Journals / Isı Bilimi ve Tekniği Dergisi / 2017 / Cilt: 37 - Sayı: 2

AN INDUSTRIAL VAPOR ABSORPTION AIR CONDITIONING APPLICATION

Pages
49–60
Publication Date
2017-10-31
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

It was found out that the flue gases had enough heat capacity to drive the VAR system.

📌 3 Key Takeaways

🎯
Objective & Hypothesis:In this study, the application of VAR system to an industrial company is investigated.
📊
Key Findings & Data:The COP of the VAR system is calculated to be 0.64 and the highest exergy destruction was obtained at the generator which is 37.19kW.
💡
Conclusion & Impact:It was found out that the flue gases had enough heat capacity to drive the VAR system.
🔬Design:Research Article
📍Scope:Comprehensive Sample
⚙️Variables:Absorption · Water-Lithium bromide solution

Özet

In this study, the application of VAR system to an industrial company is investigated. For this purpose, the company which requires an air-conditioning system to its office building was chosen. After determining this company had an industrial furnace, this research aimed to design the VAR system utilizing waste heat from this furnace flue gases to air-condition the office building. Firstly, the physical properties and heat quantity of the flue gases were determined and the cooling load of the office building was calculated. It was found out that the flue gases had enough heat capacity to drive the VAR system. Next, single effect VAR system was introduced and the thermodynamic, energy and exergy analysis were made. The COP of the VAR system is calculated to be 0.64 and the highest exergy destruction was obtained at the generator which is 37.19kW. Finally, the application of the VAR system to this industrial company was analyzed in detail. The capital, maintaining and operating costs of the VAR system were analyzed and compared with alternative systems.

🔖

Cite This Article

KURTULMUŞ, N., HORUZ, İ. (2017). AN INDUSTRIAL VAPOR ABSORPTION AIR CONDITIONING APPLICATION. Isı Bilimi ve Tekniği Dergisi, Cilt: 37 - Sayı: 2, 49–60. https://ajindex.com/articles/133273

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (7)

  1. Balaji K. and Ramkumar R., 2012, Study of waste heat recovery from steam turbine xhaust for vapour absorption system in sugar industry, Procedia Engineering, 38, 1352-1356
  2. Chen Q., Han W., Zheng J., Sui J. and Jin H., 2014, The exergy and energy level analysis of a combined cooling, heating and power system driven by a small scale gas turbine at off design condition, Applied Thermal Engineering, 66, 590-602
  3. Choudhury B., Chatterjee P.K. and Sarkar J.P., 2010, Review paper on solar-powered air-conditioning through adsorption route, Renewable and Sustainable Energy Reviews, 14, 2189-2195 Cosenza F. and Vliet G.C., 1990, Absorption in falling water/libr films on horizontal tubes, Conference Proceeding by ASHRAE, 96, 673-701 Çengel Y.A., 2002, Heat Transfer: A Practical Approach (Second edition), McGraw-Hill Davies J.T. and Rideal E.K., 1961,
  4. Interfacial phenomena, Academic Press, New York Dinçer I. and Rozen M., 2007, EXERGY: Energy, Environment and Sustainable Development, Elsevier science Elsafty A. and Al-Daini A.J., 2002, Economical comparison between a solar powered vapour absorption air-conditioning system and a vapour compression system in the Middle East, Renewable Energy, 25, 569-583 Garimella S., 2012, Low-grade waste heat recovery for simultaneous chilled and hot water generation, Applied Thermal Engineering, 42, 191-198 Genceli O.F., 1999,
  5. Heat exchangers, Birsen Publishing, İstanbul (in Turkish). Florides A.G., Kalogirou S.A., Tassou S.A. and Wrobel L.C., 2003, Design and construction of a LiBr-water absorption machine, Energy Conversion and Management, 44, 2483-2508 Horuz I., 1998, A comparison between ammonia-water and water-lithium bromide solutions in vapor absorption refrigeration systems, International Communications Heat Mass Transfer, 5, 711-721
  6. Kalkan N., Young E.A. and Celiktas A., 2012, Solar thermal air conditioning technology reducing the footprint of solar thermal air conditioning, Renewable and Sustainable Energy Reviews, 16, 6352-6383 Kaynakli O. and Kilic M., 2007, Theoretical study on the effect of operating conditions on performance of absorption refrigeration system, Energy Conversion and Management, 48, 599-607
  7. Kaynaklı O., Saka K. and Kaynakli F.,2015, Energy and exergy analysis of a double effect absorption refrigeration system based on different heat sources, Energy Conversion and Management, 106, 21-30 Kaita Y., 2001, Thermodynamic properties of lithium bromide-water solutions at high temperatures, International Journal o