Journals / Isı Bilimi ve Tekniği Dergisi / 2014 / Cilt: 34 - Sayı: 2

Thermodynamic Analysis of Expander Usage in Two Stage-Transcritical R744 Cooling Systems

Çift Kademeli Transkritik R744 Soğutma Sistemlerinde Genleşme Türbini Kullanımının Termodinamik Analizi

Pages
91–97
Publication Date
2014-06-01
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

Additionally, it is emphasized that there could be an optimum evaporation temperature concept, and the general approach for calculation of inter-stage pressure is a wrong practice for cycle efficiency

📌 3 Key Takeaways

🎯
Objective & Hypothesis:In this study, difference of the expansion valve and expander usage in two-stage, transcritical R744 (CO2) refrigeration cycle was analyzed thermodynamically.
📊
Key Findings & Data:By using expander instead of expansion valve in the cycle, COP and second law efficiency values increase 10% averagely.
💡
Conclusion & Impact:Additionally, it is emphasized that there could be an optimum evaporation temperature concept, and the general approach for calculation of inter-stage pressure is a wrong practice for cycle efficiency
🔬Design:Research Article
📍Scope:Comprehensive Sample
⚙️Variables:R744 · genleşme türbini · transkritik soğutma çevrimi

Abstract

In this study, difference of the expansion valve and expander usage in two-stage, transcritical R744 (CO2) refrigeration cycle was analyzed thermodynamically. Variable parameters on this study are gas cooler pressure, interstage pressure and evaporation temperature of refrigerant. Isentropic efficiency of the compressor is calculated by an empirical equation. COP and second law efficiency values of cycles are obtained by parametrical analysis. By using expander instead of expansion valve in the cycle, COP and second law efficiency values increase 10% averagely. Additionally, it is emphasized that there could be an optimum evaporation temperature concept, and the general approach for calculation of inter-stage pressure is a wrong practice for cycle efficiency

Özet

İki kademeli transkritik (kritik nokta üstü) R744 (CO2) soğutma çevriminde, genleşme valfi ve genleşme türbini kullanımının farklılığı termodinamik açıdan analiz edilmiştir. Çalışmada değişken parametreler gaz soğutucu basıncı, ara kademe basıncı ve soğutkanın buharlaşma sıcaklığıdır. Kompresörün izentropik verimi bir ampirik ifade ile hesaplanmıştır. Çevrimlerin COP ve ikinci yasa verimleri parametrik analizler ile elde edilmiştir. Çevrimde genleşme valfi yerine genleşme türbini kullanmak ile çevrimin COP ve ikinci yasa verimleri ortalama %10 artış göstermiştir. Ayrıca çevrim için bir optimum buharlaşma sıcaklığı kavramının olabileceği ve ara kademe basıncının hesaplanmasında kullanılan genel bir yaklaşımın, çevrim verimliliği için hatalı bir uygulama olacağı vurgulanmıştır

🔖

Cite This Article

BAYRAKÇI, H. C., ÖZGÜR, A. E., ALAN, A. (2014). Thermodynamic Analysis of Expander Usage in Two Stage-Transcritical R744 Cooling Systems. Isı Bilimi ve Tekniği Dergisi, Cilt: 34 - Sayı: 2, 91–97. https://ajindex.com/articles/133419