Journals / Isı Bilimi ve Tekniği Dergisi / 2018 / Cilt: 38 - Sayı: 1

EXPERIMENTAL STUDY OF SINGLE-PHASE FLUID FLOW AND HEAT TRANSFER CHARACTERISTICS IN RECTANGULAR MICROCHANNELS

DİKDÖRTGENSEL MİKROKANALLARDA TEK FAZLI AKIŞKAN AKIŞI VE ISI TRANSFERİ KARAKTERİSTİKLERİNİN DENEYSEL İNCELENMESİ

Pages
65–72
Publication Date
2018-04-30
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

It is disclosed that increasing AR increases Nusselt number while decreasing the friction factor.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:In this study, single-phase laminar flow of deionized water through microchannel heat sinks is investigated experimentally.
📊
Key Findings & Data:Three different channel geometries with different aspect ratio (AR = 1.22, 0.82 and 0.37) but with the same hydraulic diameter (100 μm) are considered.
💡
Conclusion & Impact:It is disclosed that increasing AR increases Nusselt number while decreasing the friction factor.
🔬Design:Research Article
📍Scope:Comprehensive Sample
⚙️Variables:Mikrokanal · tek faz · laminer

Abstract

In this study, single-phase laminar flow of deionized water through microchannel heat sinks is investigated experimentally. Heat sinks including twenty-nine parallel rectangular channels have been used as the test samples. Three different channel geometries with different aspect ratio (AR = 1.22, 0.82 and 0.37) but with the same hydraulic diameter (100 μm) are considered. A constant heating power of 9 W is applied to the test section. The range of Reynolds number varies from 12.3 to 47.3. It is disclosed that increasing AR increases Nusselt number while decreasing the friction factor.

Özet

Bu çalışmada, deiyonize suyun mikrokanallı ısı alıcılardaki tek fazlı laminer akışı deneysel olarak incelenmiştir. Yirmi dokuz paralel dikdörtgensel kanallı ısı alıcılar test numuneleri olarak kullanılmıştır. Aynı hidrolik çapa (100 μm) fakat farklı boyut oranlarına sahip (AR = 1.22, 0.82 and 0.37) üç farklı kanal geometrisi dikkate alınmıştır. Test bölgesine, 9 W olacak şekilde sabit bir ısıtma gücü uygulanmıştır. Reynolds sayısı 12.3 ile 47.3 arasında değişmektedir. Artan AR değerlerinin Nusselt sayısını artırdığı ve sürtünme faktörünü azalttığı görülmüştür.

🔖

Cite This Article

MARKAL, B., AYDIN, O., AVCI, M. (2018). EXPERIMENTAL STUDY OF SINGLE-PHASE FLUID FLOW AND HEAT TRANSFER CHARACTERISTICS IN RECTANGULAR MICROCHANNELS. Isı Bilimi ve Tekniği Dergisi, Cilt: 38 - Sayı: 1, 65–72. https://ajindex.com/articles/133314

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (5)

  1. Dai B., Li M., Dang C., Ma Y. and Chen Q., 2014, Investigation on Convective Heat Transfer Characteristics of Single Phase Liquid Flow in Multi-Port Micro-Channel Tubes, Int. J. Heat Mass Transfer, 70, 114 – 118. Dey R., Das T. and Chakraborty S., 2012, Frictional and Heat Transfer Characteristics of Single-Phase Microchannel Liquid Flows, Heat Transfer Eng. 33, (4-5) 425- 446. Harms T.M., Kazmierczak, M.J. and Gerner F.M., 1999, Developing Convective Heat Transfer in Deep Rectangular Microchannels, Int. J. Heat Fluid Flow, 20 (8), 149 - 157. Hernando N.G., Iborra, A.A., Rivas U.R. and Izquierdo M., 2009, Experimental Investigation of Fluid Flow and Heat Transfer in a Single-Phase Liquid Flow Micro-Heat Exchanger, Int. J. Heat Mass Transfer, 52, 5433 – 5446. Herwig H. and Hausner O., 2003, Critical View on ‘‘New Results in Micro-Fluid Mechanics’’: an Example, Int. J. Heat Mass Transfer, 46, 935-937. Hrnjak P. and Tu X., 2007, Single Phase Pressure Drop in Microchannels, Int. J. Heat Fluid Flow, 28, 2-14.
  2. Incropera P.F., DeWitt P.D., Bergman L.T. and Lavine S.A., 2007, Fundamentals of heat and mass transfer, (Sixth Ed.), John-Wiley & Sons Inc, USA. Judy J., Maynes, D. and Webb B.W., 2002, Characterization of Frictional Pressure Drop for Liquid Flows Through Microchannels, Int. J. Heat Mass Transfer, 45, 3477 – 3489. Jung J.Y. and Kwak H.Y., 2008, Fluid Flow and Heat Transfer in Microchannels with Rectangular Cross Section, Heat Mass Transfer 44, 1041-1049. Kline S.J. and McClintock F.A., 1953, Describing Uncertainties in Single-Sample Experiments, Mech. Eng., 73 (1), 3–8.
  3. Lee P.S., Garimella S.V. and Liu D., 2005, Investigation of Heat Transfer in Rectangular Microchannels, Int. J. Heat Mass Transfer, 48, 1688-1704. Liu D. and Garimella S.V., 2004, Investigation of Liquid Flow in Microchannels, J. Thermophysics and Heat Transfer, 18 (1), 65 – 72. Markal B., Aydin, O. and Avci, M., 2016, Effect of Aspect Ratio on Saturated Flow Boiling in Microchannels, Int. J. Heat Mass Transfer, 93, 130-143.
  4. Mirmanto M., Kenning D.B.R., Lewis J.S. and Karayiannis T.G., 2012, Pressure Drop and Heat Transfer Characteristics for Single-Phase Developing Flow of Water in Rectangular Microchannels, Journal of Physics: Conference Series 395, 012085.
  5. Mokrani O., Bourouga B., Castelain C. and Peerhossaini H., 2009, Fluid Flow and Convective Heat Transfer in Flat Microchannels, Int. J. Heat Mass Transfer, 52, 1337 – 1352. Morini G.L., 2004, Single-Phase Convective Heat Transfer in M