Journals / Mediterranean Agricultural Sciences / 2088 / Volume: 1 Issue: 2

The Effect of lnsulation on Periodic Heat Flow Through the Poultry Building Components

Kümes Yapı Elemanlarındaki Periyodik Isı Akımına Yalıtım Düzeylerinin Etkisi

Pages
87–107
Publication Date
1988-12-01
DOI
—
🏛️Bibliographic metadata and full text access for this article are provided via DergiPark.
DergiPark Record ↗
✨

AI Summary & Key Takeaways

AI Insight
⚡ TL;DR(Too Long; Didn't Read)

The decrement factor (μ) should be at least 0,25 - 0,35 and the time- lag (ɸ) 3-4 hours on the roof for the tropic days (T a ≥ 30°C).

📌 3 Key Takeaways

🎯
Objective & Hypothesis:The aim of this study was to investigate the effect of insulation levels on periodic heat flow through the building components, on the decrement factor (μ) and on the time-Lag (ɸ) in the tropic days (T a ≥ 30°C) .
📊
Key Findings & Data:At the poultry buildings, the decrement factor (μ) on the roof was found with adequate roof insulation as 0,27 - 0.34 and the time-lag (ɸ) as 2- 3 hours, without roof insulation as 0,91 - 0,97 and the time-lag (ɸ) as 0-35 minutes.
💡
Conclusion & Impact:The decrement factor (μ) should be at least 0,25 - 0,35 and the time- lag (ɸ) 3-4 hours on the roof for the tropic days (T a ≥ 30°C).
🔬Design:Araştırma Makalesi
📍Scope:Comprehensive Sample
⚙️Variables:Kümes · Isı Akımı · decrement factor

Abstract

The aim of this study was to investigate the effect of insulation levels on periodic heat flow through the building components, on the decrement factor (μ) and on the time-Lag (ɸ) in the tropic days (T a ≥ 30°C) . At the poultry buildings, the decrement factor (μ) on the roof was found with adequate roof insulation as 0,27 - 0.34 and the time-lag (ɸ) as 2- 3 hours, without roof insulation as 0,91 - 0,97 and the time-lag (ɸ) as 0-35 minutes. The decrement factor (μ) of the walls was 0,42 - 0,95 and the time- lag (ɸ) was 0-4 hours. The decrement factor (μ) should be at least 0,25 - 0,35 and the time- lag (ɸ) 3-4 hours on the roof for the tropic days (T a ≥ 30°C).

Özet

Araştırma, tropik günlerde (yüksek sıcaklık ≥ 30°C) yapı malzemelerinin ve yalıtım düzeylerinin; yapı elemanlarındaki periyodik ısı akımına, azalan ısı kazancı miktarına (sönüm faktörü, μ), ısı geçişini geciktirmeye (zaman gecikmesi, ɸ ) olan etkisinin belirlemesi amacı ile yapılmıştır. Çatı örtüsü yalıtımı yeterli sayılan kümeslerde çatıdaki sönüm faktörü (μ) 0.27 - 0.34, zaman gecikmesi (ɸ) 2.00 ' - 3.00', çatı örtüsü yalıtımsız olan kümeste ise, çatıdaki sönüm faktörü (μ) 0.91 - 0.97, zaman gecikmesi (ɸ ) 0.00' - 0.35' olarak hesaplanmıştır. Duvarlar için, sönün faktörü (μ) 0.42 - 0.95, zaman gecikmesi 0.00'- 4.00' arasında bulmuştur. Tropik günler için (yüksek sıcaklık ≥ 30°C) çatıda sağlanması gereken sönüm faktörü (μ) 0.25 - 0.35, zaman gecikmesi (ɸ) 3.00 ' - 4.00' olmalıdır.

🔖

Cite This Article

Mutaf, S., Tığlı, R. (1988). The Effect of lnsulation on Periodic Heat Flow Through the Poultry Building Components. Mediterranean Agricultural Sciences, Volume: 1 Issue: 2, 87–107. https://ajindex.com/articles/1170982

📄 Full Text PDF Viewer

📄

PDF görüntüleyici hazırlanıyor...

References (25)

  1. Adam, M., 1979. Untersuchungen über.Warmetechnisches Verhalten der raumunschlissenden Bauteile intensiv belüfteter Stille. Universitat Hohenheim, Institut für Agrartechnik (MEG) Dissertation.
  2. Borchert, K.L., 1967. Wamedamnung und Feuchtigkeitsschutz landuirtschaftlicher Gebaude-Bauphysik (Fast) ohne Zahlen. Sanderdruck aus der Zeitschrift "das Baugewerbe" Heft 1.
  3. Borchert, K.L., 1970. Die innere Oberflâchentemperature won Wanden, Decken und Fussböden als Kriterium der Warmedammung des Feuchtigkeitschutzes raumumschliessender Bauteile für Stallraume und Aufenthaltsaume für Menschen. Lancbaufoschung valkenrode, Sonderheft, 6.
  4. Candura, A. ve Gusman, A., 1980. Periodic Heat Flow Influence on Planning Criteria of Farm Building in Southern Italy. Working Session of the 2 nd. Technical Section of the CIGR s.317-324, Tanikon, Schweiz.
  5. Candura, A. ve Gusman, A., 1982. Test on a Traditional Building Subject to an Intense Solar Radiation to be Used as Animals Shelter. Working Session Of the 2 nd Section of the CIGR, s.385-410, Braunschweig, Deutschland.
  6. Egan, D. M., 1975. Consep in Thermal Comfort. Printice - Hall, Inc. Englewood Clifs, New Jersey.
  7. Eichler, F., 1970. Bauphysikalische Entmurfslehre, Band l.Verlagsgsselschaft Rudolf Müller Köln - Braunsfeld.
  8. Esmay, M.L., 1982. Principles of Animal Enuironment. The Avi Publishing Company, Inc. Westport, Connecticut.
  9. Hatem, M.H.H., 1980. Untersuchungen über das wartnetechnische Verhalten von Baukonstruktionen für Stalle unter agyptischen verhaltnissen mit besonderer Berücksichtigung der Geflügelhaltung. Universitat Hohenheim, Institut für Agrartechnik (MEG) Dissertation.
  10. Hellickson, M.L. ve Chen, C.F., 1987. Simulated and Tested Performance of a Rockbed Heat Sink for Cooling Sumner Ventilation Air. Transaction of the ASAE, Vol, 30 (1) s.207-214.
  11. Janac, K., 1966. Grundsatze für don Entwurf von Viehstallen unter Beachtung der warmetechnischen Forderungen im Hinblick auf die Winter - und Sommer- verhaltnisse. ALB - Berichtsheft 28.
  12. Koenigsberger, O.H., Ingersoll, T.C., Mayhew, A., Szakolay, S.V., 1978. Manual of Tropical Housing and Building. Part 1, Climatic Design. Longman Group Limited. London.
  13. Marsden, A. ve Marris, T.R., 1987. Quantative Review of the Effects of Environmental Temperature on Food Intake, Egg Output and Energy Balance in Laying Puliets. British Poultry Science, vol. 26, s.693-704.
  14. Moritz, K., 197D. Richtig und Falsch im Warmeschutz, Feuchtigkeitschutz, Bautenschutz. Bauenverlag GMBH Wiesbaden, Berlin.
  15. Mutaf, S., 1980. Buharlaşma ile Serinletmenin Kümes içi İklimsel Çevre Koşullarına Etkisi. E.Ü.Zir.Fak.Yay. No:341, Bomova-lzmir.
  16. Mutaf, S., 1932. Economic Aspects of Environmental Control in Poultry Houses. International Scientific Poultry Congres, 24-25 Play, s.73-87, Ankara.
  17. Mutaf, S., 1986. Değişik Yapı ve Yalıtım Malzemelerinin Kümes içi İklimsel Çevre Koşullarına Etkisi. II.Ulusal Kültürteknik Kongresi. Ç.Ü.Ziraat Fak. Kültürteknik Bölümü. S.803-817, Adana.
  18. Mutaf, S., Özmerzi, A., Tığlı, R., 1988. Kümeslerde Yapı Elemanları İç Yüzey Sıcaklıkları ile Etkin Sıcaklık Arasındaki İlişkiler. III.Ulusal Kültürteknik Kongresi. E.ü.Kültür Merkezi, İzmir (Baskıda).
  19. Otto, J., 1963. Messung der oberflachentemperaturen an Bauteilen eines Hühnerstalles ınd Berechnungen der Warmeabstrahlung. Banyerisches Landwirtschaftliches Jahrbuch, 40. Jahrgang Heft 1, s.98-127.
  20. Petit, K.L. ve Nikolaus, A., 1966. Die Rolle der thermischen Kapazitat der Wande in Viehstallen. Vortrag wahrend der Sitzung der Cembureau Arbeitsgruppe Beton in der Landwirtschaft, Lausonne 26-28 April. *
  21. Rietschel, H. ve Raiss, W., 1970. Heiz und Klimatechnik. 15 Aufl. von Raiss Springerverlag, Berlin - Heidelberg - New York.
  22. Sieler, K., 1967. Massnahmen zur Beeinflussung des Stallklimas im Sommer. ALB- Bericht Nr. 33, s.35-47.
  23. Van Kampen, M., 1978. Effect of Drinking Water Temperature and Leg Cooling on Heat Stress of LAying Hens (Callus Domesticus) Journal of Thermal Biology vol. 13, No:l, s.43-47.
  24. Walker, P.N., Galis, E.A., Manbeck, H.B., Meyer, D.J., 1986. Wall Surface Heat Exchanger for Ventilation Air. American Society of Agricultural Engineers Vol 29 (2) s.565-570.
  25. Adam, M., 1979. Untersuchungen über.Warmetechnisches Verhalten der raumunschlissenden Bauteile intensiv belüfteter Stille. Universitat Hohenheim, Institut für Agrartechnik (MEG) Dissertation.