AI InsightThe decrement factor (μ) should be at least 0,25 - 0,35 and the time- lag (ɸ) 3-4 hours on the roof for the tropic days (T a ≥ 30°C).
📌 3 Key Takeaways
Abstract
The aim of this study was to investigate the effect of insulation levels on periodic heat flow through the building components, on the decrement factor (μ) and on the time-Lag (ɸ) in the tropic days (T a ≥ 30°C) . At the poultry buildings, the decrement factor (μ) on the roof was found with adequate roof insulation as 0,27 - 0.34 and the time-lag (ɸ) as 2- 3 hours, without roof insulation as 0,91 - 0,97 and the time-lag (ɸ) as 0-35 minutes. The decrement factor (μ) of the walls was 0,42 - 0,95 and the time- lag (ɸ) was 0-4 hours. The decrement factor (μ) should be at least 0,25 - 0,35 and the time- lag (ɸ) 3-4 hours on the roof for the tropic days (T a ≥ 30°C).
Özet
Araştırma, tropik günlerde (yüksek sıcaklık ≥ 30°C) yapı malzemelerinin ve yalıtım düzeylerinin; yapı elemanlarındaki periyodik ısı akımına, azalan ısı kazancı miktarına (sönüm faktörü, μ), ısı geçişini geciktirmeye (zaman gecikmesi, ɸ ) olan etkisinin belirlemesi amacı ile yapılmıştır. Çatı örtüsü yalıtımı yeterli sayılan kümeslerde çatıdaki sönüm faktörü (μ) 0.27 - 0.34, zaman gecikmesi (ɸ) 2.00 ' - 3.00', çatı örtüsü yalıtımsız olan kümeste ise, çatıdaki sönüm faktörü (μ) 0.91 - 0.97, zaman gecikmesi (ɸ ) 0.00' - 0.35' olarak hesaplanmıştır. Duvarlar için, sönün faktörü (μ) 0.42 - 0.95, zaman gecikmesi 0.00'- 4.00' arasında bulmuştur. Tropik günler için (yüksek sıcaklık ≥ 30°C) çatıda sağlanması gereken sönüm faktörü (μ) 0.25 - 0.35, zaman gecikmesi (ɸ) 3.00 ' - 4.00' olmalıdır.