., Mijinyawa, Y., & Lee, H. W. (2022). Building energy simulation model application to greenhouse microclimate, covering material and thermal blanket modelling: A review. Nigerian Journal of Technological Development, 19(3), 276–286. https://doi.org/10.4314/njtd.v19i3.10
  6. Tiwari, G. N. (2003). Greenhouse technology for controlled environment. Alpha Science International.
  7. Jain, D., & Tiwari, G. N. (2002). Modeling and optimal design of evaporative cooling system in controlled environment greenhouse. Energy Conversion and Management, 43(16), 2235–2250. https://doi.org/10.1016/S0196-8904(01)00164-6
  8. Akpenpuun, O., Ogunlowo, Q., Na, W., Rabiu, A., Adesanya, M., Dutta, P., Zakir, E., Ogundele, O., Kim, H., & Lee, H. (2023). Review of temperature management strategies and techniques in the greenhouse microenvironment. Adeleke University Journal of Engineering and Technology, 6(2), 126–147.
  9. Muller, N., Delgado, J. M. P. Q., & De Freitas, V. P. (2017). Greenhouse cooling technologies: An overview of greenhouse microclimate and cooling methods in tropical and arid climates. Renewable and Sustainable Energy Reviews, 75, 51–60. https://doi.org/10.1016/j.rser.2016.10.059
  10. Mongkon, S., Thepa, S., Namprakai, P., & Pratinthong, N. (2013). Cooling performance and condensation evaluation of horizontal earth tube system for the tropical greenhouse. Energy and Buildings, 66, 104–111. https://doi.org/10.1016/j.enbuild.2013.07.007
  11. Bisoniya, T. S. (2015). Design of earth–air heat exchanger system. Energy and Buildings, 86, 214–222. https://doi.org/10.1016/j.enbuild.2014.09.078
  12. Misra, R., Bansal, V., Agarwal, G. D., Mathur, J., & Aseri, T. K. (2013). Thermal performance investigation of hybrid earth air tunnel heat exchanger. Energy and Buildings, 49, 531–535. https://doi.org/10.1016/j.enbuild.2012.03.001
  13. Chel, A., & Tiwari, G. N. (2010). Thermal performance and embodied energy analysis of a passive house–case study of an Indian traditional house. Applied Energy, 86(10), 1956–1969. https://doi.org/10.1016/j.apenergy.2008.12.033
  14. Agrawal, K. K., Misra, R., & Bansal, N. K. (2018). Experimental investigation of earth–air heat exchanger performance in hot and arid climates. Energy and Buildings, 176, 164–173. https://doi.org/10.1016/j.enbuild.2018.07.042
  15. Cuny, M., Lartigue, B., & Berthier, F. (2019). Seasonal performance of earth-to-air heat exchangers in temperate climate: Impact of soil moisture. Renewable Energy, 132, 899–910. https://doi.org/10.1016/j.renene.2018.08.046
  16. Wei, X., Zhang, L., & Zhao, J. (2020). Quantification of latent and sensible cooling in earth-to-air heat exchangers under varying climatic conditions. Applied Thermal Engineering, 165, Article 114544. https://doi.org/10.1016/j.applthermaleng.2019.114544
  17. Pakari, A., & Ghani, S. (2021). Parametric analysis of earth-to-air heat exchangers: Depth, length, and diameter effects on system performance. Energy Reports, 7, 1573–1585. https://doi.org/10.1016/j.egyr.2021.02.002
  18. Hsu, C. T., Cheng, T. C., & Lee, Y. H. (2020). Performance of deep-buried earth-to-air heat exchangers for building cooling in hot climates. Energy and Buildings, 211, Article 109803. https://doi.org/10.1016/j.enbuild.2020.109803
  19. Nwaokoro, A. N. & Nymphas, E. F. (2019). Seasonal variations in soil thermal properties in humid tropical climates of West Africa. Journal of Agricultural Engineering and Technology, 27(1): 21-30.
  20. Odesola, I. F., & Onyebuchi, O. (2009). Greenhouse climate control: Comparison of natural ventilation and evaporative cooling. Renewable Energy, 34(10): 2235-2243. DOI: 10.1016/j.renene.2009.02.011
  21. Ayodele, T. R. & Ogunjuji, L. A. O. (2015). Cooling strategies for greenhouse crop production in hot climates: A review. Agricultural Engineering International: CIGR Journal. 17(3): 1-15.
  22. Asiru, A. A., Omobowale, M., Akpenpuun, T. D., Mijinyawa, Y., & Adesanya, M. A. (2026). Sustainable Cooling Solutions for Greenhouses under Humid Tropical Climate: A Preliminary Study of a Ground-to-Air Heat Exchanger Cooling System. Research in Agricultural Sciences, 57(1), 57-64.
  23. Zajch, A., Gough, W. A., and Yoon, G. 2020. Influence of daily temperature behavior on earth-air heat exchangers: A case study from Aichi, Japan. City and Environment Interactions, 8, 100054. https://doi.org/10.1016/j.cacint.2020.100054
  24. Donde, S., & Maurya, R. (2021). Characterizing soil’s thermal property for earth air heat exchanger through experiment. Materials Today: Proceedings, 51, 1516-1520. https://doi.org/10.1016/j.matpr.2021.10.311.